Haw. Code R. § 6-77-114

Current through April, 2024
Section 6-77-114 - Service lines: general requirements for connections to main piping
(a) Location. Each service-line connection to a main must be located at the top of the main or, if that is not practical, at the side of the main, unless a suitable protective device is installed to minimize the possibility of dust and moisture being carried from the main into the service line.
(b) Compression-type connection to main. Each compression-type service line to main connection must:
(1) Be designed and installed to effectively sustain the longitudinal pull-out or thrust forces caused by contraction or expansion of the piping, or by anticipated external or internal loading; and
(2) If gaskets are used in connecting the service line to the main connection fitting, have gaskets that are compatible with the kind of gas in the system.

Haw. Code R. § 6-77-114

[Eff ] (Auth: HRS § 269-6) (Imp: 49 C.F.R. §192.367, OCT 1, 1990)