Haw. Code R. § tit. 3, Building Code Council, State Fire Code, 64

Current through September, 2024
Positive alarm sequence occupant notification

Section 13.7.1.9.4 is amended to read as follows: 13.7.1.9.4 Where permitted by Chapter 11 through Chapter 43 of NFPA 101, a positive alarm sequence shall be permitted, provided that it is in accordance with NFPA 72. The following additional requirements shall also apply:

(1) An automatic fire sprinkler system installed in conformance with the building code shall be provided throughout the building or facility;
(2) Written fire emergency procedures and an evacuation plan for the building or facility shall be reviewed by the AHJ prior to approval testing. The procedures and plan shall include, but not be limited to immediate notification to the fire department, use of primary and secondary exits, use of fire protection appliances for the building(s) or facility(ies);
(3) Trained personnel shall respond to emergencies on a twenty-four hour basis. The staff shall be instructed in fire emergency procedures and the use and operation of in-house fire appliances. Documentation of such training shall be maintained and filed on the premises;
(4) Immediate notification of the fire department shall take place upon activation of any fire alarm initiating device;
(5) The AHJ shall conduct a test of the positive alarm sequence prior to implementation; and
(6) The AHJ may disapprove or rescind approval of the positive alarm sequence of the fire alarm system if all of the above requirements are not met and shall require the fire alarm system to be reprogrammed to meet a general alarm notification at the owner's expense.

Haw. Code R. tit. 3, Building Code Council, State Fire Code, 64

[Eff 1/19/2021]