Section 138 is amended to add as follows: Section 1381 Inspection, Testing, and Maintenance Label Other fire protection systems satisfactorily passing an inspection, testing, and maintenance test shall have an approved label affixed to the manual activation device or, if not present, actuator valve to the extinguishing agent The label shall, as a minimum, entail the following:
13.8.2 Hydrostatic Testing
Every twelve years from the date of manufacture, stored pressure extinguishing agent cylinders shall be hydrostatically tested.
13.8.3 Hydrostatic Testing Label. Stored pressure extinguishing agent cylinders satisfactorily passing a twelve-year hydrostatic test shall, as a minimum, have a label attached to the cylinder as follows:
13.8.4 The fire department shall be verbally notified immediately of any systems determined to be out of service. Systems that cannot be utilized for firefighting operations shall have an inoperable system sign affixed to the manual activation device. The sign shall remain in place until all repairs have been made and a satisfactory system test is completed.
13.8.5 Inspection, testing, and maintenance report. An inspection, testing, and maintenance report entitled "Foam Water Sprinkler System", "Other Fire Protection Systems" available on the State Fire Council's website and at each county fire department's fire prevention bureau, or a similar report approved by the AHJ shall be provided to the property owner or agent within fourteen days after the test.
13.8.6 Inspection Report. An electronic copy of the unsatisfactory test report shall be submitted to the AHJ within five working days. The AHJ shall determine if the submittal of a satisfactory test report will be required.
13.8.7 Table 13.2.3.4.3A entitled "Fire Protection Systems Reference Dates" may be used as a reference for applicable codes and standards in effect when the building was permitted.