IECC Section R401.2.1 is amended to read as follows:
R401.2.1 Tropical zone.Residential buildings in the tropical zone at elevations below 2,400 feet (731.5 m) above sea level shall be deemed to comply with this chapter where the following conditions are met:
1. Not more than one-half of the dwelling unit is air conditioned2. The dwelling unit is not heated.3. Solar, wind or other renewable energy source supplies not less than 90 percent of the energy for service water heating.4. Glazing in dwelling units shall have a maximum solar heat gain coefficient as specified in Table R402.1.2.5. Skylights in dwelling units shall have a max imum U-factor as specified in Table R402.l.4.6. Permanently installed lighting is in accordance with Section R404.7. The roof/ceiling complies with one of the following options: a. Comply with one of the roof surface options in Table C402.3 and install R-13 insulation or greater.b. Install R-19 insulation or greater.8. Roof surfaces have a minimum slope of 1/4 inch per foot of run. The finished roof does not have water accumulation areas.9. Operable fenestration provides ventilation area equal to not less than 14 percent of the floor area in each room. Alternatively, equivalent ventilation is provided by a ventilation fan.10. Bedrooms with exterior walls facing two different direction have operable fenestration or exterior walls facing two different directions.11. Interior doors to bedrooms are capable of being secured in the open position.12. A ceiling fan or ceiling fan rough-in is provided for bedrooms and the largest space that is not used as bedroom.13. Walls, floors and ceilings separating air conditioned spaces from non-air conditioned spaces shall be constructed to limit air leakage in accordance with the requirements in Table R402.4.1.1. Haw. Code R. tit. 3, Building Code Council, State Energy Conservation Code, subch. 2, 18