Section 2104.1.3 is added to read as follows:
2104.1.3 " Cleanouts. Cleanouts shall be provided for all grout pours over 5 feet 4 inches in height. Special provisions shall be made to keep the bottom and sides of the grout spaces, as well as the minimum total clear area required by TMS 602 clean and clear prior to grouting. Exception: Cleanouts are not required for grout pours 8 feet or less in height providing all of the following conditions are met:
1. The hollow masonry unit is 8-inch nominal width or greater.2. The specified compressive strength of masonry, f'm, is less than or equal to 2,000psi as determined per TMS 602 Table 2;3. Fine grout is used complying with ASTM C-476 with a minimum compressive strength of 3,000 psi; and4. Special Inspection is provided". Haw. Code R. tit. 3, Building Code Council, State Building Code Council, Amendments to the 2018 ICC International Building Code (IBC), 43