Appendix W is added to read as follows:
"APPENDIX W
Hawaii Wind Design Provisions for New Construction
W101 Revisions to Chapter 2, Chapter 16 and Chapter 23.
Wind design shall be in accordance with this code as amended by Sections W101 through W109.
W102 Windborne Debris Region definition.
The definition of "Windborne Debris Region" in Section 202 is amended to read as follows:
"WIND-BORNE DEBRIS REGION. Areas in Hawaii where the basic design wind speed is 130 mph (63 m/s) or greater. For Risk Category II buildings and structures, the wind-borne debris region shall be based on Fig 1609.3 (5). For Risk Category III buildings and structures, the wind-borne debris region shall be based on Figure 16093(6). For Risk Category IV buildings, the windborne debris region shall be based on Fig 1609.3 (7)."
W103 Revised Notations for Section 1602
The following Notations are added to Section 1602: "Veff-asd= Effective allowable stress design wind speed, miles per hour (mph) (km/hr) where applicable, calculated per Section 160931, that includes the effect of the special Hawaii factors for topographic effects and directionality.
V = Basic design wind speeds, miles per hour (mph) (km/hr) determined from Figures 1609.3(1) through 1609.3(8) or ASCE 7 map for the Risk Category, applied to the strength design of the structure.
Vunt = Ultimate design wind speed miles per hour, (mph) (km/hr), of the region prior to any pressure calculation adjustments of topographic effects per Section 1609.3.2 or directionality effects per Section 1609.3.3."
W104 Wind design data.
Section 1603.1.4 is amended to read as follows:
W105 Amendments to Section 1609.1 through 1609.4
Sections 1609.1 through 1609.4 are amended to read as follows:
Buildings, structures and parts thereof shall be designed to withstand the minimum wind loads prescribed herein. Decreases in wind loads shall not be made for the effect of shielding by other structures.
Wind loads on every building or structure shall be determined in accordance with Chapters 26 to 30 of ASCE 7. Minimum values for Directionality Factor, Kd, Velocity Pressure Exposure Coefficient, Kz, and Topographic Factor, Kzt, shall be determined in accordance with Section 1609. The type of opening protection required, the basic design wind speed, V, and the exposure category for a site is permitted to be determined in accordance with Section 1609 or ASCE 7. Wind shall be assumed to come from any horizontal direction and wind pressures shall be assumed to act normal to the surface considered.
Exceptions:
The wind speeds in Figures 1609.3(1) through 1609.3(8) are basic design wind speeds, V, and shall be converted in accordance with Section 1609.3.1 to allowable stress design wind speeds, Veff-asd, when the provisions of the standards referenced in Exceptions 4 and 5 are used.
The provisions of ICC 600 are applicable only to buildings located within Exposure B or C as defined in Section 1609.4.
The prescriptive provisions of ICC 600, AWC WFCM, or AISI S230 shall not be permitted for either of the following cases:
In windborne debris regions, glazing in buildings shall be impact resistant or protected with an impact-resistant covering meeting the requirements of an approved impact-resistant standard or ASTM E1996 and ASTM E1886 referenced herein as follows:
Louvers protecting intake and exhaust ventilation ducts not assumed to be open that are located within 30 feet (9144 mm) of grade shall meet the requirements of AMCA 540.
The text of Section 6.2.2 of ASTM E1996 shall be substituted as follows:
Table 1609.2.2
Wind-Borne Debris Protection Fastening Schedule For Wood Structural Panels a,b,c,d
Fastener Type | Fastener Spacing | ||
Panel span [LESS THAN EQUAL TO] 4 feet | Panel span [GREATER THAN] 4 feet and [LESS THAN EQUAL TO] 6 feet | Panel span [GREATER THAN] 6 feet and [LESS THAN EQUAL TO] 8 feet | |
No. 8 Wood screw based anchor with 2 inch embedment length | 16" | 10" | 8" |
No. 10 Wood screw based anchor with 2-inch embedment length | 16" | 12" | 9" |
1/4 - inch lag screw based anchor with 2-inch embedment length | 16" | 16" | 16" |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 0.454 kg, 1 mile per hour = 1.609 km/h.
Garage door glazed opening protection for windborne debris shall meet the requirements of an approved impact-resisting standard of ANSI/DASMA 115.
The basic design wind speed, V, in mph, for the determination of the wind loads shall be determined by Figures 1609.3(1) through (8). The basic design wind speed, V, for use in the design of Risk Category II buildings and structures shall be obtained from Figures 1609.3(1) and 1609.3(5). The basic design wind speed, V, for use in the design of Risk Category III buildings and structures shall be obtained from Figures 1609.3(2) and 1609.3(6). The basic design wind speed, V, for use in the design of Risk Category IV buildings and structures shall be obtained from Figures 1609.3(3) and 1609.3(7). The basic design wind speed, V, for use in the design of Risk Category I buildings and structures shall be obtained from Figures 1609.3(4) and 1609.3(8).
The basic design wind speed, V, shown for Hawaii in Figures 1609.3(5) through 1609.3(8) include topographic effects near mountainous terrain and near gorges, and shall be used with a topographic factor Kzt of 1.0 and the directionality factors given in Table 26.6-1 of ASCE 7.
Alternatively, when determining wind loads using both the explicit topographic factors given in section 1609.3.2 and the explicit directionality factors of section 1609.3.3, the ultimate design wind speed, Vunt, in mph, without topographic effects shall be as follows:
Risk Category I buildings and structures: 115 mph
Risk Category II buildings and structures: 130 mph
Risk Category III buildings and structures: 145 mph
Risk Category IV buildings and structures: 153 mph
Where required, the basic design wind speeds of Figures 1609.3(1) through 1609.3(8), shall be converted to effective allowable stress design wind speeds, Veff-asd, using Table 1609.3.1 or Equation 16-33.
(Equation 16-33)
where:
Veff-asd = Effective Allowable stress design wind speed applicable to methods specified in Exceptions 4 and 5 of Section 1609.1.1 and for Section 2308.10.1.
V = Basic design wind speeds determined from Figures 1609.3(1) through 1609.3(8).
TABLE 1609.3.1
WIND SPEED CONVERSIONS a, b, c
V | 100 | 110 | 120 | 130 | 140 | 150 | 160 | 170 | 180 | 190 | 200 |
Veff-asd | 78 | 85 | 93 | 101 | 108 | 116 | 124 | 132 | 139 | 147 | 155 |
For SI: 1 mile per hour = 0.44 m/s.
Wind speed-up effects caused by topography shall be included in the calculation of wind loads by using the factor Kzt, where Kzt is given in Figures 1609.3.2(a) through 1609.3.2(f).
Exception:
Site-specific probabilistic analysis of directional Kzt based on windtunnel testing of topographic speed-up shall be permitted to be submitted for approval by the building official.
Basic design wind speed, V, is determined per Figures 1609.3(5) through 1609.3(8) that already include topographic effects near mountainous terrain and near gorges, which shall be used with a topographic factor Kzt of 1.0 and the directionality factors given in Table 26.6-1 of ASCE 7.
Figure 1609.3.2(a)
County of Hawaii Peak Gust Topographic FactorKzt
Figure 1609.3.2(b)
County of Maui, Island of Maui Peak Gust Topographic FactorKzt
Figure 1609.3.2(c)
County of Maui, Island of Molokai Peak Gust Topographic FactorKzt
Figure 1609.3.2(d)
County of Maui, Island of Lanai Peak Gust Topographic FactorKzt
Figure 1609.3.2(e)
City and County of Honolulu Peak Topographic FactorKztfor Building Heights up to 100 feeta,b
Interpolation is permitted.
Table 1609.3.3(e)2
Height Adjustment of Mapped Kzt Values at Sites with Ground Elevation Less than 500 feet
Building roof height above ground (ft) | [LESS THAN OR EQUAL TO]100 | 120 | 140 | 160 | 180 | 200 | 220 | [GREATER THAN OR EQUAL TO]240 |
Adjustment factor to Kzt [GREATER THAN OR EQUAL TO] 1.2 | 100% | 98% | 96% | 94% | 92% | 90% | 92% | 94% |
Figure 1609.3.2(f)
County of Kauai Peak Gust Topographic FactorKzt
The wind directionality factor, Kd, shall be determined from Tables 1609.3.3(a)(1) through 1609.3.3(a)(3) and 1609.3.3(b)(1) through 1609.3.3(b)(3), and Figures 1609.3.3(a)(4) and 1609.3.3(b)(4).
Exception: Basic design wind speed, V, is determined per Figures 1609.3(5) through 1609.3(8) that already include topographic effects near mountainous terrain and near gorges, which shall be used with a topographic factor Kzt of 1.0 and the directionality factors given in Table 26.6-1 of ASCE 7.
Table 1609.3.3(a)(1)
Kd Values for Main Wind Force Resisting Systems Sited in Hawaii County a,b
Topographic Location on the Island of Hawaii | Main Wind Force Resisting Systems | Main Wind Force Resisting Systems with totally independent systems in each orthogonal direction | Biaxially Symmetric and Axisymmetric Structures of any Height and Arched Roof Structures | ||
Mean Roof Height less than or equal to 100 ft. | Mean Roof Height greater than 100 ft. | Mean Roof Height less than or equal to 100 ft. | Mean Roof Height greater than 100 ft. | ||
Sites in North Kohala, South Kohala, South Kona, South Hilo, and Puna Districts at an elevation not greater than 3000 ft. | 0.65 | 0.70 | 0.70 | 0.75 | 0.85 |
All other sites | 0.70 | 0.80 | 0.75 | 0.80 | 0.95 |
Table 1609.3.3(a)(2)
Kd Values for Main Wind Force Resisting Systems Sited in Maui County a,b
Topographic Location in the County of Maui | Main Wind Force Resisting Systems | Main Wind Force Resisting Systems with totally independent systems in each orthogonal direction | Biaxially Symmetric and Axisymmetric Structures of any Height and Arched Roof Structures | ||
Mean Roof Height less than or equal to 100 ft. | Mean Roof Height greater than 100 ft. | Mean Roof Height less than or equal to 100 ft. | Mean Roof Height greater than 100 ft. | ||
Sites on the Island of Maui at an elevation not greater than 1000 ft. | 0.60 | 0.65 | 0.70 | 0.75 | 0.85 |
Sites on the Island of Maui at an elevation greater than 1000 ft. | 0.65 | .70 | 0.75 | 0.80 | 0.90 |
All other sites on the Islands of Molokai and Lanai | 0.80 | 0.85 | 0.80 | 0.85 | 0.95 |
Table 1609.3.3(a)(3)
Kd Values for Main Wind Force Resisting Systems Sited on Oahu, Hawaiia,b
Topographic Location on Oahu, Hawaii | Main Wind Force Resisting Systems | Main Wind Force Resisting Systems with totally independent systems in each orthogonal direction | Biaxially Symmetric and Axisymmetric Structures of any Height and Arched Roof Structures | ||
Mean Roof Height less than or equal to 100 ft. | Mean Roof Height greater than 100 ft. | Mean Roof Height less than or equal to 100 ft. | Mean Roof Height greater than 100 ft. | ||
Sites within valleys at an elevation of at least 50 ft. but not greater than 500 ft. | 0.65 | 0.70 | 0.70 | 0.75 | 0.85 |
Central Oahu above an elevation of 500 ft, the Ewa and Kapolei plains, and coastal areas with Kzt (10m) not greater than 1.2 | 0.75 | 0.80 | 0.75 | 0.80 | 0.95 |
All other areas, including Hills, Hillsides, Ridges, Bluffs, and Escarpments at any elevation or height; coastal and inland areas with Kzt (10m) greater than 1.2 | 0.70 | 0.75 | 0.75 | 0.80 | 0.90 |
Figure 1609.3.3(a)(4)
Kd Values for Main Wind Force Resisting Systems Sited on Kauai County, Hawaii a,b
Table 1609.3.3(b)(1)
Kd Values for Components and Cladding of Buildings Sited in Hawaii County a,b
Topographic Location on the Island of Hawaii | Components and Cladding | ||
Mean Roof Height less than or equal to 100 ft. | Mean Roof Height greater than 100 ft. | Risk Category IV Buildings and Structures | |
Sites in North Kohala, South Kohala, South Kona, South Hilo, and Puna Districts at an elevation not greater than 3000 ft. | 0.65 | 0.70 | 0.75 |
All other sites | 0.75 | 0.80 | 0.85 |
Table 1609.3.3(b)(2)
Kd Values for Components and Cladding of Buildings Sited in Maui County a,b
Topographic Location on the County of Maui | Components and Cladding | ||
Mean Roof Height less than or equal to 100 ft. | Mean Roof Height greater than 100 ft. | Risk Category IV Buildings and Structures | |
Sites on the Island of Maui at an elevation not greater than 1000 ft | 0.65 | 0.70 | 0.75 |
Sites on the Island of Maui at an elevation greater than 1000 ft. | 0.70 | 0.75 | 0.85 |
All other sites on the Islands of Molokai and Lanai | 0.80 | 0.85 | 0.85 |
Table 1609.3.3(b)(3)
Kd Values for Components and Cladding of Buildings Sited on Oahu, Hawaii a,b
Topographic Location on Oahu | Components and Cladding | ||
Mean Roof Height less than or equal to 100 ft. | Mean Roof Height greater than 100 ft. | Risk Category IV Buildings and Structures | |
Sites within valleys at an elevation of at least 50 ft. but not greater than 500 ft. | 0.65 | 0.70 | 0.75 |
Central Oahu above an elevation of 500 ft, the Ewa and Kapolei plains, and coastal areas with Kzt (10m) not greater than 1.2 | 0.75 | 0.80 | 0.85 |
All other areas, including Hills, Hillsides, Ridges, Bluffs, and Escarpments at any elevation or height; coastal and inland areas with Kzt (10m) greater than 1.2 | 0.70 | 0.75 | 0.80 |
Figure 1609.3.3(b)(4)
Kd Values for Components and Cladding of Buildings Sited on Kauai County, Hawaii a,b
For each wind direction considered, an exposure category that adequately reflects the characteristics of ground surface irregularities shall be determined for the site at which the building or structure is to be constructed. Account shall be taken of variations in ground surface roughness that arise from natural topography and vegetation as well as from constructed features.
For each selected wind direction considered, at which the wind loads are to be evaluated, the exposure of the building or structure shall be determined for the two upwind sectors extending 45 degrees (0.79 rad) either side of the selected wind direction. The exposures in these two sectors shall be determined in accordance with Sections 1609.4.2 and 1609.4.3 and the exposure resulting in the highest wind loads shall be used to represent winds from that direction.
Exception: Exposure categories shall be permitted to be determined using Figures 1609.4(a) through 1609.4(e).
Figure 1609.4 (a)
Exposure Category Zones for Hawaii County
Figure 16094 (b)
Exposure Category Zones for Island of Maui, Maui County
Figure 16094 (c)
Exposure Category Zones for Islands of Molokai and Lanai, Maui County
Figure 16094 (d)
Exposure Category Zones for the City and County of Honolulu
Figure 1609.4 (e)
Exposure Category Zones for Kauai County"
W106 Roof-top Solar panels
Section 1609.5.4 is added to read as follows:
The normal force on other configurations of roof-top panels not regulated by ASCE 7 Chapter 29 shall be not less than that determined by Equation 1609-5:
F = qh (GCp) CN A (lb) (N) (Equation 1609-5)
Where:
CN = pressure coefficients for monoslope free roofs from ASCE 716 Table 30.8-1 considering each elevated panel as a free roof surface in clear wind flow. The angle [THETA] used for the determination of CN shall be measured as the angle of the panel with respect to the plane of the roof ( [OMEGA] in Figure 16095-1) Values of CN for forces on the panel may be taken as the Zone 1 coefficients
Exception: Zone 2 coefficients for CN shall be used where the panel angle, [OMEGA], is greater than 7.5 degrees; panels are located a distance less than or equal to twice the roof height measured from a roof corner; and the parapet is greater than 24 inches (610 mm) in height above the roof.
GCp = the component and cladding external pressure coefficient for roofs for the roof zone corresponding to the location of the solar panel, and the effective wind area shall be that of the solar panel. The minimum magnitude of negative pressure values of GCp in Zone 1 shall be taken as -1.0.
A = the total area of the solar panel element.
When located in roof zone 2 or 3 as defined in ASCE 7, the force F shall be applied with an eccentricity equal to a third of the solar panel width.
Click here to view image (lb) (N) (Equation 1609-7)
Where:
F = the normal force on each panel determined in accordance with Section 1609.5.4
[ALPHA] = the angle of the roof plane with respect to horizontal.
[BETA] = the angle of tilt of the panel with respect to the roof plane.
µ = the static friction coefficient between the panel base and its bearing surface.
Alternatively, to resist uplift and sliding, ballasted panels that are tilted at an angle of less than 10 degrees from a horizontal plane shall each be ballasted to resist a force equal to 2 times the normal force on each panel. Ballasted panels that are tilted at an angle between 10 degrees to 25 degrees from a horizontal plane shall each be ballasted to resist a force equal to 8 times the normal force on each panel.
W107 Revisions to Section 2304.6.1.
Section 2304.6.1 is amended to read as follows:
W108 Revisions to Table 2304.6.1.
Table 2304.6.1 is amended to read as follows:
"TABLE 2304.6.1
MAXIMUM EFFECTIVE ALLOWABLE STRESS DESIGN WIND SPEED, Veff-asd PERMITTED FOR WOOD STRUCTURAL PANEL WALL SHEATHING USED TO RESIST WIND PRESSURESa,b,c
MINIMUM NAIL | MINIMUM WOOD STRUCTURA L PANEL SPAN RATING | MINIMUM NOMINAL PANEL THICKNESS (inches) | MAXIMU M WALL STUD SPACING (inches) | PANEL NAIL SPACING | MAXIMUM EFFECTIVE ALLOWABLE STRESS DESIGN WIND SPEED, Veff-asdd(MPH) | ||||
Size | Penetration (inches) | Edges (inches o.c.) | Field (inches o.c.) | Wind exposure category | |||||
B | C | D | |||||||
6d common (2.0" ×0.113") | 1.5 | 24/0 | 3/8 | 16 | 6 | 12 | 110 | 90 | 85 |
24/16 | 7/16 | 16 | 6 | 12 | 110 | 100 | 90 | ||
6 | 150 | 125 | 110 | ||||||
8d common (2.5" ×0.131") | 1.75 | 24/16 | 7/16 | 16 | 6 | 12 | 130 | 110 | 105 |
6 | 150 | 125 | 110 | ||||||
24 | 6 | 12 | 110 | 90 | 85 | ||||
6 | 110 | 90 | 85 |
For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s.
W109 Revisions to Table 2308.7.5.
Table 2308.7.5 is amended to read as follows:
"Table 2308.7.5
Required Rating of Approved Uplift Connectors (pounds)a,b,c,d,e,f,g,h,i
Effective Allowable Stress Design Wind Speed, | Roof Span (feet) | Overhangs (pounds/ft)d | ||||||
Veff-asd, 3-sec gust | 12 | 20 | 24 | 28 | 32 | 36 | 40 | |
85 | -72 | -120 | -144 | -168 | -192 | -216 | -240 | -38.55 |
90 | -91 | -152 | -182 | -213 | -243 | -274 | -304 | -43.22 |
100 | -131 | -218 | -262 | -305 | -349 | -392 | -436 | -53.36 |
110 | -175 | -292 | -350 | -409 | -467 | -526 | -584 | -64.56 |
120 | -240 | -400 | -480 | -560 | -640 | -720 | -800 | -76.83 |
130 | -304 | -506 | -607 | -708 | -810 | -911 | -1012 | -90.17 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 1.61 km/hr, 1 pound = 0.454 Kg, 1 pound/foot = 14.5939 N/m.
Exposure | Mean Roof Height (feet) | |||||||||
15 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 | |
B | 1.00 | 1.00 | 1.00 | 1.00 | 1.05 | 1.09 | 1.12 | 1.16 | 1.19 | 1.22 |
C | 1.21 | 1.29 | 1.35 | 1.40 | 1.45 | 1.49 | 1.53 | 1.56 | 1.59 | 1.62 |
D | 1.47 | 1.55 | 1.61 | 1.66 | 1.70 | 1.74 | 1.78 | 1.81 | 1.84 | 1.87 |
For SI: 1 inch - 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 1.61 km/hr, 1 pound = 0.454 Kg, 1 pound/foot = 14.5939 N/m.
Connection loads for connections located a distance of 20 percent of the least horizontal dimensions of the building from the corner of the building are permitted to be reduced by multiplying the table connection value by 0.7 and multiplying the overhang load by 0.8.
Haw. Code R. tit. 3, Building Code Council, State Building Code Council, Amendments to the 2018 ICC International Building Code (IBC), 56