Haw. Code R. § tit. 12, subtit. 8, pt. 11, ch. 229, exh. C

Current through August, 2024
Exhibit C - INSPECTION AND TEST INTERVALS (IN MONTHS)

Equipment Type

Permit Renewal

Category 3

Category 5

Electrical Elevators

12

N/A

60

Hydraulic Elevators

12

36

N/A

Escalators and Moving Walks[1]

12

36

N/A

Dumbwaiters

12

36

60

Material Lifts

12

36

60

Platform Lifts and Stairway Chairlifts

12

N/A

N/A

Inclined Elevators

12

36

60

Screw-Column Elevators

12

36

60

Roof-top Elevators

12

36

60

Limited-use/Limited-Application Elevators

3

36

60

Construction Cars

3

36

60

Personnel Hoists[2]

3

N/A

N/A

Amusement Rides

6

N/A

N/A

1 Internal inspections of escalators and moving walks shall be performed at intervals of 36 months.

2 Personnel hoists shall be load tested at intervals of 3 months.

Where an equipment is listed under both Category 3 of 36 months and Category 5 of 60 months, the appropriate testing interval is dependent on whether the lifting mechanism is rope or hydraulic or a combination of rope and hydraulic.

Haw. Code R. tit. 12, subtit. 8, pt. 11, ch. 229, exh. C

July 1, 2012
Am and Comp 11/10/2016
January 1, 2017
Comp 1/31/2021