Section 12-224.1-1 - ScopeThe requirements in this section shall apply to pressure vessels, except for the exemptions in section 12-220-2.1 (c)(3) and (4), and is not limited to the following:
(1) All unfired pressure vessels with design pressure exceeding fifteen (15) psi or five (5) cubic feet in volume;(2) Hot water storage tanks with a nominal water containing capacity greater than one hundred-twenty (120) gallons;(3) Unfired autoclaves greater than five (5) cubic feet in volume regardless of operating pressure;(4) Fired or self-contained sterilizers, jacketed kettles, steam cookers, and autoclaves exceeding a heat input of three (3.0) kw or a volume of one and a half (1.5) cubic feet;(5) Unfired jacketed kettles with a cooking capacity of forty (40) gallons or more;(6) Heat exchangers with a heat input exceeding 200,000 Btu/H or five (5) cubic feet in volume;(7) Hydro pneumatic tanks exceeding one hundred twenty (120) gallons in volume;(8) Expansion tanks exceeding five (5) cubic feet in volume for hot water heating system; and(9) Pressure Vessels for Human Occupancy (PVHOs).Haw. Code R. § 12-224.1-1
[Eff and comp 12/21/2019] (Auth: HRS § 397-4) (Imp: HRS § 397-4)