Table 2.9.1.3
MINIMUM POUNDS OF STEAM PER HOUR PER SQUARE FOOT OF HEATING SURFACE lb steam/hr ft2 (kg steam/hr m2)
Firetube Boiler | Watertube Boiler | |
Boiler Heating Surface | ||
Hand-fired | 5(24) | 6(29) |
Stoker-fired | 7(34) | 8(39) |
Oil, gas, or pulverized coal | 8(39) | 10 (49) |
Waterwall Heating Surface | ||
Hand-fired | 8(39) | 8(39) |
Stolker-fired | 10 (49) | 12(59) |
Oil, gas, or pulverized coal | 14 (68) | 16 (78) |
Copper-finned Watertubes | ||
Hand-fired | 4(20) | |
Stoker-fired | 5(24) | |
Oil, gas, or pulverized coal | 6(29) |
Notes:
* When a boiler is fired only by a gas having a heat value not in excess of 200 Btu/ft.3(7.5MJ(m3), the minimum relieving capacity should be based on the values given for hand-fired boilers above.
* The heating surface shall be computed for that side of the boiler surface exposed to the products of combustion, exclusive of the superheating surface In computing the heating surface for this purpose only the tubes, fireboxes, shells tubesheets, and the projected area of headers need to be considered, except that for vertical firetube steam boilers, only that portion of the tube surface up to the middle gage cock is to be computed
* For firetube boiler units exceeding 8,000 Btu/ft.2 (9 085 J/cm 2) (total fuel Btu (J) Input divided by total heating surface), the factor from the table will be increased by 1 (4.88) for every 1,000 Btu/ft.2 (1,136 J/cm.2) above 8.000 Btu/ft.2 (9,085 J/cm 2) For units less than 7,000 Btu/ft.2 (7,950 J/cm 2), the factor from the fable will be decreased by 1 (4 88)
* For watertube boiler units exceeding 16,000 Btu/ft.2 (18,170 J/cm.2) (total fuel Btu input divided by the total heating surface) the factor from the table will tie increased by 1 (4.88) for every 1,000 Btu/ ft.2 (1,136 J/cm.2) above 16,000 Btu/ft.2 (18,170 J/cm.2). For units with less than 15,000 Btu/ft.2 (17,034 J/cm.2), the factor In the table will be decreased by 1 (4 88) for every 1,000 Btu/ft.2 (1,136 J/cm.2) below 15,000 Btu/ft.2 (17.034 J/cm 2).
Haw. Code R. § 12-222.1-6