Haw. Code R. § 12-222.1-6

Current through August, 2024
Section 12-222.1-6 - Pressure relief valves for power boilers
(a) General requirements. The following shall apply to all power boilers:
(1) Each power boiler, miniature boiler, electric boiler, and high-temperature water boiler shall have at least one ASME and NB certified pressure relief valve marked with the ASME certification mark and "V" designator, and National Board NB symbols;
(2) When a new boiler is installed, ASME Form P-7 Manufacturer's Data Report for Pressure Relief Valves, or ASME Form P-8 Manufacturer's or Assembler's Certificate of Conformance for Pressure Relief Valves, as required by the ASME BPVC, shall be submitted along with the manufacturer's data on the power boiler;
(3) Only direct spring-loaded pressure relief valves or pilot operated pressure relief valves designed to relieve steam shall be used for steam service;
(4) Safety relief valves are valves designed to relieve either steam or water, depending on the application;
(5) Deadweight or weighted-lever pressure relief valves shall not be used;
(6) For high-temperature water boilers, safety relief valves shall have a closed bonnet, and valve bodies shall not be constructed of cast iron;
(7) At least one NB capacity certified pressure relief valve shall be installed on the boiler. If the boiler has more than 500 square feet of heating surface, or if an electric boiler has a power input of more than 1,100 kilowatts, two or more NB capacity certified pressure relief valves shall be installed;
(8) The pressure relief valve capacity for each boiler shall be so that the valve or valves will discharge all the steam that can be generated by the boiler without allowing the pressure to rise more than six per cent (6%) above the highest pressure to which any valve is set, and in no case to more than six per cent (6%) above the maximum allowable working pressure of the boiler. In no case shall the minimum relieving capacity be less than the maximum designed steaming capacity as determined by the manufacturer;
(9) One or more pressure relief valves on the boiler proper shall be set at or below the maximum allowable working pressure. If additional valves are used, the highest pressure setting shall not exceed the maximum allowable working pressure by more than three per cent (3%). The complete range of pressure settings of all the pressure relief valves on a boiler shall not exceed ten per cent (10%) of the highest pressure to which any valve is set;
(10) Adjustments, repairs, and reconditioning of pressure relief valves shall be done by a National Board authorized "VR" repair company. The "VR" repair company shall affix a "VR" nameplate to the valve and provide repair documentation and the owner and user shall ensure that the nameplate identification plates remain legible; and
(11) The owner and user shall maintain all pressure relieving devices in good operating condition. When the valves cannot be tested in service, the user shall maintain and make available to the inspector records showing the test dates and set pressure for the valves.
(b) Installation of pressure relief valves. The following shall apply to the installation requirements of pressure relief valves:
(1) Every boiler shall have outlet connections for the pressure relief valve, or valves, independent of any other outside steam connection, and the area of opening shall be at least equal to the aggregate areas of inlet connections of all the attached pressure relief valves. An internal collecting pipe, splash plate, or pan should be used, provided the total area for inlet of steam is not less than twice the aggregate areas of the inlet connections of the attached pressure relief valves. The holes in such collecting pipes shall be at least 1/4 inch in diameter, and the least dimension in any other form of opening for inlet of steam shall be 1/4 inch. If pressure relief valves are attached to a separate steam drum or dome, the opening between the boiler proper and the steam drum or dome shall be not less than ten (10) times the total area of the pressure relief valve inlet;
(2) Every pressure relief valve shall be connected to stand in an upright position with spindle vertical;
(3) The opening or connection between the boiler and the pressure relief valve shall have at least the area of the valve inlet and the inlet pipe to the pressure relief valve shall be as short and straight as possible, no longer than twice the center-to-end (face) dimension of a corresponding tee fitting of the same diameter, pressure class, and connection type. When a discharge pipe is used, the cross-sectional area shall not be less than the full area of the valve outlet or of the total of the areas of the valve outlets. It shall be as short and straight as possible and arranged to avoid undue stresses on the valve or valves;
(4) When a pressure relief valve is exposed to outdoor elements that may affect operation of the valve, the valve may be shielded with a cover. The cover shall be properly vented and arranged to permit servicing and normal operation of the valve;
(5) No valves of any type except a changeover valve as defined below, shall be placed between the pressure relief valves and the boiler, nor on the discharge pipe between the pressure relief valves and the atmosphere. A changeover valve, which allows two redundant pressure relief valves to be installed for the purpose of changing from one pressure relief valve to the other while the boiler is operating, may be used provided the changeover valve is in accordance with the original code of construction. It is recommended that the department be contacted to determine the acceptability of changeover valves on boiler applications. The changeover valve shall be designed such that there is no intermediate position where both pressure relief valves are isolated from the boiler;
(6) When two or more pressure relief valves are used on a boiler, they should be mounted either separately or as twin valves made by placing individual valves on Y-bases, or duplex valves having two valves in the same body casing. Twin valves made by placing individual valves on Y-bases or duplex valves having two valves in the same body shall be of equal size;
(7) When two valves of different sizes are installed singly, the relieving capacity of the smaller valve shall not be less than fifty per cent (50%) of that of the larger valve; and
(8) When a boiler is fitted with two or more pressure relief valves on one connection, this connection to the boiler shall have a cross-sectional area not less than the combined areas of inlet connections of all the pressure relief valves with which it connects.
(c) Discharge pipe. The following shall apply to pressure relief valve discharge piping requirements:
(1) All pressure relief valves shall be piped to a safe point of discharge so located or piped as to be carried clear from running boards or platforms. Provision for an ample gravity drain shall be made in the discharge pipe at or near each pressure relief valve, and where water or condensation may collect. Each valve shall have an open gravity drain through the casing below the level of the valve seat. For iron and steel-bodied valves exceeding NPS 2, the drain hole shall be tapped not less than NPS 3/8;
(2) Discharge piping from pressure relief valves on high-temperature water boilers shall have adequate provisions for water drainage as well as steam venting;
(3) If a muffler is used on a pressure relief valve, it shall have sufficient outlet area to prevent back pressure from interfering with the proper operation and discharge capacity of the valve. The muffler plates or other devices shall be so constructed as to avoid a possibility of restriction of the steam passages due to deposits. Mufflers shall not be used on high-temperature water boiler pressure relief valves; and
(4) When a discharge pipe is used, it shall be at least the same size of the safety valve discharge port and fitted with an open drain to prevent water lodging in the upper part of the safety valve or in the discharge pipe. Sectional areas of a common discharge pipe shall not be less than the same size of the combined multiple valve outlets discharging into the common discharge pipe. The discharge pipe shall be as short and straight as possible and arranged to avoid undue stresses on the valve or valves. Discharge pipe elbows shall be placed close to the safety valve outlet, or the discharge pipe shall be anchored and supported securely. If umbrella type drip pan connection is used, the discharge piping shall be designed to prevent binding due to expansion.

Haw. Code R. § 12-222.1-6

[Eff and comp 12/21/2019] (Auth: HRS § 397-4) (Imp: HRS § 397-4)