The following amendments to codes are hereby adopted by the Board of Community Affairs as amendments to the Georgia State Minimum Standard Codes for Construction:
GEORGIA AMENDMENTS TO THE 1994 STANDARD BUILDING CODE
· Add to Chapter 2, Definitions, a definition for Exterior Insulation and Finish Systems (EIFS) to read as follows:
Chapter 2 - Definitions:
Exterior Insulation and Finish Systems (EIFS) - Exterior Insulation and Finish Systems are non-load bearing exterior wall cladding systems generally consisting of an insulation board, an adhesive and/or mechanical attachment of the insulation board to the substrate, glass fiber reinforcing mesh, a base coat on the face of the insulation board and an aggregated polymer binder based finish coat.
· Said building code is further amended by adding a section 1403.10 to Chapter 14 to read as follows:
Chapter 14 - Exterior Wall Covering 1403 - Veneered Walls
1403.10 Exterior Insulation and Finish Systems:
Exterior Insulation and Finish Systems (EIFS) on type III, V and VI construction used on buildings with areas less than 5000 square feet of gross floor area shall be installed according to this section. For other than type III, V and VI construction, refer to the local jurisdiction's adoption of methods, guidelines or procedures for the use of alternate materials or methods. The contractor shall supply an Evaluation Report and the EIFS manufacturer's installation and application instructions.
1403.10.1 Exterior Insulation and Finish System (EIFS) Class PB shall conform to Appendix "I", Performance Requirements for Exterior Insulation and Finish Systems.
1403.10.2 Wall Assemblies incorporating EIFS shall be provided with a drainage system as recognized in a current model code Evaluation Report and shall conform to Appendix "J", Requirements for Drainage Installed with Exterior Insulation and Finish Systems.
1403.10.3 Wall assemblies incorporating EIFS shall demonstrate drying potential as recognized in a current model code Evaluation Report and in conformance with Appendix "K", Requirements for Drying Potential for Exterior Insulation and Finish Systems.
1403.10.4 Installation of Exterior Insulation and Finish Systems (EIFS) Class PB shall comply with ASTM PS 49, Standard Practice for Application of Class PB Exterior Insulation and Finish Systems. Where there is a conflict between ASTM PS 49 and other provisions of the code, the more restrictive shall apply.
1403.10.5 Foam plastic insulation in Exterior Insulation and Finish Systems (EIFS) shall conform to the requirements of Chapter 26, Sections 2603.1, 2603.2, 2603.3.
1403.10.6 Weather Resistive Barriers
The weather resistive barrier shall be asphalt saturated felt weighing at least 14 lb. per hundred square feet, or conform to ASTM D226 Type I or equal as determined by qualified testing. The barrier shall be free from holes and breaks and shall be applied over studs or sheathing of all exterior walls. Weather-resistant sheathing paper type barriers shall be applied horizontally with the upper layer lapped over the lower layer not less than 2 inches (31 mm). Where vertical joints occur, the felt or paper shall be lapped not less than 6 inches (152 mm). Approved surface applied type barriers shall be monolithic and continuous and shall be applied in accordance with the manufacturer's specifications and application instructions.
1403.10.7 Flashing for Exterior Insulation and Finish Systems (EIFS)
Flashing shall be approved, corrosion resistive, and provided in such a manner as to be leakproof and flashed to the exterior. Windows, doors, louvers and other similar openings shall be flashed. Windows shall be flashed at the top, sides and sills. Window heads shall be flashed to the exterior, except that self-flashing windows having a continuous lap of not less than 1 1/8 inches (28 mm) over sheathing material around the perimeter of the opening, including corners, do not require additional flashing at the head. Flashing shall be installed at the intersections of walls, including chimney chase walls, with roofs, decks, balconies, porches, stairs, landings and similar construction. The weather resistive barrier shall be continuous with the weather resistive barrier behind wall coverings adjacent to the EIFS or flashed to the exterior.
1403.10.8 Sealants for Exterior Insulation and Finish Systems (EIFS)
Sealants shall be installed between EIFS and adjoining construction or penetrations in accordance with ASTM C1193. Minimum 3/4 inch wide sealant joints shall be installed at floor lines of wood framed floors. Minimum 1/2 inch wide sealant joints shall be installed at perimeters of wall openings such as for windows and doors. Sealants applied in a fillet configuration shall be installed over bond breaker tape or other pre-formed closed cell sealant backing. Sealants shall be installed so as not to block weeps or other water drainage. Sealants shall conform to ASTM C920, grade NS, Type M or S, Class 25. Sealants shall be tested in accordance with ASTMC 1135. Minimum 50% elongation after conditioning shall be required.
· Said building code is further amended by adding figure 2304.1 to Chapter 23 as follows:
· Said building code is further amended by adding a section 2603.1.3 and section 2603.1.4 to Chapter 26 "Plastic" to read as follows:
Chapter 26: Plastic
2603 Foam Plastic Insulation
Section 2603.1.3. In areas where hazard of termite damage is very heavy, in accordance with Figure 2304.1, foam plastic including, but not limited to, extruded or expanded polystyrene or polyiscyanorate shall not be installed below grade on the exterior of foundation walls or below grade on slab foundations.
Exceptions:
1) When approved protective membranes that separate the foam plastics from the soil are provided.
2) Cold storage construction
3) Foam filled doors
4) Types I, II and IV construction
5) Interior side of basement walls
Section 2603.1. In areas where hazard of termite damage is very heavy, in accordance with Figure 2304.1, clearance between earth and foam plastics applied to the exterior wall shall not be less than 6 inches (152 mm).
· Said building code is further amended by adding ASTM reference standards to Chapter 35 to read as follows:
Chapter 35 - Reference Standards
ASTM - Reference Standards
B117-94 | Standard Practice for Operating Salt Spray (Fog) Testing Apparatus |
C297-94 | Test method for Tensile Strength of Flat Sandwich Constructions Flatwise Plane |
C578-92 | Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation |
C1193-91 | Standard Guide for Use of Joint Sealants |
C1289-95 | Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board |
D968-93 | Standard Test Method for Abrasion Resistance of Organic Coatings by Falling Abrasive |
D2247-94 | Standard Practice for Testing Water Resistance of Coatings in 100% Relative Humidity |
D3273-94 | Standard Test Method for Resistance to Growth of Mold on the Surface of Interior Coatings in an Environmental Chamber |
D5035-90 | Standard Test Method for Breaking Force and Elongation of Textile Fabrics (Strip Force) |
E331-93 | Standard Test Method for Water Penetration of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference |
G23-93 | Standard Practice for Operating Light-Exposure Apparatus (Carbon-Arc Type) With and Without Water for Exposure of Nonmetallic Materials PS 49-96 Standard Practice for Application of Class PB Exterior Insulation and Finish System |
· Said Building Code is further amended by adding an Appendix I to read as follows:
APPENDIX I
Performance Requirements For Exterior Insulation and Finish Systems (EIFS)
The system and its components shall meet or exceed the following performance standards.
1.0 System Performance
Characteristic | Test Method | Acceptance Criteria |
1.1 Abrasion Resistance | ASTM D 968 | No cracking, checking or loss film integrity at 528-quarts (500 liters) of sand |
1.2 Accelerated Weathering | ASTM G 23 | No deleterious effects* after 2000 hours when viewed under 5X magnification |
1.3 Freeze/Thaw Resistance | air dry at 120 degrees Fahrenheit minimum eight hours total immersion in water at 70 degrees Fahrenheit to 80 degrees Fahrenheit for eight hours then exposure to 20 degrees Fahrenheit for 16 hours. | 10 cycles. No deleterious effects* viewed under 5X magnification |
1.4 Mildew Resistance | ASTM D3273 | No growth supported during 28 day exposure time |
1.5 Salt Spray Resistance | ASTM B117 | No deleterious effects* at 300 hour exposure |
1.6 Tensile Adhesion | ASTM C297 | No failure in the adhesive, Base coat or finish coat. Minimum 5 PSI (34.5 kPa) Tensile strength before and after freeze/thaw and accelerated weathering test. |
1.7 Water Penetration | ASTM E331 | No water penetration beyond the plane of the base coat/ Insulation board interface after 15-minutes at 6.24 psf (299 Pa), or 20% of positive design wind pressure, whichever is greater. |
1.8 Water Resistance | ASTM D2247 | No deleterious effects* at 14 day exposure. |
1.9 Wind Load | ASTM E330 | Withstand negative and positive wind loads required by building code. |
2.0 Component Performance | ||
2.1 Physical Properties and | ASTM C578 | Meets TYPE I Requirements for EPS |
2.2 Physical Properties and | ASTM C 1289 | Meets TYPE II Requirements for Polyisocyanuarate Thermal Insulation Board |
*No deleterious effects: no cracking, checking, crazing, erosion, rusting, blistering, peeling or delamination.
*Said Building Code is further amended by adding an Appendix J to read as follows:
APPENDIX J
Requirements For Drainage Installed With Exterior Insulation and Finish Systems (EIFS)
1.01 | Scope: |
These requirements cover the drainage of water from wall construction incorporating EIFS and weather resistive barriers. Drainage is provided to prevent water intrusion beyond the water resistive barrier and to discharge water to the exterior. | |
2.01 | Reference Documents ASTM Standards E 331 Standard Test Method for Water Penetration of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference. |
3.01 | Terminology Description of Terms Specific to This Standard: |
3.01.1 | Drainage: The collection and discharge of water gravity flow. |
4.01 | Drainage of Water. |
4.01.1 | Walls incorporating EIFS and drainage shall be constructed to collect incidental water at the exterior outside faces of a weather resistive barrier and flashing. The wall assembly shall allow water collected at the outside faces of the weather resistive barrier and flashing to flow by gravity to the exterior. |
4.01.2 | The weather resistive barrier shall be integrated with the flashing to prevent water intrusion to the interior. |
4.01.3 | Drainage shall be confirmed by testing in accordance with ASTM E331 and Section 5.01. |
5.01 | Test Method For Determining The Drainage Performance of Wall Assemblies Clad With Exterior Insulation and Finish Systems (EIFS). |
This test method consists of testing EIFS clad wall assemblies for Drainage Performance by ASTM E331, Standard Test Method for Water Penetration of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference, except as described otherwise herein.
5.01.1 | Scope: This test method evaluates the drainage performance of EIFS when subjected to water applied in conjunction with a positive uniform static air pressure. |
5.01.2 | Test Method: ASTM E331 |
5.01.3 | Apparatus ASTM E 331 for application of water and positive uniform static air pressure and a catchment to collect and measure drained water. |
5.01.4 | Test Specimen |
5.01.4.1 | The EIFS clad wall test specimens shall be a minimum of 4'X8' (123 cm X 246 cm). |
5.01.4.2 | Minimum of four test specimens plus a control shall be assembled and allowed to cure for 28 days prior to test. The test specimens shall contain a fault. Dimensions and location of the fault are shown in figure J-1.0. |
5.01.4.3 | The EIFS assemblies shall be installed with the materials, details, and methods of assembly as required by the manufacturer. |
5.01.4.3.1 | For acceptance of wall assemblies with wood-based sheathing, the test wall shall include the sheathing to be accepted. |
5.01.4.4 | The supporting framework for the EIFS wall assemblies shall be of wood or metal stud construction with framing spacing as required by the manufacturer. The standard framing spacing is 16" (41 cm) o.c. |
5.01.4.5 | The test specimens shall be constructed to allow observation of drainage. |
5.01.5 | Test Procedure. |
5.01.5.1 | Test pressure difference shall be minimum 6.24 pounds per square foot. |
5.01.5.2 | Water delivery to the exterior surface shall be uniform and at a rate of 5.0 Gallons per square foot hour. |
5.01.5.3 | Water and pressure duration shall be minimum 15 minutes. |
5.01.5.4 | Subject the four test specimens to the conditions in 5.1, and 5.3. Observe and Verify that specimens drain freely. |
5.01.5.5 | Allow each specimen to drain in the vertical position. |
5.01.5.6 | After one hour of drainage, select one of the test specimens; disassemble and verify drainage by observation. Note: Disassembly of wall must assure inspection of all wall components. Any water accumulation beyond incidental beading due to surface tension shall be reported. |
6.01 | REPORT. |
6.01.1 | Follow ASTM E331 Sections, 12.1.1, 12.1.2, 12.1.7, 12.1.9, 12.1.10, and 12.2 plus the following: |
6.01.2 | Observations from 5.4, 5.5, and 5.6. |
6.01.3 | Details of assembly, including a description of components, mixing and application, thickness of components and a statement of conformance to the manufacturer's application instructions. |
6.01.4 | Photographic video documentation of test specimens, including assembly, components, drainage verification, and samples removed in 5.6. |
6.01.5 | Detailed drawings of the test specimens. |
6.01.6 | A record of all points of water penetration to the cavity and drainage performance. |
* Said Building Code is further amended by adding an Appendix K to read as follows:
APPENDIX K
Requirements For Drying Potential For Exterior Insulation And Finish Systems (EIFS)
1.01 | Scope These requirements cover the potential for drying of wall construction incorporating EIFS and drainage. Drying of water in excess of 1 ounce per square foot shall be confirmed by testing in accordance with ASTM E331 and Section 2.01. |
2.01 | TEST METHOD |
2.01.1 | Follow Appendix "J", Requirements for Drainage Installed with Exterior Insulation Finish Systems (EIFS), Section 5.01 through 5.01.5.6. |
2.01.2 | Allow three test specimens plus the control specimen to dry in a conditioned space (73 degrees Fahrenheit ± 4 degrees at 50% relative humidity) For 72 hours. {NOTE: These are usually the same test specimens tested for drainage.} |
2.01.3 | After 72 hours of drying, cut three 12" X 12" samples to include all components of the assembly except framing from each test specimen and the control, as shown in figure K-1.0. |
2.01.4 | Record observations. |
2.01.5 | Immediately weigh each sample and place in an oven controlled at 120 ± 10 degrees Fahrenheit until constant weight is obtained. Record weight loss of each sample to the nearest .01 ounce. |
2.01.6 | Determine the average weight loss for the nine samples (TSRM) from the test specimens. Determine the average weight loss for the three control samples (CSBM). |
3.01 | TSRM - CSBM = SRM TSRM - Average residual moisture in nine test samples (oz.) CSRM - Average background moisture in three control samples (oz.) SRM - Average residual moisture in system per square foot; (ounce per square foot). |
4.01 | REPORT A record of all weights as recorded in Section 2.01.5 and 2.01.6 to evaluate drying potential. |
5.01 | ACCEPTANCE SRM (Average Residual Moisture in system per square foot) shall not exceed 1 ounce per square foot. |
GEORGIA AMENDMENTS TO THE 1995 CABO ONE AND TWO FAMILY DWELLING CODE
*Add to Chapter 2, Definitions, a definition for Exterior Insulation and Finish Systems (EIFS) to read as follows:
Chapter 2 - Building Definitions:
Exterior Insulation and Finish Systems (EIFS) - Exterior Insulation and Finish Systems are non-load bearing exterior wall cladding systems generally consisting of an insulation board, an adhesive and/or mechanical attachment of the insulation board to the substrate, glass fiber reinforcing mesh, a base coat on the face of the insulation board and an aggregated polymer binder based finish coat.
*Said CABO code is further amended by adding a section 323.1.1 to Section 323 to read as follows:
Section 323 - Protection Against Termites:
Section 323.1.1: Foam Plastics: Foam plastics including, but not limited to, extruded or expanded polystyrene or polyisocyanurate shall not be installed below grade on the exterior of foundation walls or below grade on slab foundations. In areas where the hazard of termite damage is very heavy, according to Figure 301.2f, clearance between earth and foam plastics applied to the exterior wall shall be not less than 6 inches (152 mm).
EXCEPTION: Interior side of basement walls.
*Said CABO code is further amended by adding a section 703.9 to chapter 7 "Wall Covering" to read as follows:
Chapter 7 - Wall Covering
703.9 - Exterior Insulation and Finish System (EIFS)
703.9.1 Exterior Insulation and Finish Systems (EIFS) shall conform to Appendix "G", Performance Requirements for Exterior Insulation and Finish Systems (EIFS)
703.9.2 Wall assemblies incorporating EIFS shall be provided with drainage as recognized in a current model building code Evaluation Report and shall conform to Appendix "H" Requirements for Drainage Installed With Exterior Insulation and Finish Systems (EIFS).
703.9.3 Wall assemblies incorporating EIFS shall demonstrate drying potential as recognized in a current model building code Evaluation Report and shall be in conformance with Appendix "I", Requirements for Drying Potential for Exterior Insulation and Finish Systems (EIFS).
703.9.4 Installation of Exterior Insulation and Finish Systems (EIFS) Class PB shall comply with ASTM PS49, Standard Practice for Application of Class PB Exterior Insulation and Finish System. Where there is a conflict between ASTM PS49 and other provisions of the code, the other provisions shall apply instead of ASTM PS49.
703.9.5 Foam plastic insulation in Exterior Insulation and Finish Systems (EIFS) Class PB shall conform to the requirements of Chapter 3, Sections 317.1, 317.1.1, 317.1.2, 317.2.1, and 317.3.
703.9.6 Weather Resistive Barriers
The weather resistive barrier shall be asphalt saturated felt weighing at least 14 lb. per hundred square feet, or conform to ASTM D226 Type I or equal as determined by qualified testing. The barrier shall be free from holes and breaks and shall be applied over studs or sheathing of all exterior walls. Weather-resistant sheathing paper type barriers shall be applied horizontally with the upper layer lapped over the lower layer not less than 2 inches (31 mm). Where vertical joints occur, the felt or paper shall be lapped not less than 6 inches (152 mm). Approved surface applied type barriers shall be monolithic and continuous and shall be applied in accordance with the manufacturer's specifications and application instructions.
703.9.7 Flashing for Exterior Insulating And Finish Systems (EIFS) Flashing shall be approved, corrosion resistive, and provided in such a manner as to be leakproof and flashed to the exterior. Windows, doors louvers and other similar openings shall be flashed. Windows shall be flashed at the top, sides and sills. Window heads shall be flashed to the exterior, except that self-flashing windows having a continuous lap of not less than 1 1/8 inches (28 MM) over sheathing material around the perimeter of the opening, including corners, do not require additional flashing at the head. Flashing shall be installed at the intersections of walls, including chimney chase walls, with roofs, decks, balconies, porches, stairs, landings and similar construction. The weather resistive barrier shall be continuous with the weather resistive barrier behind wall coverings adjacent to the EIFS or flashed to the exterior.
703.9.7.1 Refer to Appendix "11" for typical weather resistive barrier, flashing details, and installation details.
703.9.8 Sealants for Exterior Insulation and Finish Systems (EIFS) Sealants shall be installed between EIFS and adjoining construction or penetrations in accordance with ASTM C1193. Minimum 3/4 inch wide sealant joints shall be installed at floor lines of wood framed floors. Minimum 1/2 inch wide sealant joints shall be installed at perimeters of wall openings such as for windows and doors. Sealants applied in a fillet configuration shall be installed over bond breaker tape or other pre-formed closed cell sealant backing. Sealants shall be installed so as not to block weeps or other water drainage. Sealants shall conform to ASTM C920, grade NS, Type M or S, Class 25. Sealants shall be tested in accordance with ASTM C 1135 and PS49. Minimum 50% elongation after conditioning shall be required.
* Said CABO code is further amended by adding to Table 703.4 the following:
Table 703.4 - Weather-Resistant Siding Attachment and Minimum Thickness
SIDING MATERIAL | NOMINAL THICKNESS (inches) | JOINT TREATMENT | SHEATHING PAPER REQUIRED | NUMBER OR SPACING OF FASTENERS |
Exterior Insulation and Finish Systems (footnote 9) | 3/4 Minimum 4 Maximum Thickness of Insulation Board | (footnote 15) | yes (footnote 16) | Approved Corrosion Resistive Fastener or other approved attachment (footnote 17) |
Footnotes:
15. Sealant shall be applied in accordance with ASTM C 1193-91.
16. Weather resistant membrane shall be installed with provisions for drainage, without exception, over wood, wood structural panels, and sheathing of any type when installed on wood framing.
17. Insulation fastener type, number and spacing shall be as established by testing in accordance with ASTM E330 and accepted engineering practice, but insulation fastener spacing shall in all cases be a maximum of either:
1) 12 inches center to center vertically and 16 inches center to center horizontallyor
2) 8 inches center to center vertically and 24 inches center to center horizontally.
* Said CABO code is further amended by adding ASTM reference standards to Chapter 47 to read as follows:
Chapter 47 - Reference Standards
ASTM Standards
B117-94 | Standard Practice for Operating Salt Spray (Fog) Testing Apparatus |
C297-94 | Standard Test method for Tensile Strength of Flat Sandwich Constructions Flatwise Plane |
C920-87 | Standard Specification for Elastomeric Joint Sealants |
C1135-90 | Standard Test Method for Determining Tensile Adhesion Properties of Structural Sealants |
C1193-91 | Standard Guide for Use of Joint Sealants |
C1289-95 | Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board |
D226-89 | Standard Specification for Asphalt-Saturated Organic Felt used in Roofing and Waterproofing |
D968-93 | Standard Test Method for Abrasion Resistance of Organic Coatings by Falling Abrasive |
D2247-94 | Standard Practice for Testing Water Resistance of Coatings in 100% Relative Humidity |
D3272-94 | Standard Test Method for Resistance to Growth of Mold on the Surface of Interior Coatings in an Environmental Chamber |
D5035-90 | Standard Test Method for Breaking Force and Elongation of Textile Fabrics (Strip Force) |
E330-90 | Standard Test Method for Structural Performance of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference |
E331-93 | Standard Test Method for Water Penetration of Exterior Windows, Curtain walls, and Doors by Uniform Static Air Pressure Difference |
G23-93 | Standard Practice for Operating Light-Exposure Apparatus (Carbon-Arc-Type) With and Without Water for Exposure of Nonmetallic Materials |
PS 49-96 | Standard Practice for Application of Class PB Exterior Insulation and Finish System |
*Said CABO Code is further amended by adding an Appendix G to read as follows:
APPENDIX G
Performance Requirements For Exterior Insulation and Finish Systems (EIFS)
The system and its components shall meet or exceed the following performance standards.
1.0 System Performance
Characteristic | Test Method | Acceptance Criteria |
1.1 Abrasion Resistance | ASTM D 968 | No cracking, checking or loss of film integrity at 528-quarts (500 liters) of sand |
1.2 Accelerated Weathering | ASTM G 23 | No deleterious effects* after 2000 hours when viewed under 5X magnification |
1.3 Freeze/Thaw Resistance | Air dry at 120 degrees Fahrenheit minimum eight hours total immersion in water at 70 degrees Fahrenheit to 80 degrees Fahrenheit for eight hours then exposure to 20 degrees Fahrenheit for 16 hours. 10 cycles. No deleterious effects* viewed under 5X magnification | |
1.4 Mildew Resistance | ASTM D3273 | No growth supported during 28 day exposure time |
1.5 Salt Spray Resistance | ASTM B117 | No deleterious effects* at 300 hour exposure |
1.6 Tensile Adhesion | ASTM C297 | No failure in the adhesive, Base coat or finish coat. Minimum 5 PSI (34.5 kPa) Tensile strength before and after freeze/thaw and accelerated weathering test. |
1.7 Water Penetration | ASTM E331 | No water penetration beyond the plane of the base coat/Insulation board interface after 15-minutes at 6.24 psf (299 Pa), or 20% of positive design wind pressure, whichever is greater. |
1.8 Water Resistance | ASTM D2247 | No deleterious effects* at 14 day exposure. |
1.9 Wind Load | ASTM E330 | Withstand negative and positive wind loads required by building code. |
2.0 Component | ||
Performance: 2.1 Physical Properties and Requirements for EPS | ASTM C 578 | Meets TYPE I |
2.2 Physical Properties and Requirements for Polyisocyanuarate Thermal Insulation Board | ASTM C 1289 | Meets TYPE II |
*No deleterious effects: no cracking, checking, crazing, erosion, rusting, blistering, peeling or delamination.
* Said CABO Code is further amended by adding an Appendix H to read as follows:
APPENDIX H
REQUIREMENTS FOR DRAINAGE INSTALLED WITH EXTERIOR INSULATION AND FINISH SYSTEMS (EIFS)
1.01 Scope: | These requirements cover the drainage of water from wall construction incorporating EIFS and weather resistive barriers. Drainage is provided to prevent water intrusion beyond the water resistive barrier and to discharge water to the exterior. |
2.01 Reference Documents | ASTM Standards E 331 Test Method for Water Penetration of Exterior Windows, Curtain Walls, and Doors by Uniform Static Air Pressure Difference. |
3.01 Terminology | Descriptions of Terms Specific to This Standard: |
3.01.1 Drainage: | The collection and discharge of water gravity flow. |
4.01 | Drainage of Water |
4.01.1 | Walls incorporating EIFS and drainage shall be constructed to collect incidental water at the exterior outside faces of a weather resistive barrier and flashing. The wall assembly shall allow water collected at the outside faces of the weather resistive barrier and flashing to flow by gravity to the exterior. |
4.01.2 | The weather resistive barrier shall be integrated with the flashing to prevent water intrusion to the interior. |
4.01.3 | Drainage shall be confirmed by testing in accordance with ASTM E331 and Section 5.01. |
5.01 | Test Method For Determining The Drainage Performance of Wall Assemblies Clad With Exterior Insulation and Finish Systems (EIFS). |
This test method consists of testing EIFS clad wall assemblies for Drainage Performance by ASTM E331, Standard Test Method for Water Penetration of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference, except as described otherwise herein.
5.01.1 | Scope: This test method evaluates the drainage performance of EIFS when subjected to water applied in conjunction with a positive uniform static air pressure. |
5.01.2 | Test Method ASTM E331 |
5.01.3 | Apparatus ASTM E 331 for application of water and positive uniform static air pressure and a catchment to collect and measure drained water. |
5.01.4 | Test Specimen |
5.01.4.1 | The EIFS clad wall test specimens shall be a minimum of 4' X 8' (123 cm X 246 cm) |
5.01.4.2 | Minimum of four test specimens plus a control shall be assembled and allowed to cure for 28 days prior to test. The test specimens shall contain a fault. Dimensions and location of the fault are shown in figure H-1.0. |
5.01.4.3 | The EIFS assemblies shall be installed with the materials, details, and methods of assembly as required by the manufacturer. |
5.01.4.3.1 | For acceptance of wall assemblies with wood-based sheathing, the test wall shall include the sheathing to be accepted. |
5.01.4.4 | The supporting framework for the EIFS wall assemblies shall be of wood or metal stud construction with framing spacing as required by the manufacturer. The standard framing spacing is 16" (41 cm) o.c. |
5.01.4.5 | The test specimen shall be constructed to allow observation of drainage. |
5.01.5 | Test Procedure: |
5.01.5.1 | Test pressure difference shall be minimum 6.24 pounds per square foot (psf). |
5.01.5.2 | Water delivery to the exterior surface shall be uniform and at a rate of 5.0 Gallons per square foot hour. |
5.01.5.3 | Water and pressure duration shall be minimum 15 minutes. |
5.01.5.4 | Subject the four test specimens to the conditions in 5.1, and 5.3. Observe and Verify that specimens drain freely. |
5.01.5.5 | Allow each specimen to drain in the vertical position. |
5.01.5.6 | After one hour of drainage, select one of the test specimens; disassemble and verify drainage by observation. Note: Disassembly of wall must assure inspection of all wall components. Any water accumulation beyond incidental beading due to surface tension shall be reported. |
6.01 | REPORT |
6.01.1 | Follow ASTM E331 Sections 12.1.1, 12.1.2, 12.1.7, 12.1.9, 12.1.10, and 12.2 plus the following: |
6.01.2 | Observations from 5.4, 5.5, and 5.7. |
6.01.3 | Details of assembly, including a description of components, mixing and application, thickness of components and a statement of conformance to the manufacturer's application instructions. |
6.01.4 | Photographic video documentation of test specimens, including assembly, components, drainage verification, and samples removed in 5.8 |
6.01.5 | Detailed drawings of the test specimens. |
6.01.6 | A record of all points of water penetration to the cavity and drainage performance. |
*Said CABO Code is further amended by adding an Appendix I to read as follows:
APPENDIX I
Requirements For Drying Potential for Exterior Insulation and Finish Systems (EIFS)
1.01 | Scope: These requirements cover the potential for drying of wall construction incorporating EIFS and drainage. Drying of water in excess of 1 ounce per square foot shall be confirmed by testing in accordance with ASTM E331 and Section 2.01. |
2.01 | TEST METHOD |
2.01.1 | Follow Appendix "H", Requirements for Drainage Installed with Exterior Insulation Finish Systems (EIFS), Section 5.01 through 5.01.5.6. |
2.01.2 | Allow three test specimens plus the control specimen to dry in a conditioned space (73 degrees Fahrenheit ±4 degrees @ 50% Relative Humidity) For 72 hours. {NOTE: These are usually the same test specimens tested for drainage}. |
2.01.3 | After 72 hours of drying, cut three 12" X 12" (369 cm X 369 cm) samples to include all components of the assembly except framing from each test specimen and the control, as shown in figure 1-1.0. |
2.01.4 | Record observations. |
2.01.5 | Immediately weigh each sample and place in an oven controlled at 120±10 degrees Fahrenheit until constant weight is obtained. Record weight loss of each sample to the nearest .01 ounce. |
2.01.6 | Determine the average weight loss for the nine samples (TSRM) from the test specimens. Determine the average weight loss for the three control samples (CSBM). |
3.01 | TSRM - CSBM = SRM |
TSRM - Average residual moisture in nine test samples (oz.) CSRM - Average background moisture in three control samples (oz.) SRM - Average residual moisture in system per square foot; (ounce per square foot). | |
4.01 | REPORT A record of all weights as recorded in Section 2.01.5 and 2.01.6 to evaluate drying potential. |
5.01 | ACCEPTANCE SRM (Average Residual Moisture in system per square foot) shall not exceed 1 ounce per square foot. |
GEORGIA AMENDMENT TO THE 1994 STANDARD PLUMBING CODE
*Amend Section 507.8.4 of the 1994 Standard Plumbing Code to read as follows:
507.8.4 The discharge from the relief valve shall be piped full size separately to the outside of the building or to an indirect waste receptor so that any discharge can cause no personal injury or property damage and can be readily observed by the building occupants. In no case shall the discharge from a relief valve be trapped.
EXCEPTION: In basements or one and two family dwellings, the discharge from the relief valve may be piped upward when necessary. A thermal expansion control devise shall be installed in accordance with Section 613.2.1. An elbow shall be placed to the valve outlet and provisions shall be made at the low point for positive drainage.
*Said Plumbing Code is further amended by deleting in its entirety section 613.2 Thermal Expansion Control, and substituting the following in lieu thereof:
613.2 Thermal Expansion Control
If water is heated and stored in a consumer's system and the system has been closed by the installation of a backflow preventor or a pressure reducing valve, a thermal expansion control device shall be installed at an accessible location and in accordance with manufacturer's installation instruction. The device shall limit thermal expansion of the water being heated to not more than 80 pounds per square inch (552 kPa) static pressure at any fixture on the system. A potable water expansion tank or auxiliary relief valve set at 80 PSI (552 kPa) shall be acceptable.
The auxiliary relief valve shall be in addition to the eater heater safety relief valve. This thermal expansion control device shall be designed and trimmed for repeated operation. The valve shall have a minimum one-half inch pipe size. It shall be installed in accordance with manufacturer's installation instructions.
GEORGIA AMENDMENT TO THE 1995 CABO MODEL ENERGY CODE WITH GEORGIA SUPPLEMENTS AND AMENDMENTS
*Add the following footnote to Table 502.2 1a of the 1995 CABO Model Energy Code, to be designed as footnote 5 and renumber the remaining footnotes:
" 5. Slab edge insulation is not required for unheated slabs in areas of very heavy termite infestation probability as shown in Figure 4 contained in Chapter 8."
* The 1995 CABO Model Energy Code with Georgia Supplements and Amendments is further amended by deleting in their entirety the table concerning 3500 Heating Degree Days and 4500 Heating Degree Days in Chapter 6 of the Georgia Supplements and Amendments and substituting in lieu thereof the following:
Climate Zone 3500 HDD or less (Greater Atlanta Area) Low-rise residential WOOD FRAMING No Foam Insulation shall be installed within 6" of the ground on the outside of any wall (for detached one and two family dwellings only | ||||||
Option No. | Flat Ceiling Insulation R-value | Wall R-value | Window & Door Area | Window U-value R-value | Floor R-value | Masonry Basement Wall R-value |
Double pane metal with thermal break | ||||||
35A67 | R-30 | R-13 | 12.8% | 0.67 (R-1.49) | R-19 | R-5 |
35B67 | R-30 | R-14 | 13.4% | 0.67 (R-1.49) | R-19 | R-5 |
35C67 | R-30 | R-15 | 13.9% | 0.67 (R-1.49) | R-19 | R-5 |
35D67 | R-30 | R-16 | 14.5% | 0.67 (R-1.49) | R-19 | R-5 |
35E67 | R-30 | R-17 | 14.9% | 0.67 (R-1.49) | R-19 | R-5 |
35F67 | R-30 | R-19 | 15.4% | 0.67 (R-1.49) | R-19 | R-5 |
Double pane wood or vinyl | ||||||
35A56 | R-30 | R-13 | 15.8% | 0.56 (R-1.79) | R-19 | R-5 |
35B56 | R-30 | R-14 | 16.5% | 0.56 (R-1.79) | R-19 | R-5 |
35C56 | R-30 | R-15 | 17.0% | 0.56 (R-1.79) | R-19 | R-5 |
35D56 | R-30 | R-16 | 17.7% | 0.56 (R-1.79) | R-19 | R-5 |
35E56 | R-30 | R-17 | 18.2% | 0.56 (R-1.79) | R-19 | R-5 |
35F56 | R-30 | R-19 | 18.9% | 0.56 (R-1.79) | R-19 | R-5 |
Double pane wood or vinyl low-e | ||||||
35A52 | R-30 | R-13 | 17.3% | 0.52 (R-1.92) | R-19 | R-5 |
35B52 | R-30 | R-14 | 18.1% | 0.52 (R-1.92) | R-19 | R-5 |
35C52 | R-30 | R-15 | 18.6% | 0.52 (R-1.92) | R-19 | R-5 |
35D52 | R-30 | R-16 | 19.3% | 0.52 (R-1.92) | R-19 | R-5 |
35D52 | R-30 | R-17 | 19.9% | 0.52 (R-1.92) | R-19 | R-5 |
35F52 | R-30 | R-19 | 20.5% | 0.52 (R-1.92) | R-19 | R-5 |
Double pane wood or vinyl, low-e, inert gas | ||||||
35A47 | R-30 | R-13 | 19.5% | 0.47 (R-1.92) | R-19 | R-5 |
35B47 | R-30 | R-14 | 20.4% | 0.47 (R-1.92) | R-19 | R-5 |
35C47 | R-30 | R-15 | 20.9% | 0.47 (R-1.92) | R-19 | R-5 |
35D47 | R-30 | R-16 | 21.7% | 0.47 (R-1.92) | R-19 | R-5 |
35E47 | R-30 | R-17 | 22.3% | 0.47 (R-1.92) | R-19 | R-5 |
35F47 | R-30 | R-19 | 23.0% | 0.47 (R-1.92) | R-19 | R-5 |
Double pane wood or vinyl, low-e, inert gas & 1/2" air space or triple pane | ||||||
35A43 | R-30 | R-13 | 21.7% | 0.43 (R-2.33) | R-19 | R-5 |
35B43 | R-30 | R-14 | 22.7% | 0.43 (R-2.33) | R-19 | R-5 |
35C43 | R-30 | R-15 | 23.2% | 0.43 (R-2.33) | R-19 | R-5 |
35D43 | R-30 | R-16 | 24.1% | 0.43 (R-2.33) | R-19 | R-5 |
35E43 | R-30 | R-17 | 24.7% | 0.43 (R-2.33) | R-19 | R-5 |
35F43 | R-30 | R-19 | 25.6% | 0.43 (R-2.33) | R-19 | R-5 |
High performance double pane low-e, inert gas & 1/2" air space | ||||||
35A35 | R-30 | R-13 | 28.3% | 0.35 (R-2.58) | R-19 | R-5 |
35B35 | R-30 | R-14 | 29.4% | 0.35 (R-2.58) | R-19 | R-5 |
35C35 | R-30 | R-15 | 30.0% | 0.35 (R-2.58) | R-19 | R-5 |
35D35 | R-30 | R-16 | 30.9% | 0.35 (R-2.58) | R-19 | R-5 |
35E35 | R-30 | R-17 | 31.7% | 0.35 (R-2.58) | R-19 | R-5 |
35F35 | R-30 | R-19 | 32.7% | 0.35 (R-2.58) | R-19 | R-5 |
Note 1. May use R-19 on sloped ceilings and under HVAC up to 25% of ceiling Area.
Note 2. Wall R-value is R-value of cavity insulation plus stabilized (aged) R-value of sheathing rounded down to a whole number. 25% of exterior gross wall area may have plywood, OSB or gypsum (garage walls).
Note 3. Total area of all windows and doors in conditioned areas.
Note 4. Window and Door U-values are per U-value Default Table For Windows, Glazed Doors, Non-Glazed Door & Skylights or approved Testing Lab label. Door U-value shall be equal to or less than window U-values (up to 1% of openings U-value may be excluded (i.e. less than Table U-value) to allow for decorative glazing, fancy doors or skylights.
Note 5. R-value of insulation installed between floor joists.
Note 6. Use only if floor is not insulated or basement is conditioned. All doors and windows are included in window area. Stud walls shall be insulated same as Wall R-value. This applies to both "Code" basement walls (50% below grade) and walls in daylight basements that are less than 50% below grade. Code approved insulation be let exposed, all other insulation shall be covered with 1/2" gypsum (or other approved 15 minute thermal barrier).
Local Building Officials may develop additional tables for their area.
You are deemed to comply with the 1996 Georgia Energy Code if you build using one of these options.
Climate Zone 4500 HDD or less (North GA & Mountains) Low-rise residential WOOD FRAMING No Foam Insulation shall be installed within 6" of the ground on the outside of any wall (for detached one and two family dwellings only | ||||||
Option No. | Flat Ceiling Insulation R-value | Wall R-value | Window & Door Area | Window U-value R-value | Floor R-value | Masonry Basement Wall R-value |
Double pane metal with thermal break | ||||||
35A67 | R-38 | R-13 | 10.4% | 0.67 (R-1.49) | R-19 | R-7 |
35B67 | R-38 | R-14 | 11.1% | 0.67 (R-1.49) | R-19 | R-7 |
35C67 | R-38 | R-15 | 11.5% | 0.67 (R-1.49) | R-19 | R-7 |
35D67 | R-38 | R-16 | 12.1% | 0.67 (R-1.49) | R-19 | R-7 |
35E67 | R-38 | R-17 | 12.6% | 0.67 (R-1.49) | R-19 | R-7 |
35F67 | R-38 | R-19 | 13.1% | 0.67 (R-1.49) | R-19 | R-7 |
Double pane wood or vinyl | ||||||
35A56 | R-38 | R-13 | 12.8% | 0.56 (R-1.79) | R-19 | R-7 |
35B56 | R-38 | R-14 | 13.7% | 0.56 (R-1.79) | R-19 | R-7 |
35C56 | R-38 | R-15 | 14.1% | 0.56 (R-1.79) | R-19 | R-7 |
35D56 | R-38 | R-16 | 14.8% | 0.56 (R-1.79) | R-19 | R-7 |
35E56 | R-38 | R-17 | 15.4% | 0.56 (R-1.79) | R-19 | R-7 |
35F56 | R-38 | R-19 | 16.0% | 0.56 (R-1.79) | R-19 | R-7 |
Double pane wood or vinyl low-e | ||||||
35A52 | R-38 | R-13 | 14.20 | 0.52 (R-1.92) | R-19 | R-7 |
35B52 | R-38 | R-14 | 14.9% | 0.52 (R-1.92) | R-19 | R-7 |
35C52 | R-38 | R-15 | 15.4% | 0.52 (R-1.92) | R-19 | R-7 |
35D52 | R-38 | R-16 | 16.1% | 0.52 (R-1.92) | R-19 | R-7 |
35D52 | R-38 | R-17 | 16.8% | 0.52 (R-1.92) | R-19 | R-7 |
35F52 | R-38 | R-19 | 17.4% | 0.52 (R-1.92) | R-19 | R-7 |
Double pane wood or vinyl, low-e, inert gas | ||||||
35A47 | R-38 | R-13 | 15.8% | 0.47 (R-1.92) | R-19 | R-7 |
35B47 | R-38 | R-14 | 16.8% | 0.47 (R-1.92) | R-19 | R-7 |
35C47 | R-38 | R-15 | 17.3% | 0.47 (R-1.92) | R-19 | R-7 |
35D47 | R-38 | R-16 | 18.2% | 0.47 (R-1.92) | R-19 | R-7 |
35E47 | R-38 | R-17 | 18.8% | 0.47 (R-1.92) | R-19 | R-7 |
35F47 | R-38 | R-19 | 19.6% | 0.47 (R-1.92) | R-19 | R-7 |
Double pane wood or vinyl, low-e, inert gas & 1/2" air space or triple pane | ||||||
35A43 | R-38 | R-13 | 17.7% | 0.43 (R-2.33) | R-19 | R-7 |
35B43 | R-38 | R-14 | 18.7% | 0.43 (R-2.33) | R-19 | R-7 |
35C43 | R-38 | R-15 | 19.3% | 0.43 (R-2.33) | R-19 | R-7 |
35D43 | R-38 | R-16 | 20.2% | 0.43 (R-2.33) | R-19 | R-7 |
35E43 | R-38 | R-17 | 20.9% | 0.43 (R-2.33) | R-19 | R-7 |
35F43 | R-38 | R-19 | 21.7% | 0.43 (R-2.33) | R-19 | R-7 |
High performance double pane low-e, inert gas 1/2" air space | ||||||
35A35 | R-38 | R-13 | 23.0% | 0.35 (R-2.58) | R-19 | R-7 |
35B35 | R-38 | R-14 | 24.2% | 0.35 (R-2.58) | R-19 | R-7 |
35C35 | R-38 | R-15 | 24.9% | 0.35 (R-2.58) | R-19 | R-7 |
35D35 | R-38 | R-16 | 25.9% | 0.35 (R-2.58) | R-19 | R-7 |
35E35 | R-38 | R-17 | 26.7% | 0.35 (R-2.58) | R-19 | R-7 |
35F35 | R-38 | R-19 | 27.8% | 0.35 (R-2.58) | R-19 | R-7 |
Note 1. May use R-19 on slope ceilings and under HVAC up to 25% of ceiling Area
Note 2. Wall R-value is R-value of cavity insulation plus stabilized (aged) R-value of sheathing rounded down to a whole number. 25% of exterior gross wall area may have plywood, OSB or gypsum (garage walls).
Note 3. Total area of all windows and doors in conditioned areas.
Note 4. Window and Door U-values are per U-value Default Table For Windows, Glazed Doors, Non-Glazed Doors & Skylights or approve Testing Lab label. Door U-value shall be equal to or less than window U-values (up to 1% of openings U-value may be excluded (i.e less than Table U-value) to allow for decorative glazing, fancy doors or skylights.
Note 5. R-value of insulation installed between floor joists.
Note 6. Use only if floor is not insulated or basement is conditioned. All doors and windows are included in window area. Stud walls shall be insulated same as Wall R-value. This applies to both "Code" basement walls (50% below grade) and walls in daylight basements that are less than 50% below grade. Code approved insulation may be left exposed, all other insulation shall be covered with 1/2" gypsum (or other approved 15 minutes thermal barrier).
You are deemed to comply with the 1996 Georgia Energy Code if you build using one of these options.
The "Deemed to Comply" Approach
3500 HDD (Greater Atlanta Area) SINGLE STEP ENERGY CODE COMPLIANCE You are "deemed to comply" with the Georgia State Energy Code for Buildings if your structure meets the following conditions.
1. Your building shall be a one or two family detached dwelling
2. Your building shall not be larger in size than 5,000 square feat of conditioned floor space
3. Your building site must be located in an area of the state where climatic conditions shown in Chapter 3 of The Energy Code are 3500 Heating Degree Days (HDD) or less
4. Your building is three stories or less in height
5. You shall not make any substitutions of any kind for R-values listed below
6. Your window and door openings shall not exceed 19.0% of the gross (conditioned space) wall area
7. You shall comply with the Energy Code requirements for limiting air infiltration
8. Equipment efficiencies required by the Energy Code shall be observed
-Openings in gross wall area | 19.0% Maximum |
-Ceiling insulation* | R-30 |
-Floor Insulation | R-13 |
-Wall insulation, Fiberglass Batts | R-13 |
-Insulating Sheathing | R-3 |
-Basement Masonry wall insulation | R-7 |
-Slab Perimeter Insulation*** | R-0 |
-Windows, Double Pane or Single pane with Storm Window | R-1.79 (U-0.56) |
All R-values shall be printed on the actual insulation and be stabilized R-values
These R-values may result in some degree of "over-design". This was done so this method could apply to almost all one and two family residential construction built in Georgia (except mountains). If you must change one or more of the R-values listed to a lower R-value, then do not use this method. No substitutions are allowed here.
Instead, you may use one of the other methods to show compliance, such as the Climate Zone Table or Tradeoff Worksheet. You may use one of the "Chapter Approaches" of the actual CABO Model Energy Code 1995 Edition.
At the time a permit is requested, you shall state how you plan to meet the Georgia State Energy Code. When using this method you are not required to turn in any additional paperwork.
* Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and HVAC platforms may be insulated with R-19 batts, provided the R-19 batts do not exceed 25% of the total ceiling area and provided the flat portion of the ceilings is insulated to R-30.
** Plywood, OSB, or gypsum on garage walls may be used on 25% of opaque wall to meet corner bracing/structural requirements.
*** Unheated slabs, for heated slab consult local Building Official
The "Deemed to Comply" Approach 4500 HDD or Less (Mountains of North Georgia) SINGLE STEP ENERGY CODE COMPLIANCE
You are "deemed to comply" with the Georgia State Energy Code for Buildings if your structure meets the following conditions.
1.Your building shall be a one or two family detached dwelling
2. Your building shall not be larger in size than 5,000 square feet of conditioned floor space
3. Your building site must be located in an area of the state where climatic conditions shown in Chapter 3 of The Energy Code are 4500 Heating Degree Days (HDD) or less
4. Your building is three stories or less in height
5. You shall not make any substitutions of any kind for R-values listed below
6. Your window and door openings shall not exceed 17.8% of the gross (conditioned space) wall area
7. You shall comply with the Energy Code requirements for limiting air infiltration
8. Equipment efficiencies required by the Energy Code shall be observed
-Openings in gross wall area | 17.8% Maximum |
-Ceiling insulation* | R-30 |
-Floor Insulation | R-19 |
-Wall insulation, Fiberglass Batts | R-13 |
-Foam Sheathing Insulation** | R-4 |
-Basement Masonry wall insulation | R-8.5 |
-Slab Perimeter Insulation*** | R-4 |
-Windows, Double Pane or Single pane with Storm Window | R-1.92 (U-0.52) |
All R-values shall be printed on the actual insulation and be stabilized R-values
These R-values may result in some degree of "over-design". This was done so this method could apply to almost all one and two family residential construction built in south Georgia. If you must change one or more of the R-values listed to a lower R-value, then do not use this method. No substitutions are allowed here.
Instead, you may use one of the other methods to show compliance, such as the Climate Zone Table or Tradeoff Worksheet. You may use one of the "Chapter Approaches" of the actual CABO Model Energy Code 1995 Edition.
At the time a permit is requested, you shall state how you plan to meet the Georgia State Energy Code. When using this method you are not required to turn in any additional paperwork.
* Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, may be insulated with R-19 batts, provided the R-19 batts do not exceed 25% of the total ceiling area and provided the flat portion of the ceilings is insulated to R-38.
** May use Plywood/OSB for corner and required wall bracing 20% of gross wall area.
*** Unheated slabs, for heated slab use R-8 insulation. May eliminate slab-on-grade insulation by increasing the wall R-value by R-1 or increasing ceiling insulation from R-30 to R-38.
The "Deemed to Comply" Approach 4500 HDD (Mountain Area) SINGLE STEP ENERGY CODE COMPLIANCE
You are "deemed to comply" with the Georgia State Energy Code for Buildings if your structure meets the following conditions.
1. Your building shall be a one or two family detached dwelling
2. Your building shall not be larger in size than 5,000 square feet of conditioned floor space
3. Your building site must be located in an area of the state where climatic conditions shown in Chapter 3 of The Energy Code are 4500 Heating Degree Days (HDD) or less
4. Your building is three stories or less in height
5. You shall not make any substitutions of any kind for R-values listed below
6. Your window and door openings shall not exceed 16.2% of the gross (conditioned space) wall area
7. You shall comply with the Energy Code requirements for limiting air infiltration
8. Equipment efficiencies required by the Energy Code shall be observed
-Openings in gross wall area | 16.1% Maximum |
-Ceiling insulation* | R-38 |
-Floor Insulation | R-19 |
-Wall insulation, Fiberglass Batts | R-13 |
Insulating Sheathing | R-3 |
-Basement Masonry wall insulation | R-7 |
-Slab Perimeter Insulation*** | R-0 |
-Windows, Double Pane or Single pane with Storm Window | R-1.92 (U-0.52) |
All R-values shall be printed on the actual insulation and be stabilized R-values
These R-values may result in some degree of "over-design". This was done so this method could apply to almost all one and two family residential construction built in Georgia (except mountains). If you must change one or more of the R-values listed to a lower R-value, then do not use this method. No substitutions are allowed here.
Instead, you may use one of the offer methods to show compliance, such as the Climate Zone Table or Tradeoff Worksheet. You may use one of the "Chapter Approaches" of the actual CABO Model Energy Code 1995 Edition
At the time a permit is requested, you shall state how you plan to meet the Georgia State Energy Code.
When using this method you are not required to turn in any additional paperwork.
* Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation and HVAC Platforms may be insulated with R-19 bars, provided the R-19 batts do not exceed 25% of the total ceiling area and provided the flat portion of the ceilings is insulated to R-38.
** Plywood, OSB or gypsum on garage walls may be used on 25% of opaque wall to meet corner bracing/structural requirements.
*** Unheated slabs, for heated slab consult the Local Building Official
*The 1995 CABO Model Energy Code with Georgia Supplements and Amendments is hereby further amended by amending Section 702.1.3 of Chapter 7 to read as follows:
702.1.3 | Modify 402.3.2 by adding the following: "Slab perimeter insulation shall be done in accordance with the trade-off procedures of this Chapter or ASHRAE published procedures." |
* The 1995 CABO Model Energy Code with Georgia Supplements and Amendments is hereby further amended by revising figure 3 in Chapter 8 and by adding a figure 4 to Chapter 8 and renumbering the remaining figures as follows:
ANNUAL FARENHEIT (Celsius) HEATING DEGREE DAYS (in thousands) (65° F. BASE) 1Insulation shall be installed at least the minimum distance shown in the table below measured from the top of the slab. 2Slab edge insulation is not required for unheated slabs in areas of very heavy termite infestation probability as shown in Figure 4 contained in Chapter 8.
For SI: 1 h*ft.2. °F./Btu = 0.176 m2. k/W. °F. = 1.8°C. ÷ 32.
HEATING DEGREE DAYS MINIMUM DISTANCE
HEATED | 500-5,999 | 24 inches |
SLABS | [GREATER -THAN OR EQUAL TO]6,000 | 48 inches |
UNHEATED | 2,500-5,999 | 24 inches |
SLABS | [GREATER -THAN OR EQUAL TO] 6,000 | 48 inches |
FOR SI: 1 inch = 25.4 mm
Ga. Comp. R. & Regs. R. 110-11-1-.04
O.C.G.A. Sec. 8-2-20.