Table of New Transmission Line and Substation Standards | |||
KV Rating | Property Boundary of new Substation | Edge of Transmission Line Right-of-Way | On the Transmission Line Right-of-Way |
<=230 kV | 2.00 kV/m & 150 milliGauss | 2.00 kV/m & 150 milliGauss | 8 kV/m |
<=500 kV and > 230 kV | 2.00 kV/m & 200 milliGauss [1] | 2.00 kV/m & 200 milliGauss [1] | 10 kV/m |
>500 kV | 5.50 kV/m & 250 milliGauss | 5.50 kV/m & 250 milliGauss | 15 kV/m |
Footnote 1: Except as provided in paragraphs (2)(g) and (2)(i).
Fla. Admin. Code Ann. R. 62-814.450
Rulemaking Authority 403.061(7), 403.523(1) FS. Law Implemented 403.061(31), 403.523 FS.
New 3-21-89, Amended 1-7-93, Formerly 17-274.450, 17-814.450, Amended 6-1-08.