Section 62-550.315 - Primary Drinking Water Standards: Treatment Technique Requirements
(1) Control of Acrylamide and Epichlorohydrin - This subsection applies to all public water systems using acrylamide or epichlorohydrin.
(a) Each system using acrylamide or epichlorohydrin shall certify annually in writing to the Department that the combination of dose and monomer level does not exceed the following levels:
1. Acrylamide = 0.05 percent dosed at one part per million (or equivalent).
2. Epichlorohydrin = 0.01 percent dosed at 20 parts per million (or equivalent).
(b) Certifications required by paragraph (a) above may rely on appropriate manufacturer or third party certifications.
(2) Filtration and Disinfection (Surface Water Treatment) - This subsection applies only to subpart H systems. Filtration and disinfection treatment technique requirements are specified in Rule 62-550.817, F.A.C.
(3) Control of Lead and Copper - This subsection applies only to community water systems and non-transient non-community water systems. The treatment technique requirements for control of lead and copper are specified in 40 CFR 141, subpart I, as adopted under Rule 62-550.800, F.A.C.
(4) Control of Disinfection Byproduct Procursors (Enhanced Coagulation or enhanced Softening) - This subsection applies only to community or non-transient non-community water systems that are subpart H systems using conventional filtration treatment. The treatment technique requirements for control of disinfection byproduct precursors are specified in 40 CFR 141, subpart L, as adopted and modified under Rule 62-550.821, F.A.C.

Fla. Admin. Code Ann. R. 62-550.315

Rulemaking Authority 403.861(9) FS. Law Implemented 403.852(12), 403.853(1), 403.861(17) FS.

New 11-27-01, Amended 4-3-03.