5702.1 Each new hazardous substance UST shall be:
(a) Constructed of fiberglass-reinforced plastic, steel- fiberglass-reinforced plastic composite, or steel;(b) If constructed of steel, cathodically protected in accordance with the requirements of § 5702.2; and(c) Of three hundred sixty degree (360°) double-wall construction as set forth in § 5702.4.5702.2 Each steel tank shall be cathodically protected by being coated with a suitable dielectric material, and:
(a) The field- installed cathodic protection systems shall be designed by a corrosion expert; and(b) The impressed current cathodic protection systems shall be designed to allow determination of current operating status as required by § 5901.5.5702.3 Each cathodic protection system shall be operated and maintained in accordance with § 5901.
5702.4 Double-walled tanks shall be designed, constructed, and installed in a manner that will:
(a) Contain a release from any portion of the inner tank within the outer wall until detected and removed;(b) Detect the failure of the inner or outer wall;(c) Prevent the release of regulated substances to the environment at any time during the operational life of the UST; and(d) Check for evidence of a release at least every thirty (30) days.5702.5 The codes of practice listed in §§ 5701.10(a) and (b) may be used to comply with § 5702.1
D.C. Mun. Regs. tit. 20, r. 20-5702
Final Rulemaking published at 40 DCR 7835, 7854 (November 12, 1993); as amended by Final Rulemaking published at 46 DCR 7699 (October 1, 1999); amended by Final Rulemaking published at 67 DCR 1778 (2/21/2020)