Insert new Sections 6.4.1.1.1 and 6.4.1.1.2 in ASHRAE 90.1 in the Energy Conservation Code-Commercial Provisions to read as follows:
Higher-Efficiency Requirements. All building projects complying with the Alternate Renewables Approach in Section 13.1.1.2 shall comply with the equipment efficiency requirements in Section 13.1.1.2 in place of Tables 6.8.1-1 through 6.8.1-11 and shall comply with the applicable ENERGY STAR heating and cooling requirements in Section 10.11.2.
Heat Pump Requirement. For spaces which are both heated and cooled using unitary systems per Tables 6.8.1-1 through 6.8.1-2, and Table 6.8.1-4, heating shall also include use of a heat pump for primary heating. Packaged systems shall not include electric resistance heating unless used as back-up heat and controlled per Section 6.4.3.5.
Exceptions:
Strike Section 6.4.3.8 of ASHRAE 90.1 in its entirety and insert new Sections 6.4.3.8 and 6.4.3.8.1 in its place in the Energy Conservation Code-Commercial Provisions to read as follows:
Ventilation Controls for High-Occupancy Areas. Demand control ventilation (DCV) shall be provided for densely occupied spaces served by systems with one or more of the following:
Exceptions to Section 6.4.3.8:
Design of DCV System. The DCV system shall be designed to be in compliance with Section 6.2.7 of ANSI/ASHRAE Standard 62.1-2013. Occupancy assumptions shall be shown in the design documents for spaces provided with DCV. All CO2 sensors used as part of a DCV system or any other system that dynamically controls outdoor air shall meet the following requirements:
Strike Section 6.4.4.1.2 of ASHRAE 90.1 in its entirety and insert a new Section 6.4.4.1.2 in its place in the Energy Conservation Code-Commercial Provisions to read as follows:
Duct and Plenum Insulation. All supply and return ducts and plenums installed as part of an HVAC air distribution system shall be thermally insulated in accordance with Tables 6.8.2-1 and 6.8.2-2. Building projects complying with Chapter 13 shall instead reference Normative Appendix A, ASHRAE 189.1-2014, Table A-2, Minimum Duct Installation R-Value Heating and Cooling-Only Supply Ducts and Return Ducts (I-P), and Table A-3, Minimum Duct Installation R-Value Combined Heating and Cooling Supply Ducts and Return Ducts (I-P).
Exceptions:
Strike Section 6.4.4.1.3 of ASHRAE 90.1 in its entirety and insert a new Section 6.4.4.1.3 in its place in the Energy Conservation Code-Commercial Provisions to read as follows:
Piping Insulation. Piping, including but not limited to, all branch piping and piping components, shall be thermally insulated in accordance with Tables 6.8.3-1 and 6.8.3-2.
Exceptions:
Strike Table 6.5.1-1 and 6.5.1-2 of ASHRAE 90.1 in their entirety and insert new Table 6.5.1-1 in the Energy Conservation Code in their place to read as follows:
TABLE 6.5.1-1 Minimum Fan-Cooling Unit Size for which an Economizer is Required for Comfort Cooling
Climate Zones | Cooling Capacity for Which an Economizer is Required |
1a, 1b | No economizer requirement |
2a, 2b, 3a, 4a, 5a, 6a 3b, 3c, 4b, 4c, 5b, 5c, 6b, 7, 8 | > 33,000 Btu/ha |
a. Where economizers are required, the total capacity of all systems without economizers shall not exceed 480,000 Btu/h (140 kW) per building or 10% of the building's installed cooling capacity, whichever is greater. |
D.C. Mun. Regs. tit. 12, 12-I6.4