Insert a new Exception 3 to Section 1023.3.1 to read as follows:
Separation between an interior exit stairway or ramp and the exit passageway extension shall not be required when the interior exit stair and the exit passageway extension are pressurized in accordance with Section 909.20.5.
Strike Section 1023.9 of the International Fire Code in its entirety and insert a new Section 1023.9 into the Fire Code in its place to read as follows:
Stairway signage. Signs shall be provided for all interior exit stairways and ramps connecting more than three stories, and for all interior exit stairways and ramps in buildings with three or more interior exit stairways or ramps.
Signs outside stairway.A sign shall be provided at each entrance to the exitstairway and ramp, identifying the stair or ramp with the same designations used for the stairway identification signs in Section 1023.9.2.1. The sign also shall state "EXIT" in accordance with Section 1013.4 of the Fire Code. The sign shall state the required text in visual characters, in raised characters, and in braille complying with ICC A117.1.
Signs inside stairway.Stairway identification signs, floor-level signs, and exit discharge signs shall comply with the following requirements:
Stairway identification signs. A stairway identification sign shall be provided at each floor landing in the interior exit stairway and ramp designating the floor level, the terminus of the top and bottom of the interior exit stairway or ramp and the identification of the stair or ramp. The signage shall also identify the story of, and the direction to, the exit discharge and the availability of roof access from the interior exit stairway and ramp for the fire department. The sign shall be located entirely between 5 feet (1524 mm) and 8 feet (2438 mm) above the floor landing in a position that is readily visible when the doors are in the open and closed positions and located so that occupants egressing from floors that are more remote from the exit discharge will face the sign frontally at some point in their path of egress.
Exception: Stairway identification signs are not required to identify the story of and direction to the exit discharge in interior exit stairways and ramps that connect less than three stories.
Signage requirements.Stairway identification signs shall comply with all of the following requirements:
Floor-level signs. In addition to the stairway identification sign, a floor- level sign in visual characters, raised characters and braille complying with ICC A117.1 shall be located at each floor- level landing adjacent to the door leading from the interior exit stairway and ramp into the corridor or other building space to identify the floor level.
Exit discharge signs.A sign stating "EXIT" in visual characters, raised characters and braille shall be located adjacent to the door to the exit discharge in accordance with Section 1013.4 of the Fire Code.
D.C. Mun. Regs. tit. 12, r. 12-H1023