607.5.4 Corridors/smoke barriers.Corridor dampers, ceiling radiation dampers and smoke dampers in corridors and smoke barriers shall be provided as required in Sections 607.5.4.1 and 607.5.4.2. Smoke dampers and smoke damper actuation methods shall comply with Section 607.5.4.3.
607.5.4.1 Corridors. Duct and air transfer openings that penetrate corridors shall be protected with dampers as follows:
1. A corridor damper shall be provided where corridor ceilings, constructed as required for the corridor walls as permitted in Section 708.4, Exception 3 of the Building Code, are penetrated.2. A ceiling radiation damper shall be provided where the ceiling membrane of a fire-resistance-rated floor-ceiling or roof-ceiling assembly, constructed as permitted in Section 708.4, Exception 2 of the Building Code, is penetrated.3. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a corridor enclosure required to have smoke and draft control doors in accordance with Section 716.5.3 of the Building Code. Exceptions:
1.Corridor dampers, ceiling radiation dampers and smoke dampers are not required in corridor penetrations where: (a) the building is equipped throughout with an approved smoke control system in accordance with Section 513 and(b)smoke dampers are not necessary for the operation and control of the system.2.Corridor dampers, ceiling radiation dampers and smoke dampers are not required in corridor penetrations where: (a) the duct is constructed of steel not less than 0.019 inch (0.48 mm) in thickness and(b) there are no openings serving the corridor.3.Smoke dampers are not required in ducted corridor penetrations where: a. The building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 of the Building Code;b. The duct is constructed of steel no t less than 0.019 inches (0.48 mm) in thickness;c. The ducted system supplies outdoor air only to the corridor and to air-handling units that serve spaces adjoining the corridor through ducted connections; andd. The outdoor air supply fan is designed to provide a continuous airflow.607.5.4.2 Smoke barriers. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a smoke barrier. Smoke dampers and smoke damper actuation methods shall comply with Section 607.5.4.3.
Exceptions:
1.Smoke dampers are not required where the openings in ducts are limited to a single smoke compartment and the ducts are constructed of steel.2.Smoke dampers are not required in smoke barriers required by Section 407.5 of the Building Code for Group I-2, Condition 2, where the HVAC system is fully ducted in accordance with Section 603 and where the building is equipped throughout with (a) an automatic sprinkler system in accordance with Section 903.3.1.1 of the Building Code and with (b) quick-response sprinklers in accordance with Section 903.3.2 of the Building Code.607.5.4.3 Smoke damper actuation. Smoke dampers shall close as required by Section 607.3.3.2.
Strike Section 607.5.5 of the International Mechanical Code in its entirety and insert new Section 607.5.5 to the Mechanical Code in its place to read as follows: