NOTE: If approval cannot be issued within 10 working days, the property owner or authorized agent shall be notified of the delay and a tentative date of approval or denial shall be given. However, if no property owner or authorized agent contact number provided the Department will contact the Class D soil scientist. Once approved, the report shall be mailed to the property owner or his/her authorized agent. A percentage of randomly chosen site evaluations submitted shall be field verified by DNREC staff. Site evaluations' requiring test pits should be scheduled with the Department 72 hours prior to conducting the site evaluation.
At the discretion of the Department or Class D soil scientist, additional methodologies may be preferred as a substitute for the soil percolation test. Approved test methods are given in the current edition of Methods of Soil Analysis, ASA and the ASTM Standards.
A = 0.33 Q (t)0.5
Where:
A = the minimum disposal area required in square feet
Q = wastewater application rate in gallons per day
t = the average percolation rate in minutes per inch (minimum rate is 20 mpi for design)
A = 0.42 Q (t)0.5
Where:
A = the minimum disposal area required in square feet
Q = wastewater application rate in gallons per day
t = the average percolation rate in minutes per inch (minimum rate is 20 mpi for design)
A = 1.2 Q
Where:
A = the minimum disposal area required in square feet
Q = design flow rate in gallons per day
A = UQ
Where:
A = the minimum disposal are required in square feet
Q = design flow rate in gallons per day
U = unit absorption area (see Exhibit P)
HAR = sum (incremental loading rate (in site evaluation) (see Exhibit V)) X (thickness of each horizon (inches) to a depth of 20 inches)
EAA = Q/LTAR
Where:
Q = design flow rate in gallons per day
LTAR = long term acceptance rate (see Section 5.3.2.6.1)
EAW = HAR/(1.2 - LTAR)
Where:
HAR = horizontal acceptance rate (see Section 5.3.2.6.2)
LTAR = long term acceptance rate (see Section 5.3.2.6.1)
NOTE: An effective width of four (4) to nine (9) feet is appropriate. The designer should use an EAW that is <= the calculated value. If the calculated value is > 10 feet then limit the EAW to 10 feet.
AL = EAA/EAW
NOTE: Minimum bury depth requirements apply to all pressurized transmission piping - see Section 5.3.9.2.
Sussex - 24 inches Kent - 24 inches New Castle - 30 inches
Percolation Rate | Maximum Hole Spacing |
20 - 25 MPI | 60 inches |
30 - 60 MPI | 72 inches |
65 - 120 MPI | 96 inches |
NOTE: Trench systems designed on slopes > 5% must provide for balanced trench loading rates (gpd/ft2).
Disposal systems shall not be constructed on sites where curtain drains, vertical drains, under drains, or similar drainage methods are utilized to artificially lower the level of the water table to meet the requirements of these Regulations. Observation wells may be used to demonstrate the change in the hydrology of a particular property for the purpose of siting an on-site wastewater treatment and disposal system.
NOTE: PVC pipe caps drilled with holes is not a permissible substitute for the screen.
The Department shall make a decision on the application which it determines will best implement the purposes of 7Del.C.Ch. 60 and these Regulations. Providing of the requisite information in the application procedure by the applicant shall not be construed as a mandatory prerequisite for the issuance of the permit by the Department.
Biosolid Type | Percent Solids |
Liquid | < 15% |
Cake | 15 - 35% |
Dried | > 35% |
Sandy Fill Gradation Requirements
Sieve Size | Maximum Percentage Passing Sieve |
3/8" | 100% |
#4 | 95-100% |
#50 | 5 - 30% |
#100 | 1- 7% |
Aggregate Sizing Requirements
Sieve Size | Maximum Percentage Retained | Minimum Percentage Passing Sieve |
2 1/2" | 0% | 100% |
2" | 0-3% | 97-100% |
1 1/2" | 5-10% | 90-95% |
1" | 50-80% | 20-50% |
1/2" | 25-35% | 10-25% |
#4 | 0-5% | 0-5% |
#8 | 0% | 0% |
Tire Chip Sizing Requirements
Sieve Size | Percentage Passing Sieve |
4" | 100% minimum |
2" | 25% minimum |
#4 | 5% maximum |
NOTE: The tire shreds shall have less than one (1)% (by weight) of metal fragments that are not at least partially encased in rubber. Metal fragments shall protrude no more than one (1) inch on 100% of the pieces and no more than one half (1/2) inch on 75% of the pieces (by weight). In no case shall the tire shreds contain the remains of tires that have been subjected to a fire.
NOTE: The Class E system contractor shall submit upon request a Certification of Materials for fill, aggregate and/or tire chips used in systems. This certificate shall be obtained from the supplier.
NOTE: If an inspection has occurred within the previous 36 months and the property owner can provide documentation of such pump out and inspection, then such documentation will fulfill the requirements of 5.4.6.3.
NOTE: Report if area under the dwelling is not accessible.
NOTE: Report if access to dwelling is not available.
DISCLAIMER: The International Plumbing Code shall apply to the erection, installation, alteration, repairs, relocation, replacement, addition to, use or maintenance of plumbing systems (e.g. building drains) however this does not preclude others from visually inspecting the building drain for separate systems leaving the building.
NOTE: In a properly functioning system, the water level should not be above the invert of the outlet pipe. If the water level is above the invert of the outlet pipes, this can be an indicator that ponding may be occurring in the drainfield. Special attention should be given to the NOTE: in 5.4.6.3.13.3 as this condition in the distribution box along with probing throughout the drainfield may eliminate the need for additional excavation.
DISCLAIMER: All Occupational Safety and Health Act (OSHA) regulations must be complied with during all phases of system installation and inspection. OSHA regulations can be found at www.osha.gov or by contacting the U.S. Department of Labor.
DISCLAIMER: All electrical work must meet all currently adopted State and National Electrical Codes where applicable (Admin Code, Title 24, § 1400).
NOTE: Look for wet or depressed areas with lush vegetation.
NOTE: While probing the drainfield, care should be taken to observe the apparent operating condition of the drainfield. If, in the opinion of the inspector, there appears to be ponding in the drainfield, additional excavation, to determine the extent of the ponding and the systems functionality, may be necessary.
NOTE: Look for wet, depressed areas with lush vegetation.
NOTE: Look for wet, depressed areas with lush vegetation.
NOTE: If metal tank is encountered, it must be removed and properly disposed of.
7 Del. Admin. Code § 7101-5.0