7 Del. Admin. Code § 1146-5.0

Current through Register Vol. 28, No. 1, July 1, 2024
Section 1146-5.0 - SO[2] Emissions Limitations
5.1 From May 1, 2009 though December 31, 2011, no coal fired unit subject to this regulation shall emit SO2 at a rate exceeding 0.37 lb/MMBTU heat input.
5.1.1 Compliance with the requirements of 5.1 of this regulation shall be demonstrated on a 24-hour rolling average basis.
5.1.2 SO2 emissions from multiple units subject to this regulation at a common facility may be averaged on a heat input basis to demonstrate compliance with the requirements of 5.1 of this regulation.
5.2 On and after January 1, 2012, no coal-fired unit subject to this regulation shall emit SO2 at a rate exceeding 0.26 lb/MMBTU heat input, demonstrated on a rolling 24-hour average basis.
5.3 On and after January 1, 2009, no unit subject to this regulation shall emit annual SO2 mass emissions that exceed the values shown in Table 5-1 of this regulation.
5.3.1 From January 1, 2009 through December 31, 2011, compliance with the requirements of 5.3 of this regulation may be achieved by demonstrating that the total number of tons of SO2 emitted from a common facility does not exceed the sum of the tonnage limitations for all of the units subject to this regulation at that facility.
5.3.2 Compliance with the requirements of 5.3 of this regulation shall not be achieved by using, tendering, or otherwise acquiring SO2 allowances under any state or federal emission trading program.
5.3.3 For the purpose of determining compliance with the requirements of 5.3 of this regulation, the total tons for a specified period shall be calculated as the sum of all recorded hourly emissions, with any remaining fraction of a ton equal to or greater than 0.50 ton deemed to equal one ton and any remaining fraction of a ton less than 0.50 ton deemed equal to zero tons.
5.4 Compliance with the requirements of 5.1 through 5.3 of this regulation shall be demonstrated with a continuous emissions monitoring system that is installed, calibrated, operated and certified in accordance with 40 CFR Part 75 (May 18, 2005 amendment) or other method approved by the Department and the Administrator, and meeting the monitoring and reporting requirements of 40 CFR Part 96, subpart HHH (April 28, 2006 amendment).
5.5 On and after January 1, 2009, no residual oil with a sulfur content in excess of 0.5%, by weight, shall be received for any residual oil-fired unit subject to this regulation.
5.5.1 Compliance with the requirements of 5.5 of this regulation shall be demonstrated by fuel oil sampling and analysis. Samples shall be collected:
5.5.1.1 From the transport vessel for each shipment of residual fuel oil received at the facility for combustion in the subject residual oil-fired unit, or
5.5.1.2 From the supply pipeline each day residual oil is delivered to the facility via pipeline for combustion in a residual oil-fired unit subject to this regulation, after sufficient fuel oil has been drained from the sampling line to remove any fuel oil that may have been standing in the sampling line, or
5.5.1.3 From the supply pipeline at the inlet to the residual oil-fired unit subject to this regulation each day the unit fires any quantity of oil fuel, after sufficient fuel oil has been drained from the sampling line to remove any fuel oil that may have been standing in the sampling line.
5.5.2 Fuel oil samples shall be analyzed in accordance with ASTM D 129-00, ASTM D 1552-03, ASTM D 2622-05, or ASTM D 4294-03.