7 Del. Admin. Code § 1144-4.0

Current through Register Vol. 28, No. 1, July 1, 2024
Section 1144-4.0 - Operating Requirements
4.1 An emergency generator may operate for an unlimited number of hours during an emergency.
4.2 An emergency generator may operate for an unlimited number of hours during testing or for maintenance purposes, pursuant to the definition of an emergency generator, except as restricted by 4.4 of this regulation.
4.3 A distributed generator may operate at any time, except as restricted by 4.4 of this regulation.
4.4 No emergency or distributed generator shall be used during testing or for maintenance purposes before 5 p.m. on a day which has a Ground Level Ozone Pollution Forecast or Particle Pollution Forecast of "Code Red" or "Code Orange" as announced by the Department.
4.5 Despite of this regulation, an emergency generator may be tested on any day that such testing is required to meet National Fire Protection Association (NFPA) or Joint Commission on Accreditation of Healthcare Organizations (JCAHO) standards.

01/11/2006

7 Del. Admin. Code § 1144-4.0