Total Parking in Lot | Required Minimum Number of Accessible Spaces |
1 to 25 | 1 |
26 to 50 | 2 |
51 to 75 | 3 |
76 to 100 | 4 |
101 to 150 | 5 |
151 to 200 | 6 |
201 to 300 | 7 |
301 to 400 | 8 |
401 to 500 | 9 |
501 to 1000 | * |
1001 and over | ** |
* 2 percent of total
** 20 plus 1 for each 100 over 1000
Exception: The total number of accessible parking spaces may be distributed among parking lots, if greater accessibility is achieved.
Exception: This does not apply to parking provided for official government vehicles owned or leased by the government and used exclusively for government purposes.
Exception: These provisions are not mandatory for single user portable toilet or bathing units clustered at a single location; however, at least one toilet unit complying with 603 or one bathing unit complying with 603 should be installed at each location whenever standard units are provided.
Exception. Elevator pits, elevator penthouses, mechanical rooms, piping or equipment catwalks are excepted from this requirement.
Exception: Accessible ramps complying with 405 or, if no other alternative is feasible, accessible wheelchair lifts complying with 410 may be used in lieu of an elevator.
Exception: In multiple story buildings and facilities where at-grade egress from each floor is impossible, either of the following is permitted:
Exception: Areas of rescue assistance are not required if the building is protected throughout by an approved automatic sprinkler system and meets all the requirements of the State Fire Prevention Regulations.
Exception: The Tactile signage provisions of 703 are not mandatory for temporary information on room and space signage, such as current occupant's name.
Number of Public Telephones Provided on Each Floor | Number of Telephones Required to be Accessible* |
1 or more single unit installations | 1 per floor |
1 bank* | 1 per floor |
2 or more banks** | 1 per bank. Accessible unit may be installed as a single unit in proximity (either visible or with signage) to the bank. At least one public telephone per floor shall meet requirements for a forward reach telephone*** |
* Additional public telephones may be installed at any height. Unless otherwise specified, accessible telephones may be either forward or side reach telephones.
** A bank consists of two or more adjacent public telephones, often installed as a unit.
*** Exception: For exterior installations only, if dial tone first service is not available, then a side reach telephone may be installed instead of the required forward reach telephone (i.e., one telephone in proximity to each bank shall comply with 704).
Capacity of Seating and Assembly Areas | Number of Required Wheelchair Locations |
50 to 75 | 3 |
76 to 100 | 4 |
101 to 150 | 5 |
151 to 200 | 6 |
201 to 300 | 7 |
301 to 400 | 8 |
401 to 500 | 9 |
501 to 1,000 | * |
Over 1,000 | ** |
* 2 percent of total
** 20 plus 1 for each 100 over 1000
Exception: In projects consisting of one-to-four family dwellings where accessible entrances would be extraordinary costly due to site conditions or local code restrictions, accessible entrances are required only to those buildings containing accessible dwelling units.
Facilities | Application |
Admitting audiences | All areas which will require |
Amusement arcades | public or employee access |
Amusement park structure | |
Arenas | |
Armories | |
Art Galleries | |
Auditoriums | |
Banquet Halls | |
Bleachers | |
Bowling Alleys | |
Carnivals | |
Churches | |
Clubs | |
Community Halls | |
Courtrooms (public areas) | |
Dance Halls | |
Drive-In theaters | |
Exhibition Halls | |
Fairs | |
Funeral Parlors | |
Grandstands | |
Gymnasiums | |
Indoor & Outdoor swimming pools | |
Indoor & Outdoor tennis courts | |
Lecture Halls | |
Libraries | |
Motion picture theaters | |
Museums | |
Night Clubs | |
Passenger Stations | |
Pool & Billiard Halls | |
Restaurants | |
Skating | |
Stadiums | |
Taverns & Bars | |
Television studio | |
Theaters |
Facilities | Application |
Animal Hospitals, Kennels, Pounds | All areas which will require |
Automobile and other motor vehicle | public or employee access |
showrooms | |
Banks | |
Barber shops | |
Beauty shops | |
Car Wash | |
Civic administration | |
Clinic, outpatient | |
Dry cleaning | |
Educational above 12th grade | |
Electronic data processing | |
Fire Stations | |
Florists & Nurseries | |
Laboratories; testing & research | |
Laundries | |
Motor vehicle service stations | |
Police stations | |
Post offices | |
Print shops | |
Professional services: | |
Attorney, dentist | |
Physician, engineer, etc. | |
Radio & T.V. stations | |
Telephone exchanges |
Facilities | Application |
Academics | All areas shall comply |
Kindergarten | |
Nursery Schools | |
Schools |
Facilities | Application |
Aircraft | All areas which will require |
Applicances | public or employee access |
Athletic equipment | |
Automobile and other motor vehicles | |
Bakeries | |
Beverages | |
Bicycles | |
Boats, building | |
Brick and masonry | |
Broom or brush | |
Business machines | |
Canvas or similar | |
Cameras & photo equipment | |
Carpets & rugs including cleaning | |
Ceramic products | |
Clothing | |
Construction & agricultural machinery | |
Disinfectants | |
Dry cleaning & dyeing | |
Electronics | |
Engines, including re-building | |
Film, photographic | |
Food Processing | |
Foundaries | |
Furniture | |
Glass products | |
Gypsum | |
Hemp products | |
Ice | |
Jute products | |
Laundries | |
Leather Products | |
Machinery | |
Metal | |
Motion pictures & T.V. films | |
Musical instruments | |
Optical goods | |
Paper products | |
Printing or publishing | |
Recreational vehicles | |
Refuse incineration | |
Shoes | |
Soaps & detergents | |
Steel products: fabrication, assembly | |
Textiles | |
Tobacco | |
Trailers | |
Upholstering | |
Wood, distribution | |
Millwork | |
Woodworking, cabinets |
Facilities | Application |
Combustible dust | All areas which will require |
Combustible fibers | public or employee access |
Combustible liquid | |
Corrosive liquids | |
Explosive materials | |
Flammable liquid | |
Flammable gas | |
Liquefied petroleum gas | |
Nitromethane | |
Oxidizing materials | |
Organic peroxide |
Facilities | Application |
Child care facilities | All public use, common use, or |
employee areas |
Facilities | Application |
Long Term Care Facilities (including | At least 50% of patient toilet and |
Skilled Nursing Facilities, | bedrooms: all public use, |
Intermediate Care | common use, or employee |
areas | |
Facilities, Bed & Care and all | All patient toilet and bedrooms, |
Nursing Homes | public use, common use, or |
Outpatient facilities | employee use |
Hospital, General Purpose | At least 10% of patient toilet and |
bedrooms, all public use, | |
common use, or employee | |
Special Purpose Hospital: (Hospitals that | All patient toilet and bedrooms, |
treat conditions that affect mobility) | all public use, common use, |
or employee areas |
Facilities | Application |
Jails or other detention or correctional | Five percent of residential |
units | prisons available, or at least |
one unit, whichever is greater; | |
all common use, visitor, or | |
employee areas |
Facilities | Application |
Department stores | All areas for which the |
Drug stores | intended use will require |
Markets | public or employee access |
Retail stores | |
Shopping centers | |
Sales rooms |
Facilities | Application |
Hotels or Motels | Five percent of total units or at |
Boarding Houses | least one, whichever is greater, |
and all public u se, common | |
use, and employee areas |
Facilities | Application |
Multifamily housing | In projects of four (4) or more |
(Apartment Houses): | units, 5 percent of the total units, |
or at least one, whichever is | |
greater, shall be made adaptable | |
in accordance with the most | |
recent edition of ICC/ANSI | |
A117.1, | |
Accessible and Usable Buildings | |
and Facilities. The remainder of | |
units shall comply with the | |
requirements of the federal Fair | |
Housing Act. | |
Multifamily projects (e.g., | |
townhouses) consisting of | |
dwelling units having two levels | |
of living space with an elevation | |
difference of more than 24" and | |
which do not have an internal | |
elevator, must provide adaptability | |
throughout the first floor level. In | |
each project containing such | |
multi-level units, at least 10% of | |
the total number of units (rounded | |
to the next whole number) shall | |
be fully adaptable throughout all | |
levels. The 10% required to be | |
fully adaptable may be exempted | |
from providing access to the | |
upper level if the first floor | |
contains a full bath and bedroom | |
unit. Dormitories are included in | |
the definition of multi-family | |
projects and must comply with the | |
adaptability requirements. |
Facilities | Application |
One and two family dwelling: | Five percent of total, or at least |
State assisted, rental | one unit, whichever is greater, in |
projects of 15 or more dwelling | |
units. | |
State owned | Five percent of the total, or at |
least one unit whichever is | |
greater | |
State assisted home ownership is to be | |
determined by the buyer. |
Facilities | Application |
Metal desks | All areas for which the intended |
Electrical Coils | use will require public or |
Electrical motors | employee access |
Dry cell batteries | |
Metal parts | |
Empty cans | |
Stoves | |
Frozen foods | |
Meats | |
Fresh fruits and vegetables | |
Dairy products | |
Beer or wine up to 12% alcohol | |
Glass bottles with noncom. Liquids | |
Mirrors | |
Foods (in noncombustible containers) | |
Distribution transformers | |
Cement in bags | |
Electrical insulators | |
Gypsum board | |
Inert pigments | |
Dry insecticides | |
Washers and Dryers | |
Metal Cabinets |
Facilities | Application |
Fences over 6 ft. high | All areas for which the intended |
Tanks | use will require public or |
Cooling towers | employee access. |
Retaining walls | |
Buildilngs of less than 1,000 sq. feet | |
such as: | |
Private garages | |
Carports | |
Sheds |
Exceptions: Mechanical rooms, storage areas, and other such minor additions which normally are not frequented by the public or employees of the facility are excepted from this section.
Exceptions:
Exception: When spaces or elements are altered providing an opportunity for upgrading to the most recent Standards then compliance with those recent Standards is required.
Table 2
Allowable Ramp Dimensions for Construction in Existing Sites, Buildings, and Facilities
Maximum Rise | Maximum Run | ||||
Slope* | in | mm | ft | m | |
Steeper than 1:10 but no steeper than 1.8 | 3 | 75 | 2 | 0.6 | |
Steeper than 1:12 but no steeper than 1.10 | 6 | 150 | 5 | 1.5 |
*A slope steeper than 1.8 not allowed.
Exception: In alterations, accessible toilet stalls shall comply with 604.8.1 or 604.8.2. If provision of a 60 in wide stall is structurally impracticable or where plumbing code requirements prevent combining existing stalls to provide space, then provision of a 48 in wide alternate wheelchair accessible stall complying with Fig. 604.8.1.1 is permissible. (See Page 27)
604 Toilet Stalls. Amend 604.8.1 and 604.8.1.2 to read, "The size and arrangement of toilet stalls shall comply with Figure 1 (a) or (b), page 29, this document. (This figure supplants Fig. 604.8.3 in ICC/ANSI A117.1-2003).
Exception: Compliance with 604.8.1.1 and 604.8.1.2 is permitted if an accessible "unisex" toilet room is provided in the same area as the new single-sex toilet rooms.
706 Interpreter Illumination. It is recognized that hearing impaired persons require adequate and appropriate lighting in order to clearly see the interpreter or speaker. This section is reserved at present, however, pending research which will determine the best manner to accomplish this.
807 Areas of Rescue Assistance. Each area of rescue assistance shall be of the same fire-resistive construction as the required exit enclosure, and shall be contiguous and connected to each required exit. Each area of rescue assistance shall provide at least two accessible areas each being no less than 30 inches by 48 inches. The area of rescue assistance shall not encroach on any required exit width. The total number of such 30 inch by 48 inch areas per story shall be not less than one for every 200 persons of calculated occupant load served by the area of rescue assistance.
If an assembly area is served by areas of rescue assistance, the number of wheelchair spaces in the areas of rescue assistance shall at least equal the number of wheelchair seating spaces provided in the assembly area.
EXCEPTION: The Architectural Accessibility Board may reduce the minimum number of 30-inch by 48-inch areas to one for each area of rescue assistance on floors where the occupant load is less than 200.
Two-way Communication. If a new fire alarm system is to be installed in a building, a two-way communication system which is part of the fire alarm system, shall be provided between each area of rescue assistance and the primary entry. The two-way communication system shall have both visible and audible signals.
EXCEPTION: In all other cases, an engraved floor plan identifying areas of rescue assistance for fire fighters to search, and which is posted at the primary entry, shall be provided.
1005 Auxiliary Alarms in Dwelling Units. If a visual alarm is used to alert deaf persons to emergency situations, it shall be a white strobe light and shall be located on a wall within a direct line of sight of the bed and a bathroom door, whenever possible.
19 Del. Admin. Code § 4101-6.0