Current through Register Vol. 28, No. 7, January 1, 2025
Section 706-5-6.0 - Water Supplies6.1 A public or private water system shall be provided to supply a minimum of 1,000 gpm for a duration of three (3) hours for 10,000 units or less of tire storage.6.2 A public or private water system shall be provided to supply a minimum of 2,000 gpm for a duration of three (3) hours for more than 10,000 units of tire storage.6.3 Fire hydrants shall be located in accordance with the State Fire Marshal.6.4 If there is a reliable source of water, such as a lake, stream, pond, or other body of water, in the vicinity of the tire storage area, a dry hydrant shall be provided, even if a public or private water system is provided.1 Del. Admin. Code § 706-5-6.0