Current through Register Vol. 28, No. 7, January 1, 2025
Section 706-5-4.0 - Exposure Protection4.1 For 10,000 Units Or Less.4.1.1 Maximum pile height shall be 14 feet.4.1.2 Pile width and length shall not exceed 25 feet by 100 feet.4.1.3 Aisle width between piles shall be a minimum of 24 feet.4.1.4 The minimum distance between piles and buildings shall be 25 feet.4.2 For More Than 10,000 Units.4.2.1 Maximum pile height shall be 20 feet.4.2.2 Pile width and length shall not exceed 50 feet by 100 feet.4.2.3 Aisle width between piles shall be a minimum of 24 feet.4.2.4 The minimum distance between piles and important buildings shall be 200 feet.4.2.5 If the minimum distance required in § 4.2.4 cannot be provided, a Two Hour Rated Fire Wall (Class "B" Fire Barrier) shall be provided in accordance with Regulation 702, Chapter 2. This Two Hour Rated Wall shall be equal to or exceed the height of the pile(s).1 Del. Admin. Code § 706-5-4.0