Note: See Figure 5-8 - Fire Lane and Perimeter Access - Without Fire Suppression |
Note: See Figure 5-9 - Fire Lane and Perimeter Access with Fire Suppression |
Accessibility Table
Table 5-2
Percent of Fire Lanes | Percent of Perimeter Access | |||||
Number of Stories | 1-2 | 3-4 | > 4 | 1-2 | 3-4 | > 4 |
Height | up to 25' | >25 to 50' | > 50' | up to 25' | >25 to 50' | > 50' |
OCCUPANCY1 | ||||||
Assembly | 50 | 50 | 50 | N/A | N/A | 100 |
Educational2 | 50 | 75 | 75 | N/A | N/A | 100 |
Day Care Center | 25 | 50 | 75 | 50 | 75 | 100 |
Hospital | 50 | 75 | 75 | 100 | 100 | 100 |
Nursing Home | 25 | 50 | 75 | 75 | 75 | 100 |
Ambulatory Health Care | 25 | 25 | 50 | N/A | 50 | 75 |
Detention & Correction | TBDFM | TBDFM | TBDFM | TBDFM | TBDFM | TBDFM |
Residential | 25 | 35 | 75 | 50 | 75 | 100 |
Mercantile | 25 | 50 | 50 | 50 | 75 | 75 |
Business | 25 | 25 | 50 | N/A | 50 | 75 |
Industrial | 25 | TBDFM | TBDFM | 50 | TBDFM | TBDFM |
Storage | 25 | TBDFM | TBDFM | 50 | TBDFM | TBDFM |
TBDFM = To Be Determine in consultation with the Office of the State Fire Marshal.
1. For Mixed Use occupancies, accessibility shall be based on the floor with the individual occupancy requiring the greatest accessibility coverage.
2. Educational shall include educational buildings with mixed uses and shall not be considered as mixed use
Note: For the purposes of this Regulation and application of the Accessibility Table, the fire lane portion was based upon a 100 foot Aerial reach and the width of aerial stabilizers. The Perimeter Access portion was based upon standard fire ground operations. |
1 Del. Admin. Code § 705-5-4.0