1 Del. Admin. Code § 702-6-7.0

Current through Register Vol. 28, No. 5, November 1, 2024
Section 702-6-7.0 - Dry Hydrants
7.1 Where there is not a public water system or a central water system, the State Fire Marshal may require the installation of a dry hydrant at the nearest public body of water to provide access to a water source for fire protection for all buildings of less than 10,000 square feet of aggregate gross floor area.
7.2 The provision in subsection 7.1 of this Chapter for the providing of a dry hydrant shall also be meant that access to the dry hydrant and provisions for positioning fire apparatus to make use of the dry hydrant shall be provided.
7.3 The requirements of subsection 7.1 and subsection 7.2 of this Chapter shall meet the standards and specifications pursuant to the Construction Specifications for Dry Hydrant and Water Delivery Systems, Delaware 1991, prepared by the U. S. Department of Agriculture Soil Conversation Service and any updates thereto.
7.4 It is the responsibility of the developer, builder and/or owner to apply for and obtain any required permits for the installation of the dry hydrant.
7.5 It is the responsibility of the project developer, builder, and/or owner to provide the dry hydrants and any needed construction operations to place the dry hydrants in service.
7.6 All dry hydrants installed and accepted under this section shall be inspected, tested, and maintained in accordance with Regulation 703, Chapter 1, subsection 4.9.

Fire Flow Table 1*

The requirements of Fire Flow Table 1 apply to rural areas where public, private, or central water is not available and where specified elsewhere in these Regulations.

Occupancy

Maximum Aggregate Gross Square Footage

Provide a fire alarm system per Ch. 6, § 3.1.4

Minimum Set Back from all property lines

Maximum Height

Exposure Hazard on the Same Property

Internal Fire Separation

Apply

One & Two - Family Detached Dwellings

10,000

no

15'

3 Stories

35'

10'+

n/a

NFPA 1142

Multi-Family &

Other Residential

10,000

no

15'

3 Stories

35'

10'+

n/a

NFPA 1142

Rowhouses & Townhouses

10,000

no

15'

3 Stories

35'

10'+

2-Hr rated wall

Reg. 701

Chapter 2

NFPA 1142

Assembly

5,000

no

15'

1 Story

15'

10'+

n/a

NFPA 1142

Assembly1

5,001 to 10,000

YES

15'

2 Stories

30'

10'+

n/a

NFPA 1142

Health Care

Business

Education

10,000

no

no

no

15'

2 Stories

30'

10'+

n/a

NFPA 1142

Storage

Industrial

Mercantile

5,000

no

no

no

15'

To be reviewed on an individual basis

15'+

n/a

NFPA 1142

Storage1

Industrial1

Mercantile1

5,001 to 10,000

YES

YES

YES

25'

To be reviewed on an individual basis

15'+

n/a

NFPA 1142

Mini-Storage

5,000

no

15'

2 Stories

30'

15'+

n/a

NFPA 1142

Mini-Storage

5,001 to 10,000

no

25'

2 Stories

30'

15'+

n/a

NFPA 1142

1 A fire alarm signaling system shall be provided. See subsection 3.1.4.

*A-Fire Flow Table 1.

The requirements of Fire Flow Table 1 apply to rural areas where public, private or central water is not available. Where Exposure Hazard, Same Property (EHSP) or Minimum Set Back from all property lines (MSB) cannot be met, the following table may be utilized.

Maximum Aggregate Gross Square Footage

Fire Separation Distance (or Exposure Hazard, Same Property)

Exterior Wall Fire Resistance Rating

One- and Two-Family Detached Dwellings

10,000

Less than 10 feet

1-Hour

Multi-Family &

Other Residential

10,000

Less than 10 feet

2-Hour

Rowhouses & Townhouses

10,000

Less than 10 feet

2-Hour

Assembly

10,000

Less than 5 feet

2-Hour

5 to 10 feet

1-Hour

Health Care

Business

Education

10,000

Less than 5 feet

2-Hour

5 to 10 feet

1-Hour

Storage

Industrial

Mercantile

10,000

Less than 5 feet

2-Hour

5 to 15 feet

1-Hour

Mini Storage

10,000

Less than 5 feet

2-Hour

5 to 15 feet

1-Hour

Fire Flow Table 2

The requirements of Fire Flow Table 2 apply to areas where there is a public, private, or central water system.

Occupancy

Maximum Aggregate Gross Square Footage

Internal Fire Separation

Flow Required

Hydrant Spacing

One- and Two-Family Detached Dwellings 1

10,000

n/a

500 GPM

20 PSI Residual Pressure

1 Hour Duration

800 feet on center

Other Residential1

10,000

n/a

1,000 GPM

20 PSI Residual Pressure

1 Hour Duration

800 feet on center

Rowhouses1 & Townhouses1

10,000

2-Hr rated wall

1,000 GPM

20 PSI Residual Pressure

1 Hour Duration

800 feet on center

Reg. 701

Chapter 2

Assembly

Health Care

Business

Education

10,000

n/a

1,000 GPM

20 PSI Residual Pressure

1 Hour Duration

800 feet on center

Storage

Industrial

Mercantile

10,000

n/a

1,500 GPM

20 PSI Residual Pressure

2 Hour Duration

800 feet on center

Mini-Storage

10,000

n/a

750 GPM

20 PSI Residual Pressure

1 Hour Duration

800 feet on center

1 Sites in New Castle County are subject to the provisions of New Castle County Code Chapter 40 Article 5. See Note on § 1.4.1 and § 1.4.2.

Note: Fire Flow Table 2, Hydrant Spacing. The phrase, "on center" is intended to represent the maximum distance fire hydrants are spaced from each other. Proper application of this intention would generally provide a fire department with a maximum "hose lay" to a hydrant that would not exceed 500 feet for One & Two Family Dwellings, and 400 feet for all other structures.

Fire Flow Table 3 It is the intent of Fire Flow Table 3 to allow a credit for water flow that is available on site, but does not meet the full water flow requirements of Fire Flow Table 2. However, the available water flow on site shall be a minimum of 500 GPM, otherwise the requirements of Fire Flow Table 1 shall be applied to the site. This Table does not apply to new public, private, nor central water systems, including municipalities.

Occupancy

Maximum Aggregate Gross Square Footage

Minimum Set Back from all property lines

Exposure Hazard on the Same Property

Internal Fire Separation

One- and Two-Family Dwellings, Multi-family, and Other residential

10,000

*15'

*10'+

n/a

Rowhouses Townhouses

10,000

*15'

10'+

Two-Hour Rated Design Wall

Reg. 701,

Chapter 2

Assembly

10,000

*15'

*10'+

n/a

Health Care Business

Education

10,000

*15'

*10'+

n/a

Storage

Industrial

Mercantile

10,000

*25'

*15'+

n/a

Mini Storage

5,000

*15'

*15'+

n/a

Mini Storage

5,001 to

10,000

*25'

*15'+

n/a

Note: Fire Flow Table 3: For example, if 1,000 GPM is required for a 9,000 sq. ft. Business Occupancy business occupancy, but only 500 GPM is available, or 50%, then the required setbacks shall be reduced by 50% so that the Minimum Setback (MSB) from property lines would be 7.5 feet, instead of 15 feet, and the Exposure Hazard on the Same Property (EHSP) would be five feet, instead of ten feet.

1 Del. Admin. Code § 702-6-7.0

25 DE Reg. 74 (7/1/2021) (final)