Note: Timeframes relate to the ropeway installation date or modification date whichever controls, unless otherwise noted. For electrical drive or control system modifications performed on fixed grip aerial lifts installed prior to April 15, 2019, the requirements of ANSI B77.1-2011 shall be met (Refer to Annex R.4).
IN ADDITION TO ANSI 4.1.1.3 Location
Jan, 1, 1977 to Present:
Power lines shall be located a minimum distance equal to the height of poles or support structures from any passenger tramway so that poles and electrical lines cannot touch any portion of the tramway, loading or unloading points or platforms and tow path, if applicable, upon collapse of poles or lines, unless suitable and approved precautions are taken to safeguard human lives.
Note: Timeframes stated for this Rule define the air space requirements for each ropeway at the time when the encroachment was known to the area and DO NOT pertain to the installation date of the ropeway.
May 15, 2000 to Present:
No passenger tramway installation shall be permitted to operate when a structure encroaches into the air space of the passenger tramway, defined as the area bounded by vertical planes commencing at a point thirty-five feet from the intersection of the vertical planes of the ropes or cables and ground surface.
For purposes of this Rule, buildings controlled by the licensee used primarily for maintenance and operation of the lift and other tramways shall not be considered structures; however, buildings must comply with the following.
Jan. 1, 1994 to May 15, 2000:
No passenger tramway installation shall be permitted to operate when a structure encroaches into the air space of the passenger tramway, defined as the area bounded by planes having an outward slope of one horizontal and two vertical and commencing at a point twenty (20) feet horizontally outside of the intersection of the vertical planes of ropes or cables and ground surface.
Dec. 30, 1977 to Jan. 1, 1994:
No passenger tramway installation shall be permitted whenever the Passenger Tramway Operator does not have permanent and irrevocable control of the following air space (except when the passenger tramway is located on Forest Service land): the area bounded by planes having an outward slope of one horizontal and two vertical and commencing at a point twenty feet horizontally outside of the intersection of the vertical planes of ropes or cables and ground surface.
Prior to Dec. 30, 1977:
Not required
Note: Timeframes stated for this Rule define the air space requirements for each ropeway at the time when the encroachment was known to the area and DO NOT pertain to the installation date of the ropeway.
May 15, 2000 to Present:
Any cable or rope installed on or near a ropeway that may represent a hazard to the ropeway shall be monitored to automatically stop the ropeway if the cable or rope fails. Failure would be defined as per Section 23.1 (g).
EXCEPTION: Track or haul ropes are excluded from this Rule.
Prior to May 15, 2000:
Not required
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Jan, 1, 1984 to Nov. 1, 1991:
Terminals and towers shall be designed and installed to provide the clearances as herein specified and to minimize surge of the line under operating conditions. Local wind conditions shall be taken into consideration.
The minimum distance between passing carriers, each swung 10 degrees inward from the vertical, shall be the greater of the following:
The distance between haul ropes, (or track cables), for the purpose of these checks, shall be considered as equal to the gauge of the line.
External structures, posts, or obstructions, other than lift structural components, shall have at least 4 feet (1.22 meters) of clearance from either edge of a loaded open carrier passenger seat or open cabin body (measured from the outermost attachments on or parts of the carrier while the carrier is hanging in a vertical position).
Dec. 31, 1977 to Jan. 1, 1984:
Terminals and towers shall be designed and installed to provide the clearances as herein specified and to minimize surge of the line under operating conditions. Local wind conditions shall be taken into consideration.
The minimum distance between passing carriers, each swung 10 degrees inward from the vertical, shall be the greater of the following:
The distance between haul ropes, (or track cables), for the purpose of these checks, shall be considered as equal to the gauge of the line.
Prior to Dec. 31, 1977:
All towers shall be equipped with guards to prevent contact of carriers or hangers with a tower structure or tower machinery except that such guards shall not be required if such contact does not occur when the carrier is swung freely 15 degrees from the vertical position.
In the absence of guards described herein, the following minimum clearances shall prevail when the carrier is swung inward 10 degrees from the vertical position:
Guards shall be so shaped and located that a 30- degree lateral swing from vertical shall not place and part of the loaded or empty carrier on the inner side of the guard.
On all towers, with or without guards, when a carrier is swung longitudinally by 15 degrees, there shall be no contact between any obstruction and any part of the carrier.
Prior to Nov. 1, 1991:
Not required.
ADDITIONAL PARAGRAPH ADDED:
Any changes to software logic that would affect a Safety Related Control Function, Control Function, Protection Circuit (R.4.2.3) or Operation Circuit (R.4.2.4) after the start of initial testing shall result in a restart of testing to ensure software logic changes have not affected those systems already tested. Retesting for changes in software parameters shall be at the discretion of the Authorities Having Jurisdiction (AHJ).
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Prior to April 15, 2019:
An evacuation power unit (see 1.4 - evacuation power unit) with an independent power source shall be provided that can readily be used to unload the lift in the event of failure of the prime mover. The evacuation power unit shall not depend upon the mechanical integrity of any other power unit to drive the aerial lift. This unit shall be electrically wired to meet the requirements of R.4.2.3.1 so that it can be stopped by the Emergency Shutdown Circuit. As a minimum, the evacuation power unit shall be capable of starting and moving a line with all carriers loaded to 110% of capacity in weight in a forward direction at not less than 100 feet per minute (0.51 meters per second).
The evacuation power unit shall be designed to become operational and move all the carriers to or through terminal areas within 1 hour from the time of initiating its connection.
Prior to May 15, 2006:
Not required.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
May 15, 2006 to April 15, 2019:
The aerial lift shall have the following friction-type brakes and other devices as specified in table 4-3:
- service brake (see 4.1.2.6.1);
- drive sheave brake (see 4.1.2.6.2);
- rollback device (see 4.1.2.6.3);
- drive train backstop (see 4.1.2.6.4).
All braking systems shall be designed to ensure that:
EXCEPTION- For an aerial lift that overhauls only in the reverse direction, a drive train backstop may be used in lieu of the above.
The service brake, drive sheave brake, rollback device, and drive train backstop device shall be designed such that failure of one system will not impair the function of the other systems. All brakes shall have the braking force applied by springs, weights, or other approved forms of stored energy.
The service brake, drive sheave brake, rollback, and drive train backstop devices shall be designed to assure operation under all anticipated conditions.
Each braking system shall be capable of operation to comply with daily inspections and periodic testing.
The manufacturer or a Qualified Engineer shall furnish a written procedure to be followed, and specify the auxiliary equipment necessary for periodic testing and adjustment of the holding force of each brake and backstop device. The procedure shall additionally specify:
This baseline procedure shall be performed at the completion of the acceptance test and then at the frequency specified in order to demonstrate the ability of each brake to produce the required force.
Testing shall be accomplished as part of normal maintenance during the operating season, but shall not be performed when the aerial lift is open to the public. As a minimum, this testing shall be performed monthly during the operating season.
If a device is permanently installed to cause a brake, rollback, or drive train backstop device to be disabled for testing, it shall be electronically monitored so that the aerial lift cannot be operated in its normal mode when the brakes are so disabled.
Prior to May 15, 2006:
The aerial lift shall have the following friction-type brakes and other devices as specified in table 4-3:
- service brake (see 4.1.2.6.1);
- drive sheave brake (see 4.1.2.6.2);
- rollback device (see 4.1.2.6.3);
- drive train backstop (see 4.1.2.6.4).
All braking systems shall be designed to ensure that:
EXCEPTION- For an aerial lift that overhauls only in the reverse direction, a drive train backstop may be used in lieu of the above.
The service brake, drive sheave brake, rollback device, and drive train backstop device shall be designed such that failure of one system will not impair the function of the other systems, and all brakes shall have the braking force applied by springs, weights, or other approved forms of stored energy.
The service brake, drive sheave brake, rollback, and drive train backstop devices shall be designed to assure operation under all anticipated conditions.
Stopping distances specified in 4.1.2.5.1 shall be achieved by each brake without the aid of other braking devices or drive regeneration.
Each braking system shall be capable of operation to comply with daily inspections and periodic testing.
A Qualified Engineer shall furnish a written procedure to be followed, and specify the auxiliary equipment necessary for periodic testing and adjustment of the holding force of each brake and backstop device. This procedure shall be performed during the acceptance test, and at the frequency specified, to demonstrate the ability of each brake to produce the required torque.
Such testing shall be accomplished as part of normal maintenance during the operating season, but shall be performed when the aerial lift is not open to the public.
If a device is permanently installed to cause a brake, rollback, or drive train backstop device to be disabled for testing, it shall be electronically monitored so that the aerial lift cannot be operated in its normal mode when the brakes are so disabled.
Table 4-3 - Required stopping devices
Lift category | Service Brake | Drive Sheave Brake | Rollback device | Drive train backstop | Retarding device (see 4.1.2.4) |
Self-braking: A lift that decelerates, stops, & remains stopped within the service brake performance requirements without a braking device | Not Required | Required | Not Required | Not Required | Not Required |
Nonoverhauling : A lift that will not accelerate in either direction when it is not driven, but is not self-braking | Required* | Required | Not Required | Not Required | Not Required |
Overhauling, reverse direction: A lift that will accelerate in the reverse direction when it is not driven | Required | Required | Required | Required | Not Required |
Overhauling, forward direction: A lift that will accelerate in forward direction when it is not driven | Required | Required | Not Required | Not Required | Required |
* A service brake is not required if the overhauling reverse direction lift will meet the service brake stopping requirements under most unfavorable design loading conditions. |
Prior to May 2, 2011
The drive sheave brake shall operate on the drive sheave assembly.
The drive sheave brake shall be capable of being activated both manually and automatically to stop and hold the aerial lift under the most unfavorable design loading condition. Deceleration rates or stopping distances specified in 4.1.2.5 shall be achieved by the drive sheave brake without the aid of other braking devices or drive regeneration.
Application of the drive sheave brake shall automatically disconnect the power source to the power unit in use. This brake shall act automatically when the speed of the haul rope exceeds the design value by 15% in either direction of an overhauling lift.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Prior to Jan 1, 1994:
Not required.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Prior to May 15, 2006:
Haul rope terminal sheave frames shall be designed to retain the rope in the event of the failure of the sheave, shaft, or mounting. In instances where the sheave is cantilevered, the design working stresses shall not be more than 60% of those otherwise allowable.
The minimum diameter of terminal sheaves shall be 72 times the nominal diameter of the haul rope. The sheave assembly shall be designed to retain the haul rope in the event of a deropement from the sheave. A flange extension of 1-1/2 times the rope diameter (measured from the bottom of the rope groove) shall be deemed adequate for retention.
Haul rope terminal sheaves that act as driving, braking, or holding sheaves shall be so designed that the haul rope does not slip in the sheave groove. The design coefficient of friction for a particular sheave liner shall not exceed the following values:
Sheave Liner | Coefficient of Friction |
Steel or cast iron grooves | 0.070 |
Leather | 0.150 |
Rubber, neoprene, or other | 0.205 |
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Prior to May 15, 2006:
Counterweights, hydraulic and pneumatic cylinders, or other suitable devices shall be used to provide the tensioning requirements of the particular installation. All devices used to provide the tension shall have sufficient travel to adjust to all normal operating changes in loading and temperature.
The tension for haul ropes for all modes of operation shall be determined by the design engineer. Tension systems may be automatic or manual; however, all systems shall have monitoring equipment that will automatically prevent operation outside of design limits (see R.4.2.3.3)
Tension systems may be adjustable to provide proper tensions for different modes of aerial lift operation.
The tension system design shall consider changes, for each mode of operation, in tensions due to rope elongation, friction and other forces affecting traction on driving, braking, or holding sheaves, tower and sheave loading, and maximum vertical loads on grips to assure that tensions remain within design limits.
Prior to April 17, 2006
Roller, leaf, or welded link chains may be used in tension systems (see informative Annex H).
For chain used as a tensioning component, where the chain does not pass through or around sprockets, the minimum factor of safety shall be 5 (see H.1.2). For applications of chain where any sprockets are used, the minimum factor of safety shall be 6.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Nov. 1, 1991 to April 15, 2019:
The design of the tower structure and foundation shall be in accordance with the requirements of 4.1.1.6. Where guyed towers are used and guys intersect the ground within or near ski runs, the guys shall be marked for visibility.
Means shall be provided for ready access from the ground to all tower tops. Permanent ladders are required for heights above those accessible by portable ladders. Portable ladders, if used, shall be in at least sufficient quantity to be available at each point where attendants are positioned. Portable ladders extending more than 20 feet (6.10 meters) shall not be used.
Permanent anchor points shall be provided on all tower tops for the attachment of fall protection devices.
Towers shall be identified with successive numbers clearly visible to passengers.
Where towers are designed to permit variations in rope height, sheave unit supports shall be guided and attached so as to prevent misalignment by rotation during normal operation.
Prior to Nov. 1, 1991:
The design of the tower structure and foundation shall be in accordance with the requirements of 4.1.1.6. Where guyed towers are used and guys intersect the ground within or near ski runs, the guys shall be marked for visibility.
Means shall be provided for ready access from the ground to all tower tops. Permanent ladders are required for heights above those accessible by portable ladders.
Portable ladders, if used, shall be in at least sufficient quantity to be available at each point where attendants are positioned. Portable ladders extending more than 20 feet (6.10 meters) shall not be used.
Towers shall be identified with successive numbers clearly visible to passengers.
Where towers are designed to permit variations in rope height, sheave unit supports shall be guided and attached so as to prevent misalignment by rotation
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Prior to May 15, 1994:
Sheave flanges shall be as deep as possible, considering other features of the system. At the same time, rope grips shall be designed in relation to the sheave groove so as not to contact sheave flanges during normal operations, taking into consideration the anticipated amount of wear of the sheave liner groove. Grips shall be allowed to contact sheave flanges adjacent to the haul rope when the carrier swings, provided that this is considered in the design of the grips and sheaves. Furthermore, rope grips, sheave flanges, and hanger guides shall be designed so that hangers cannot be caught behind guides, and so that haul ropes and grips cannot be deroped from sheaves if the carrier is swinging within design limits as it approaches or passes the tower.
Suitable guards, of sufficient strength to resist the lateral forces caused by an inside deropement, shall be installed.
Construction of the entire sheave unit shall be such that the haul rope cannot become entangled in the sheave unit in the event the rope leaves the sheave toward the outside.
On each sheave unit, rope-catching devices shall be installed to reduce the risk of the rope moving excessively in the direction of the load on the sheave unit in the event of deropement. These devices shall be located less than one-half the diameter of the sheaves from the normal operating position of the rope and shall extend a minimum of two rope diameters beyond the sheave flange. Alternatively, when the catcher is located so that the rope cannot move in the direction of the load when it passes from the edge of the sheave to a position in the catcher, the catcher shall extend a minimum of two rope diameters beyond the center of the rope when the rope has reached the point where the deropement switch device initiates a stop. Rope-catching devices shall be designed to permit the passage of the haul rope and grips after deropement. The catcher shall be independent from the sheave.
On each sheave unit, suitable deropement switch devices shall be installed and maintained that will stop the lift in case of deropement.
On lifts where the carrier speed exceeds 600 feet per minute (3.0 meters per second), at least one device that senses the position of the rope shall be installed on each sheave unit. The device shall initiate a stop before the rope leaves the sheave in the horizontal direction or when the rope is displaced in the vertical direction by one rope diameter plus the distance that the rope is displaced vertically from the sheave by the grip.
If the gage of the haul rope system is varied at any point along the line, the horizontal departure at any one tower shall be provided for in the design so that deropement cannot occur by virtue of such a departure.
Sheave mounts or mounting frames shall be designed to be adjustable, allowing the sheave units to be aligned and held in the plane of the rope.
See also 4.1.1.5 through 4.1.1.5.3 for the effect of tower height and location on sheave units.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
May 15, 1999 to April 15, 2019:
Each chair shall be equipped with a railing at each side, to a height of not less than 4 inches (100 mm) above the seat for a distance of not less than 12 inches (305 mm) from the back of the seat.
For aerial lifts operating primarily for skiers, the thickness of the chair seat front, including padding, shall not exceed 5 inches (125 mm) from the top of the seating surface to the bottom of the curl. Tilt back angle of the seat bottom should be a minimum of 7 degrees when loaded. Loaded shall mean an evenly distributed load using load test criteria. Provisions shall be made to keep the tails of skis from passing through and becoming trapped in open spaces between framework, safety restraints and chair seat underside.
For aerial lifts operating primarily for foot passengers, each chair shall be equipped with a restraining device that will not open under forward pressure.
Prior to May 15, 1999:
Each chair shall be equipped with a railing at each side, to a height of not less than 4 inches (10 cm) above the seat for a distance of not less than 12 inches (30 cm) from the back of the seat.
For aerial lifts operating primarily for foot passengers, each chair shall be equipped with a restraining device that will not open under forward pressure.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
April 15, 2019 to July 15, 2023:
All electrical systems shall comply with American National Standard, ANSI/NFPA 70-2017, National Electrical Code and the Institute and Electronics Engineers, IEEE C2-2017, National Electrical Safety Code.
May 2, 2011 to April 15, 2019:
All electrical systems shall comply with American National Standard, ANSI/NFPA 70-2011, National Electrical Code and the Institute of Electrical and Electronics Engineers, IEEE C2-2007, National Electrical Safety Code.
May 15, 2006 to May 2, 2011:
All electrical systems shall comply with American National Standard, ANSI/NFPA 70-2005, National Electrical Code and the Institute of Electrical and Electronics Engineers, IEEE C2-2007, National Electrical Safety Code.
May 15, 2000 to May 15, 2006:
All electrical systems shall comply with 4.2.1.1 Applicable codes of the B77.1-1999 ANSI Standard.
Jan. 1, 1994 to May 15, 2000:
All electrical systems shall comply with 4.2.1.1 Applicable codes of the B77.1-1992 ANSI Standard.
Nov. 1, 1991 to Jan 1, 1994:
All electrical systems shall comply with 4.2.1.1 Applicable codes of the B77.1-1990 ANSI Standard.
Jan. 1, 1984 to Nov 1, 1991:
All electrical systems shall comply with 4.2.1.1 Applicable codes of the B77.1-1982 ANSI Standard.
Jan 1, 1977 to Jan. 1, 1984:
All electrical work shall comply with 4.2.1.1 Applicable codes of the B77.1-1976 ANSI Standard.
Jan 1, 1974 to Jan. 1, 1977:
All electrical work shall comply with 4.2.1.1 Applicable codes of the B77.1-1973 ANSI Standard.
Jan 1, 1972 to Jan 1, 1974:
All electrical work shall comply with 4.2.1.1 Applicable codes of the B77.1-1970 ANSI Standard.
Prior to Jan 1, 1972:
All electrical work shall comply with 4.2.1.1 Applicable codes of the B77.1-1960 ANSI Standard.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
April 15, 2019 to July 15, 2023:
All electrical power transmission wiring located near or proposed to cross over aerial lifts shall comply with 4.2.1.2 Location of the B77.1-2017 ANSI Standard.
May 15, 2006 to April 15, 2019:
All electrical power transmission wiring located near or proposed to cross over conveyors shall comply with the applicable requirements of IEEE C2-2007.
May 15, 2000 to May 15, 2006:
All electrical power transmission wiring located near or proposed to cross over aerial lifts shall comply with 4.2.1.2 Location of the B77.1-1999 ANSI Standard.
Jan. 1, 1994 to May 15, 2000:
All electrical power transmission wiring located near or proposed to cross over aerial lifts shall comply with 4.2.1.2 Location of the B77.1-1992 ANSI Standard.
Nov. 1, 1991 to Jan 1, 1994:
All electrical power transmission wiring located near or proposed to cross over aerial lifts shall comply with 4.2.1.2 Location of the B77.1-1990 ANSI Standard.
Jan. 1, 1984 to Nov 1, 1991:
All electrical power transmission wiring located near or proposed to cross over aerial lifts shall comply with 4.2.1.2 Location of the B77.1-1982 ANSI Standard.
Prior to Jan. 1, 1984:
All exposed electrical power transmission wiring shall be so located that in case of collapse or breakage of the power line it will not come into contact with carriers, ropes, or passengers.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Prior to May 15, 2006:
Signal, communication, and control circuits may be supported between towers that support the aerial lift. Voltage on overhead or exposed circuits shall be limited to 50 volts with the exception of the intermittent ring-down circuits for telephone systems.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Prior to May 15, 2006:
Not required.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Prior to Jan 1, 1984:
Not required.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Prior to April 15, 2019:
Refer to R.4.2.2.
Prior to April 15, 2019:
Refer to R.4.2.2.1
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Prior to April 15, 2019:
Refer to R.4.2.3
Prior to April 15, 2019:
Refer to R.4.2.3.1
Prior to April 15, 2019:
Refer to R.4.2.3.2.
Prior to April 15, 2019:
Refer to R.4.2.3.3.
Prior to April 15, 2019:
Refer to R.4.2.3.4.1
Prior to April 15, 2019:
Refer to R.4.2.3.4.2
Prior to April 15, 2019:
Refer to R.4.2.3.6.
Prior to April 15, 2019:
Refer to R.4.2.3.7
Prior to April 15, 2019, This Specific ANSI-B771-2017 Rule Number Not Required
Prior to April 15, 2019:
Refer to R.4.2.5
Prior to April 15, 2019:
This specific rule number not required - See 4.1.4.4.2.
Prior to April 15, 2019:
Refer to R.4.2.3, R.4.2.4, or R.4.2.5 as applicable.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Prior to May 15, 2006:
All automatic and manual stop and shutdown devices shall be of the manually reset type. An exception to this requirement is allowed for magnetic or optically operated automatic stop devices, if the operating circuit is such that it indicates that such devices initiated the stop and the circuit is of the manually reset type. Manual stop switches (push button) shall be positively opened mechanically and their opening shall not be dependent upon springs.
Manual control devices shall be installed in all attendants' and operators' work positions, in machine rooms, and out-of-doors in proximity to all loading and unloading areas. As a minimum at downhill loading stations, each of these control locations shall include an Emergency Shutdown device or a Normal Stop device. All manual control devices located in or on a control cabinet shall be mounted so that they are in the same plane or face of the cabinet. The control devices shall not be located in a position that would require the operator or attendant to pass through the path of moving carriers in order to operate the controls.
The devices shall be conspicuously and permanently marked with the proper function and color code.
REPLACES ANSI FOR SPECIFIC TIMEFRAMES
Prior to May 15, 1999:
The sign "Personnel Working on Lift - Do Not Start" or a similar warning sign shall be hung on the main disconnect switch or at control points for starting the power unit(s) when persons are working on the aerial lift.
Provision shall be incorporated in the ropeway design to render the system inoperable when necessary for the Lock-out Tag-out protection of personnel working on the aerial lift.
IN ADDITION TO ANSI 4.3.1.2 SIGNS
IN ADDITION TO ANSI 4.3.1
Each licensee shall have an operational plan that has procedures for transportation of sports equipment and recreational devices by foot passengers. This plan shall be consistent with the tramway manufacturer's specifications and instructions, if any.
IN ADDITION TO ANSI 4.3.2.5
Each licensee shall have an operational plan that identifies criteria for pre-operational tramway inspections for the transportation of personnel on aerial ropeways. Implementation of these procedures is intended for the protection of all personnel and shall be the responsibility of the area operator, supervisor, and the authorized individual.
The preoperational plan shall include, but not be limited to:
Minimum Requirements
Prior to the daily preoperational ride and the completion of X.3.2.4.2 Daily preoperational inspection, or any initial start-up of the ropeway, the following minimum steps shall be taken;
The plan shall also include the following requirements:
For the purpose of this Rule, "area employee" means an individual:
An area employee that is directly related to the opening of the aerial lift (i.e. Ski Patrol, Lift Maintenance, and Lift Operators) shall conduct the pre-operational inspection ride. If any other area employee is to ride the lift prior to the completion of the pre-operational inspection, the personnel responsible for the pre-operational inspection ride shall ride in the first carriers in front of the area employee. As used in this Rule, the term "area employee" specifically excludes independent contractors, subcontractors, vendors, and their personnel.
Only personnel related to the completion of the construction, operation, and buildings directly related to the operation of the tramway may be transported by the tramway prior to testing and licensing.
IN ADDITION TO ANSI 4.3.5
A software parameters log shall be maintained for each aerial lift. This log is intended for changes in software parameters that can be altered which affect the supervision circuit. The log shall include, but not be limited to:
3 CCR 718-1-4