8 Colo. Code Regs. § 1302-14-2

Current through Register Vol. 47, No. 20, October 25, 2024
Rule 8 CCR 1302-14-2 - Codes and Standards

Pursuant to sections 24-32-3303(1), 24-32-3304(1)(a) and (b), and section 24-32-3305(2), C.R.S., the State Housing Board hereby adopts and incorporates by reference the following nationally recognized codes, standards, guidelines, procedures, or rules in their entirety, except for the revisions, additions, deletions, or exceptions/exemptions specified below. The incorporated codes, standards, guidelines, procedures, or rules do not include later revisions. They are readily available for public inspection in written format during the regular business hours at the Division of Housing, Building Codes and Standards Section, 1313 Sherman Street, Suite 320, Denver, CO 80203. Paper copies are available for a reasonable fee paid to the Division of Housing. Electronic copies are available from the agencies originally issuing them as noted below.

Building Codes for Factory-Built Residential Structures and Tiny Homes; Factory-Built Nonresidential Structures; and Site-Built Hotels, Motels, and Multi-Family Structures in those areas of the State where no Standards Exist

Manufacturers are permitted to use the construction codes in effect prior to the adoption of any new code for a maximum of 180 days after the amendment in rule takes effect. The Program Manager for the Building Codes & Standards Section, the Director of the Office of Regulatory Oversight, the Deputy Division Director, or the Division Director is authorized to grant, in writing, one extension, for a period not more than 180 days.

2.1The International Building Code (IBC), 2018 Edition, published by the International Code Council, Inc. (ICC). This is a safety code and is available through the ICC at:https://www.iccsafe.org.
2.1.1Section 105.2 Work exempt from permit

Add the following exceptions prior to "Building:"

2.1.1.1Equipment Enclosures:

One story detached buildings designed to protect equipment from heat, weather elements, or damage that:

- Do not exceed 500 sq. ft.,

- Are not connected to a permanent source of power,

- Are not classified as an electrical hazardous area per Article 500 of the NEC (is a nonhazardous area), and

- Are not installed on a permanent foundation.

A building that in its entirety operates as a listed product is automatically exempt as long as the manufacturer is able to demonstrate it is labeled as such.

2.1.1.2Building Components:

A building component, assembly, or system constructed in the factory as open construction (see definitions).

The above exemptions from approval through the State factory-built program do not grant any exemption from local jurisdiction requirements or state electrical or plumbing requirements. The above exemptions do not grant authorization for any work to be done in a manner that is in violation of the provisions of the adopted codes.

2.1.2Section 901.2 Fire Protection systems

Add the following new section:

2.1.2.1Section 901.2.1 Certified inspector required

An automatic fire sprinkler system shall be installed in buildings as required by the local jurisdiction where the structure will be set. Final tests required by this Section shall be approved by a certified inspector as required by a local jurisdiction. The inspector must be either an employee of the fire department having jurisdiction or another qualified individual with prior approval of the Colorado Division of Fire Prevention & Control.

2.1.3Section 907.2.10.2 (1) Smoke Alarms - Location

Revise "immediate vicinity" to read "within 15 feet".

2.1.4Section 907.2.10.6 Smoke Alarms - Power Source

Add to the end of the paragraph the following:

Smoke and/or carbon monoxide alarms shall not be installed on a circuit dedicated only for smoke and/or carbon monoxide alarms.

2.1.5Section 915.2.1 Carbon monoxide alarms - Locations

Revise "immediate vicinity" to read "within 15 feet".

2.1.6Section 915.4.1 Carbon monoxide alarms - Power Source

Add to the end of the paragraph the following:

Smoke and/or carbon monoxide alarms shall not be installed on a circuit dedicated only for smoke and/or carbon monoxide alarms.

2.1.7Section 1015.8 Window openings

Replace the words "top of the sill" with "bottom of the clear opening".

2.1.8Chapter 13

Delete in its entirety.

2.1.9Section 1507.1.1 Ice barriers

Add the following sentence at the beginning:

Due to a history of ice forming along the eaves in Colorado, an ice barrier is required.

And add the following language at the end of the first sentence:

...or not fewer than two layers of underlayment cemented together and to the roof.

2.1.10Section 1608.2 Ground snow loads

Revise to read as follows:

Roof Snow Load (Pf) shall be in accordance with the local jurisdiction requirements and shall not be less than a minimum roof snow load of 30 PSF. The allowable increase of snow duration shall not be used when the snow load is above 65 PSF.

2.1.11Section 1609.3.1 Wind speed conversion

Add this new section with the following language:

The 3 second gust basic wind speed shall be in accordance with the local jurisdiction requirements. For jurisdictions that have adopted a building code edition prior to the 2012, the basic wind speed of that jurisdiction shall be multiplied by 1.20 for Risk category I structures, 1.29 for Risk category II structures, and 1.38 for Risk category III and IV structures to obtain Vult. The design wind speed Vult shall not be less than the minimum basic wind speeds as follows (Risk category as determined by Table 1604.5):

Risk category I structures - 105 MPH

Risk category II structures - 115 MPH

Risk category III and IV structures - 120 MPH

The Exposure category shall be C, unless otherwise justified.

2.1.12Section 2111.1 and 2111.14.1 Fireplaces

Add this new section with the following language:

Every new fireplace must comply with one of the following:

1. Listed and labeled fireplace and chimney systems composed of factory-made components, and assembled in the field in accordance with the manufacturer's instructions and the conditions of the listing, and
2. Approved gas logs.
2.2The International Residential Code (IRC), 2018 Edition, published by the International Code Council, Inc. (ICC). This is a safety code and is available through the ICC at:https://www.iccsafe.org.
2.2.1Table R301.2 (1) -

Revise as follows:

Climatic or Geographic Design Criteria for IRC Dwellings

(Risk Category II Structures)

Division of Housing Minimum

Roof Snow load(1)

30 psf, non-reducible

Basic Wind Speed(1)

115 mph (Vult), Exposure C

Wind Topographic Effects

Per Local

Seismic Design Category(1)

Minimum B

Weathering

Severe

Frost Line Depth(4)

Per Local

Termite Damage

Slight

Winter Design Temperature(2)

Per Local

Ice Barrier Underlayment Requirement

Yes

Flood Hazards

Per Local

Air Freezing Index(3)

Per Local

Mean Annual Temperature(3)

Per Local

Wildfire Risk

Per Local

(1)The roof snow load, wind design, and seismic zone shall be in accordance with the local jurisdiction requirements and shall not be less than the minimums stated. The allowable increase for snow duration shall not be used when the snow load is above 65 PSF.
(2)See Appendix B and verify with local jurisdiction.
(3)See the National Climatic Data Center data table "Air Freezing Index-USA Method (Base 32° Fahrenheit)" at www.ncdc.noaa.gov.
(4) In areas of the state without a local jurisdiction, the Division of Housing will approve all temporary or permanent foundation systems as defined in Rule 2.
2.2.2Table R301.5 - Live Loads

Add footnote (j) to Decks, Porches, Exterior balconies, Fire escapes to read as follows:

(j) When the snow load is above 65 psf, the minimum uniformly distributed live loads for exterior balconies, decks and fire escapes shall be as required for roof snow loads.
2.2.3Table R302.1 (1) - Exterior Walls

Delete footnote (b).

2.2.4Table R302.1 (2) - Exterior Walls-Dwellings with Fire Sprinklers

Delete footnote (c).

2.2.5Section R308.4.6 Glazing adjacent to stairs and ramps

Revise to include the following sentence as an exception:

1. Where the glazing is protected by a guard complying with Section R312 and the plane of the glass is more than 18 inches (457 mm) from the guard.
2.2.6Section R308.4.7 Glazing adjacent to the bottom of the stair landing

Revise to increase to less than 60 inches (1524 mm) above the landing.

2.2.7Section R310.1 Emergency escape and rescue opening required

Add a second sentence that reads as follows:

Cape Code style attics that qualify as a story shall require one operable emergency and escape opening.

2.2.8Section R310.2.2 Window sill height

Replace the word "sill" with the word "opening" in the section title and replace the word "sill" with "window opening".

2.2.9Section 311.7.12 Ships ladders

Add the following sentence to the end of the Exception:

The device must remain fixed in position when used in these areas.

2.2.10Section R312.2.1 Window sill heights

Replace the word "sill" with the word "opening" in the section title and delete the words "the sill of".

2.2.11Section R313 Automatic Fire Sprinkler Systems

Delete this section and replace it with the following:

An automatic fire sprinkler system shall be installed in one and two family dwellings and townhouses as required by the local jurisdiction where the home will be set. In-plant and final tests required by this Section shall be approved by a certified inspector. The inspector shall be an employee of the fire department having jurisdiction or another qualified individual with prior approval of the Colorado Division of Fire Prevention & Control.

2.2.12Section 314.3 (2) Smoke Alarms - Location

Revise "immediate vicinity" to read "within 15 feet".

2.2.13 Section 314.4 Revise "Physical interconnection of smoke alarms shall not be required where listed wireless alarms are installed and..." to "Physical interconnection of smoke alarms shall not be required where listed wireless alarms are installed in existing construction when approved by the Division of Housing and..."
2.2.14Section 314.6 Smoke Alarms - Power Source

Add to the end of the paragraph the following:

Smoke and/or carbon monoxide alarms shall not be installed on a circuit dedicated only for smoke and/or carbon monoxide alarms.

2.2.15Section 315.3 Carbon monoxide alarms - Locations

Revise "immediate vicinity" to read "within 15 feet".

2.2.16Section 315.6 Carbon monoxide alarms - Power Source

Add to the end of the paragraph the following:

Smoke and/or carbon monoxide alarms shall not be installed on a circuit dedicated only for smoke and/or carbon monoxide alarms.

2.2.17Section R802.10 Wood trusses

Add the following new section:

Section R802.10.5 Marking

Each truss shall be legibly branded, marked, or shall have other permanent labeling of the truss drawing's designated identification number on the large face of the top chord and within two (2) feet of the peak of the truss.

2.2.18Section R905.1.2 Ice barriers

Revise to read as follows:

Due to a history of ice forming along eaves in Colorado, an ice barrier is required. The ice barrier shall consist of a self-adhering polymer-modified bitumen sheet and shall extend from the eave's edge to a point at least 24" inside the exterior wall line of the building or of not fewer than two layers of underlayment cemented together and to the roof.

2.2.19Section R1004.4, G2406.2 exceptions 3 and 4, G2425.8 #7, G2445

Delete all and replace with the following:

Unvented fuel fired room heaters and unvented fuel fired fireplaces are prohibited.

2.2.20 Add the following new sections:

Section R1001.1 and R1004.1 - Fireplaces

Every new fireplace must comply with one of the following:

1. Listed and labeled fireplace and chimney systems composed of factory-made components, and assembled in the field in accordance with manufacturer's instructions and the conditions of the listing, and
2. Approved gas logs.
2.2.21Section P2503.5.1 Rough plumbing

Delete the words "other than plastic" in the sentence for water and air testing.

2.2.22Chapter 11 ENERGY EFFICIENCY

Delete in its entirety.

2.2.23Section M2001.1 Installation and G2452.2 Installation

Add the following sentence:

All rooms or spaces containing boilers shall be provided with a floor drain and trap primer.

2.2.24Section G2417.4.1 Test pressure

Revise to read as follows:

The test pressure to be used shall not be less than 1 1/2 times the proposed maximum working pressure, but not less than 10 psig (69 kPa gauge) for a period of not less than 15 minutes. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. The test pressure for valves and connections to appliances shall not exceed 0.5 psig (3kPa).

2.2.25Electrical Sections

Delete Chapters 34 through 43.

2.2.26Appendix A - Sizing and Capacities of Gas Piping

Adopted.

2.2.27Appendix P - Sizing of Water Piping System

Adopted.

2.2.28Appendix Q - Tiny Houses
1. Amend Appendix Q Tiny Houses as follows:
a. Q101.1 Scope: Change to read: This appendix shall be applicable to tiny houses, and "tiny homes" as defined by section 24-32-3302(35), C.R.S., used as single dwelling units. Tiny houses, and "tiny homes" as defined by section 24-32-3302(35), C.R.S., shall comply with this code except as otherwise stated in this appendix. Insert "...and tiny homes" after each reference to "tiny houses" in all sections of this appendix.
b. Q102.1 General: Add TINY HOME: as defined by section 24-32-3302(35), C.R.S. The square footage of a tiny home excludes loft area.
c. Edit Q104.2 to read: Loft Access and egress. The access to and primary egress from lofts shall be of any type described in Sections Q104.2.1 through Q104.2.5. The loft access and egress element along its required minimum width shall meet the loft where its ceiling height is not less than 3 feet (914 mm). Egress from the sleeping loft must be present and may be reached from the loft or the loft landing.
d. Edit Q104.2.1. to read: Stairways. Stairways accessing lofts shall comply with this code or with Sections Q104.2.1.1 through Q104.2.1.7.
e. Edit Q104.2.2 to read: Headroom. The headroom above stairways accessing a loft shall be not less than 6 feet 2 inches (1880 mm), as measured vertically, from a sloped line connecting the tread, landing or landing platform nosings in the center of their width and vertically from the landing platform along the center of its width.
f. Edit Q10 4.1.3: Add See Figure Q104.1.3:

Click to view image

g. Edit Q104.2.1.4 to read: Landings. Intermediate landings and landings at the bottom of stairways shall comply with Section R311.7.6, except that the depth in the direction of travel shall be not less than 24 inches (610 mm).
h. Add Q104.2.1.5: Landing platforms. The top tread and riser of stairways accessing lofts shall be constructed as a landing platform where the loft ceiling height is less than 6 feet 2 inches (1880 mm) where the stairway meets the loft. The landing platform shall be not less than 20 inches (508 mm) in width and in depth measured horizontally from and perpendicular to the nosing of the landing platform. The landing platform riser height to the loft floor shall be not less than 16 inches (406 mm) and not greater than 26 inches (660 mm).
i. Renumber Q104.2.1.5 Handrails to Q104.2.1.6 Handrails.
j. Renumber Q104.2.1.6 Stairway guards to Q104.2.1.7 Stairway guards.
k. Edit Q104.2.2.1 Size and capacity from "...supporting a 200-pound (75kg) load..." to "...supporting a 300-pound (136kg) load...".
l. Edit Q104.2.5 to read: Loft guards. Loft guards shall be located along the open sides of lofts. Loft guards shall be not less than 36 inches (914 mm) in height or one-half of the clear height to the ceiling, whichever is less. Loft guards shall comply with Section R312.1.3 and Table R301.5 for their components.
m. Add: Q106: SECTION Q106

ENERGY CONSERVATION

Q106.1 Air leakage testing. The air leakage rate for shall not exceed 0.30 cubic feet per minute at 50 Pascals of pressure per square foot of the dwelling unit enclosure area. The air leakage testing shall be in accordance with the testing methods required in IECC 2015 R402.4.1.2. The dwelling unit enclosure area shall be the sum of the areas of ceilings, floors and walls that separate the conditioned space of a dwelling unit from the exterior, its adjacent unconditioned spaces and adjacent dwelling units.
Q106.1.1 Whole-house mechanical ventilation. Where the air leakage rate is in accordance with Section Q106.1, the tiny house shall be provided with whole house mechanical ventilation in accordance with Section M1505.4.
Q106.2 Alternative compliance. Tiny houses and tiny homes shall be deemed to be in compliance with Chapter R4 of the adopted International Energy Conservation Code, provided that the following conditions are met:
1. The insulation and fenestration meet the requirements of IECC 2015 Table R402.1.2 as amended by these rules (allowing ceiling insulation to be R30 vs. R49).
2. The thermal envelope meets the requirements of IECC 2015 Section R402 and IECC 2015 Table R402.4.1.1.
3. Solar, wind or other renewable energy source supplies not less than 90 percent of the energy use for the structure.
4. Solar, wind or other renewable energy source supplies not less than 90 percent of the energy for service water heating.
5. Permanently installed lighting is in accordance with IECC 2015 Section R404.
6. Mechanical ventilation is provided in accordance with IRC 2018 Section M1505 and operable fenestration is not used to meet ventilation requirements.
n. Add: Q107: Bathroom Lavatory, For Tiny Homes, if a bathroom lavatory cannot be added due to size constraints, then the kitchen sink can be substituted to meet the lavatory requirement.
o. Add: Q108: Construction on a Built-for-Purpose Trailer. The tiny home will be built on a built-for-purpose trailer. Trailers that have structure modifications prior to the start of the tiny home build must provide engineered stamped drawings and the documentation to be roadworthy on Colorado roads. (Structural modifications may change the trailer classification to a kit trailer or homemade trailer and a new VIN/GVWR and physical inspection by CDOT or Colorado State Highway Patrol, or other approved agencies may be required.)
p. Add: Q109: Tiny Home on a Temporary Foundation. A tiny home on wheels which is installed on a temporary foundation may utilize connections to an electrical pedestal or plumbing connections that allow for movement from one location to another.
2.3The International Mechanical Code (IMC), 2018 Edition, published by the International Code Council, Inc. (ICC). This is a safety code and is available through the ICC at:https://www.iccsafe.org.
2.3.1Section 303.3.1 LPG appliance

Add the following new section:

LPG appliances shall not be installed in a pit, basement, or crawl space where unburned fuel may accumulate unless an approved sensing device is installed in conjunction with an automatic shutoff valve located where the gas enters the structure only for retro-fitting of existing structures or as required by the local jurisdiction.

2.3.2Section 903.1 General

Add the following additional sentence:

Every new installation of a solid fuel-burning, vented decorative appliance or room heater shall meet the most stringent emission standards for wood stoves established under State statute and/or regulations promulgated by the State Air Quality Control Commission as of the time of installation of the appliance or room heater. (Effective January 1, 1991 - CC90-617).

2.3.3Section 903.3 Unvented gas log heaters

Delete this section in its entirety.

2.4The International Plumbing Code (IPC), 2018 Edition, published by the International Code Council, Inc. (ICC). This is a safety code and is available through the ICC at:https://www.iccsafe.org.
2.4.1Appendix Chapter E - Sizing of water piping systems
2.4.1.1Section 312.3

Delete the words "Plastic Piping shall not be tested by using air".

2.5The National Electric Code (NEC), published by the National Fire Protection Association, Inc. (NFPA), and the Edition as adopted by the Colorado State Electrical Board at the time of plan submittal. This is a safety code and is available through the NFPA at:https://www.nfpa.org.

A transition period of 180 days after the effective date applies. The Program Manager for the Building Codes and Standards Section is authorized to grant, in writing, one extension, for a period not more than 180 days.

Any conflicts that may arise between these amendments and a future State adopted edition of the NEC shall be resolved by applying the specific amended provisions of the 2020 edition. The following amendments are made to the NEC for use with all factory-built units:

2.5.1Article 545 Manufactured Buildings

Add the following new section:

2.5.1.1Section 545.14 Testing
(A) Continuity and Operational Tests and Polarity Checks. Each manufactured building shall be subjected to:
(1) An electrical continuity test to ensure that all exposed electrically conductive parts are properly bonded;
(2) An electrical operational test to demonstrate that all equipment, except water heaters and electric furnaces, is connected and in working order; and
(3) Electrical polarity checks of permanently wired equipment and receptacle outlets to determine that connections have been properly made.

These tests shall be performed after branch circuits are complete and after wiring devices are installed and wiring properly terminated.

2.5.2Article 334.23 Cables Run Across the Top of Floor Joists/Rafters

Add the following new sentence at the end:

Substantial guard strips or other protection shall be provided to protect wiring within three (3) feet of the marriage line where the attic is exposed and the roof is completed on-site, such as a hinged roof.

2.5.3 Article 210.8(F) Outdoor Outlets

Add the following to the existing exception:

...than those covered in 210.8(C), and outlets designated for outdoor mechanical cooling equipment.

This exception is limited to outdoor mechanical cooling equipment shipped loose by the manufacturer with the factory-built structure to be completed on-site. This exemption does not apply if the outdoor mechanical cooling equipment is provided by any other party. If it is provided by a party that is not the manufacturer of the factory-built structure, then the State Electrical Board's requirement applies.

2.6The International Fuel Gas Code (IFGC), 2018 Edition, published by the International Code Council, Inc. (ICC). This is a safety code and is available through the ICC at:https://www.iccsafe.org.
2.6.1Section 303.3 Prohibited locations

Add the following:

LPG appliances shall not be installed in a pit, basement, or crawl space where unburned fuel may accumulate unless an approved sensing device is installed in conjunction with an automatic shutoff valve located where the gas enters the structure only for retro-fitting of existing structures or as required by the local jurisdiction.

2.6.2Section 303.3, 501.8 #8, Section 621

Delete all and replace with the following:

Unvented fuel fired room heaters and unvented fuel fired fireplaces are prohibited.

2.6.3 Section 406.4.1 Test pressure

Revise to read as follows:

The test pressure to be used shall not be less than 1 1/2 times the proposed maximum working pressure, but not less than 10 psig (69 kPa gauge), irrespective of design pressure. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe. The test pressure for valves and connections to appliances shall not exceed 0.5 psig (3kPa).

2.7The International Energy Conservation Code (IECC), 2015 Edition, published by the International Code Council, Inc. (ICC). This code is available through the ICC at:https://www.iccsafe.org.
2.7.1Section C101.5 and R101.5 Compliance

Residential buildings shall meet the provisions of the 2015 IECC-Residential provisions.

Commercial buildings shall meet the provisions of the 2015 IECC-Commercial provisions.

Add the following exception:

Where the location the factory-built structure is to be permanently set is known and the local jurisdiction has adopted the 2012 IECC, the building may comply with the 2012 IECC. Where the location of the factory-built structure is to be permanently set is known and the local jurisdiction has adopted an earlier version of the energy code which is less restrictive than the 2012 IECC, including any local jurisdiction amendments, or where no code has been adopted that regulates the design of buildings for effective energy use, the structure may comply as far back as the 2009 IECC.

2.7.2Section C202, R202 - Definitions

Add the following definition:

ZERO-ENERGY BUILDING. A building with zero net energy consumption and zero carbon emissions annually as certified by an approved annual energy use analysis.

2.7.3Section C402.1.1 Low energy buildings

Add the following exemption:

4.Zero-Energy Buildings. Zero energy buildings are exempt from the provisions of the International Energy Conservation Code.
2.7.4Section C402.1.2

Add the following exemption:

Equipment buildings intended to house temperature sensitive equipment, not intended for human occupancy, and not exceeding 1000 sq. ft. will be exempt from the building thermal envelope provisions of this code.

2.7.5Section C404.5

Delete this section in its entirety.

2.7.6Section R402.1 Low energy buildings

Add the following exemption:

1. Zero-Energy Buildings. Zero energy buildings are exempt from the provisions of the International Energy Conservation Code.
2.7.7Section R402.4.2.1

Revise to add the following exception:

All air barrier elements shall be installed as detailed in Table 402.4.1.1. and are inspected and verified with a checklist incorporated into the Quality Assurance Inspection Checklist and part of the "finished home" file for the building/dwelling. All elements of the air barrier shall be listed and installed per the manufacturer's installation instructions. A completed air barrier checklist shall be kept on file with the Division of Housing and the manufacturer's quality assurance program.

If not complying with the first paragraph, an air leakage test shall not exceed 5 air changes per hour in all climate zones and shall comply with one of the compliance methods in R401.2.

Construction Standards and Procedures for U.S. Housing and Urban Development (HUD) Homes

These standards and procedures are available through HUD at:https://www.hud.gov.

Pursuant to sections 24-32-3302(12), 24-32-3302(13), 24-32-3302(20), 24-32-3302(32), 24-32-3305(5), 24-32-3306(1), 24-32-3307(2), 24-32-3309(1)(a), and 24-32-3327, C.R.S., the State Housing Board adopts the following requirements for manufactured homes constructed to the "National Manufacturing Housing Construction and Safety Standards Act of 1974", 42 U.S.C. sec. 5401 et seq. (manufactured from June 15, 1976 to present):

2.8 Compliance with Title 24: Housing and Urban Development; Subtitle B-Regulations Relating to Housing and Urban Development (Continued); Chapter XX-Office of Assistant Secretary for Housing-Federal Housing Commissioner, Department of Housing and Urban Development; Part 3280-Manufactured Home Construction and Safety Standards, of Title 24.
2.9 Compliance with Part 3282-Manufactured Home Procedural and Enforcement Regulations of the same title, subtitle, and chapter in Rule 2.8 above as applied and enforced as the state administrative agency for the federal government.
2.10 Compliance with Part 3286-Manufactured Home Installation Program of the same title, subtitle, and chapter in in Rule 2.8 above, which is inspected and enforced through application of the Division of Housing's adopted Manufactured Housing Installation Codes.
2.11 Compliance with Part 3288-Manufactured Home Dispute Resolution Program of the same title, subtitle, and chapter in Rule 2.8 above as applied and enforced as the state administrative agency for the federal government.

Manufactured Home and Tiny Home Installation Standards

These standards and guidelines are available through the Division of Housing in the form of the "Manufactured Home and Tiny Home Installation Handbook" located at:https://www.colorado.gov/dola/division-housing.

2.12 Pursuant to section 24-32-3310, C.R.S., nothing in this rule is intended to interfere with the right of a local jurisdiction to enforce its rules governing the installation of a manufactured home or tiny home as long as those rules are not inconsistent with this rule. Pursuant to section 24-32-3318, C.R.S., a local jurisdiction may not adopt less stringent standards for the installation of a manufactured home or tiny home than those adopted by the Division and may not adopt a different standard without express consent by the Division. However, a local jurisdiction may adopt unique public safety requirements related to geographic or climatic conditions such as weight restrictions for snow loads or wind shear factors subject to the conditions outlined in section 24-32-3318, C.R.S.
2.12.1 Factory-built residential structures (modular) must be installed on a permanent foundation approved through the local jurisdiction. In areas where no building codes have been adopted, the foundation must be designed and approved by a State of Colorado licensed engineer unless plans are approved by the Division and in compliance with its adopted International Residential Code (IRC) foundation prescriptive requirements.
2.13 Primary Standards (required for all new homes):
2.13.1 The current written installation instructions provided by the manufacturer of the home.
2.13.1.1 An installation of a HUD-code home in this state must be performed in strict accordance with the applicable manufacturer's installation instructions. The value of the allowable bearing capacity of the soil the home will rest on must be recorded by the installer on the Installation Authorization form or other Division-approved form and justification for higher values also provided if it is determined to be other than 1,500 psf.
2.14 Alternate Standards (for older homes or homes that do not include the manufacturer's installation instructions) - installation must be in accordance with the following alternate standards adopted by the Division and State Housing Board:
2.14.1 Modular Homes and Tiny Homes
2.14.1.1 Structural attachment requirements approved by a State of Colorado actively licensed engineer.
2.14.1.2 Current version of the International Residential Code (IRC) as adopted by the State Housing Board.
2.14.2 Mobile and HUD-code Homes
2.14.2.1 National Fire Protection Association (NFPA) 225, Model Manufactured Home Installation Standard 2013 Edition, including any revisions, additions, and deletions identified below.
2.14.2.1.1Section 4.4.4 Site suitability with home design

Revise to read as follows:

The installer shall verify data plates provided with a HUD-code home prior to installation in the state of Colorado. The data plate shall be matched with the home (serial numbers). The data plate shall indicate the following minimums:

Wind Zone: I

Thermal Zone: III

Roof Load: Middle (30 PSF)

If the data plate does not meet these minimum requirements, the installer shall not set the home. The installer is required to check with the local jurisdiction where the home will be located to determine if it is designed for the area's proven snow or wind load since some parts of the state are subjected to heavy snow and/or high winds.

2.14.2.1.2Section 5.3 Fire separation distance

Revise to read as follows:

Fire separation distances shall comply with local rules or regulations. In their absence, the most current version of the International Residential Code (IRC) as adopted by the Housing Board applies.

2.14.2.1.3Section 5.5.2

Revise to read as follows:

Soil that supports footings and foundations shall be capable of accommodating all loads required by this standard. To help prevent settling or sagging, the foundation must be constructed on firm, undisturbed soil or 90% compacted soil. The design bearing capacity of the soil shall be determined in accordance with Section 5.6.

2.14.2.1.4Section 5.6 Investigation and Bearing Capacity of Soil

Revise as follows:

Soils that appear to be composed of peat, organic clays, uncompacted fill, expansive or other unusual conditions shall have a licensed engineer determine the classification and maximum allowable soil bearing capacity.

Otherwise the bearing capacity of the soil shall be assumed to be 1,500 psf.

A larger bearing capacity for the soil may be used as follows provided the class of soil is known:

Sandy gravel and/or gravel, very dense or cemented sands (GW, GP, SW, SP, GM, SM) ------------- 2,000 psf

Sedimentary and foliated rock---------------------------- 4,000 psf

When a value other than 1,500 psf is determined for the soil bearing capacity it shall be recorded by the installer on the Division of Housing's Installation Authorization form and justification for higher values shall also be provided.

2.14.2.1.5Section 5.8.1 Vapor retarder

Revise as follows:

If the space under the home is to be enclosed with skirting or other material, a vapor retarder that keeps ground moisture out of the home shall be installed unless specifically allowed to be omitted by the authority having jurisdiction.

2.14.2.1.6Section 5.8.3.2

Revise as follows:

The vapor retarder may be placed directly beneath footings, or otherwise installed around or over footings placed at grade, and around anchors or other obstructions. Any voids or tears in the vapor retarder must be repaired.

2.14.2.1.7Section 6.2.3.1.2

Delete this section.

2.14.2.1.8Section 6.2.3.1.3.1

Revise as follows:

Tables 6.2.3.1.3(a), 6.2.3.1.3(b), and 6.2.3.1.3(c) for pier capacities, as replaced in Appendix A, shall be used when the manufacturer's installation instructions are not available.

2.14.2.1.9Section 6.2.3.1.3.2

Revise as follows:

Manufactured piers shall be rated at least to the capacities given in Tables 6.2.3.1.3(a), 6.2.3.1.3(b), and 6.2.3.1.3(c), as replaced in Appendix A, and locally constructed piers shall be designed to transmit these loads safely as required by 6.2.3.2.

2.14.2.1.10Section 6.2.3.2.2.2

Revise as follows:

Caps shall be of solid masonry of at least 4 in. (100 mm) nominal thickness, or of treated or hardwood dimensional lumber at least 2 in. (50mm) nominal thickness, or of 1/2" thick steel.

2.14.2.1.11Section 6.2.3.2.3.1

Revise as follows:

Nominal 4 in. x 6in. (100mmx 150mm) hardwood shims shall be used to level the home and fill any gaps between the base of the I-beam and the top of the pier cap. Any of the following hardwood species may be used: Ash, Beech, Birch, Hickory, Oak, Rock Elm, Black or Red Maple, or Sweetgum.

2.14.2.1.12Section 6.2.3.2.3.3

Revise as follows:

Hardwood (species identified in the amendment to Section 6.2.3.2.3.1 above) or treated wood plates shall be used to fill in any remaining vertical gap no thicker than 2". The maximum total gap to be filled with shims and plates shall be 2".

2.14.2.1.13Section 6.2.5.5

Revise as follows:

All homes. Supports shall be placed on both sides of side wall exterior doors and any other side wall openings greater than 48 in. (such as entry and sliding glass doors), and under porch posts, factory installed fireplaces and wood stoves. Size perimeter piers under openings based on Table 6.2.3.1.3(b), as replaced in Appendix A, "Exterior wall" where the actual side wall opening shall be less than or equal to the spacing selected from the table.

Homes requiring perimeter blocking. Refer to Figure 6.2.5.3 and Figure 6.2.5.4 and Table 6.2.3.1.3(b), as replaced in Appendix A, for homes requiring perimeter blocking in addition to sidewall opening blocking described above.

2.14.2.1.14Section 6.3.1.2.2

Delete this section.

2.14.2.1.15Section 6.5.2

Delete this section.

2.14.2.1.16Section 7.2

Revise as follows:

The home shall be installed and leveled by installation personnel approved by the State of Colorado to install manufactured homes.

2.14.2.1.17Section 7.3

Revise as follows:

The interconnection of multi-section homes shall be completed in accordance with the manufacturer's installation instructions. When the manufacturer's installation instructions are not available, the interconnection of multi-section homes shall be in accordance with Table 7.3, as provided in Appendix A, or per the requirements approved by a State of Colorado licensed engineer.

2.14.2.1.18Section 7.5 Anchoring Instructions

Section 7.5.1 Security against the wind

Section 7.5.1.1

Revise as follows:

After blocking and leveling, the installer shall secure the manufactured home against wind per Section 7.5.2 or Section 7.5.3. Anchorage shall be for Wind Zone I. Homes that are designed for Wind Zone II and III must be anchored per the Manufacturer's Installation Instructions or the requirements of a professional engineer.

2.14.2.1.19Section 7.5.2 Proprietary Anchorage Systems

Add the following:

A proprietary anchorage system may be used to resist overturning and lateral movement (sliding) caused by wind as long as it complies with all of the following:

1. The system shall be listed by a nationally recognized third-party agency for anchoring manufactured homes.
2. The system shall be evaluated and approved by a licensed professional engineer.
3. The system shall be recognized as acceptable for use by the Division of Housing.
4. The installer shall follow the requirements in the anchorage system installation instructions.
2.14.2.1.20Section 7.5.3 Ground Anchor System

Section 7.5.3.1 Specifications for Tie-Down Straps and Anchors

Add the following:

Straps and anchors are to have corrosion protection at least equivalent to that provided by a coating of zinc on steel of not less than 0.30 oz/ft2 of surface coated. Straps and anchoring equipment must be capable of resisting a minimum ultimate load of 4,725 lbs and a working load of 3,150 lbs as installed; determined by a licensed professional engineer, architect or tested by a nationally recognized third-party agency. Straps are to be 1.25"x0.035" or larger steel strapping conforming to ASTM D 3953, Type 1, Grade 1, Finish B. Anchors are to be installed in accordance with their listing or certification to their full depth.

2.14.2.1.21Section 7.5.3.2 Number and Location of Anchors

Section 7.5.3.2.1 Transverse Anchorage

Add the following:

The number and location of anchors and anchor straps for securing single-section and multi-section manufactured homes in the transverse direction shall conform to the manufacturer's installation instructions. When relocating the home or when the manufacturer's installation instructions are not available, the number and location of anchors and anchor straps shall conform to Table 7.5.3.2.1, Figure 7.5.3.2.1(a), and Figure 7.5.3.2.1(b), as provided in Appendix A.

2.14.2.1.22Section 7.5.3.2.2 Longitudinal Anchorage

Add the following:

The number and location of anchors and anchor straps for securing single-section and multi-section manufactured homes in the longitudinal direction shall conform to the manufacturer's installation instructions. When relocating the home or when the manufacturer's installation instructions are not available, the number and location of longitudinal anchors and anchor straps shall conform to Table 7.5.3.2.2 and Figure 7.5.3.2.1(a), as provided in Appendix A.

2.14.2.1.23Section 7.5.3.2.3 Anchor Installation

Add the following:

The installed ground anchor type and size/length must be listed for use in the soil class at the site and for the minimum and maximum angle permitted between the diagonal strap and the ground and all ground anchors must be installed in accordance with their listing or certification and the ground anchor manufacturer installation instructions. Unless the foundation system is frost-protected to prevent the effects of frost heave, the ground anchors shall be installed below the frost line. Ground anchor stabilizer plates shall be installed in accordance with the anchor and plate manufacturer installation instructions.

2.14.2.1.24Section 7.5.3.2.4 Side wall or over the roof straps

Add the following:

If sidewall, over-the-roof, mate-line, or shear wall straps are installed on the home, they must be connected to an anchoring assembly.

2.14.2.1.25Section 7.6.3 Expanding Rooms

Revise as follows:

Expanding rooms shall be installed in accordance with the manufacturer's instructions. When the manufacturer's instructions are not available, perimeter blocking shall be installed in accordance with Table 6.2.3.1.3(b), as replaced in Appendix A, and anchors shall be installed in accordance with Section 7.5.3.2.

2.14.2.1.26Section 7.7.4.2

Revise (2) as follows:

(2) Walls-200.
2.14.2.1.27Section 8.1 Installation of Site-Installed Features

Revise as follows:

Carports, awnings, porches, roof covers, and other similar attachments or additions shall not be supported by a manufactured home unless the home was specifically designed to accommodate such attachments or the attachment is designed by a licensed professional engineer. Non-structural connections for flashings and coverings at the junction are acceptable.

2.14.2.1.28Section 8.4

Delete this section.

2.14.2.1.29Section 8.8.3

Revise as follows:

Access opening(s) not less than 18 inches in width and 24 inches in height must be provided and located so that any utility connections are accessible.

2.14.2.1.30Section 8.9 Telephone and Cable TV

Revise as follows:

Telephone, cable TV, and similar wiring shall be installed per the Authority Having Jurisdiction (AHJ) requirements and the National Electric Code (NEC).

2.14.2.1.31Section 9.4 Range, Cooktop, Oven Venting, and other Fixtures or Appliances

Add new Section 9.4.3 to read as follows:

If other fixtures or appliances are to be site-installed, follow the manufacturer's installation instructions. Use only products listed for manufactured homes and follow all applicable local codes.

2.14.2.1.32Section 9.7 Furnace, Water Heater, and other Fuel Fired Appliances

Add this new section to read as follows:

Verify appliance is installed per the manufacturer's installation instructions including any combustion air requirements. Verify flues are in place and are properly connected and extend through the roof with flashing and caps.

2.14.2.1.33Section 10.4.2 Orifices and Regulations

Revise as follows:

Before making any connection to the site supply, the inlet orifices of all gas-burning appliances shall be checked to ensure they are correctly set-up for the type of gas to be supplied and are sized correctly for the altitude above sea level where the home is set. The manufacturer's installation instructions for the appliance shall be followed.

2.14.2.1.34 Chapter 11 Life Safety Features

Revise as follows:

2.14.2.1.34.1Smoke Alarms

Verify smoke alarms are installed to protect the living area, rooms designed for sleeping, on upper levels, and in the basement for homes installed over a basement. Verify smoke alarms are installed and operating properly to meet the requirements of 24 CFR 3280.

2.14.2.1.34.2Carbon Monoxide Alarms

An approved carbon monoxide alarm shall be installed outside of each separate sleeping area within 15 feet of the entrance to the bedrooms in dwelling units within which fuel-fired appliances are installed and in dwelling units that have attached garages.

2.14.2.1.34.3Fire Separation Distance

Fire separation distances shall comply with local rules or regulations. In their absence, the most current version of the International Residential Code (IRC) as adopted by the State Housing Board, shall apply.

2.14.2.2 Permanent Foundations Guide for Manufactured Housing (4930.3G),, published by the U.S. Department of Housing and Urban Development (HUD), including any revisions, additions, and deletions identified below, or the most recent version.
2.14.2.2.1 Appendix B - Foundation Design Load Tables

Revised as follows:

In the multi-section tables under the marriage wall opening width (ft.), the values given for required effective footings area - Aftg (sq.ft.), shall be divided by 2.

2.15 Upon written request, the Division of Housing will consider modifications to the standards or alternate materials and methods of construction. The Division of Housing will require that sufficient evidence or proof be submitted to support and substantiate the modification or alternate request.
2.15.1 The Division of Housing may approve any such modification or alternate, provided the Division of Housing finds that the proposed modification or alternate conforms with the intent and purpose of the standards and is equivalent in suitability, strength, effectiveness, durability, safety, and sanitation.
2.15.2 The approval of any modification and/or alternate by the Division of Housing will be made in writing and is required prior to commencing the work in question.
2.15.3 In the event that a local jurisdiction has declared a state of emergency, and met the written request and evidence or proof submitted to support and substantiate the request as stated in Rule 2.15, and provided the Division of Housing makes the findings required by Rule 2.15.1, the Division may for a period of 180 days allow a modification to the standards, or alternate materials and methods of construction. Additional 180 day extensions may be requested in writing by the local jurisdiction to DOH. Requests from the local jurisdiction should include a copy of the approved local jurisdiction codes and explanation of the requested changes and any site specific information. Requests will not be accepted that are more stringent than the current adopted codes. These structures will receive an Emergency Response Unit insignia from the Division of Housing.

8 CCR 1302-14-2

41 CR 11, June 10, 2018, effective 7/1/2018
42 CR 21, November 10, 2019, effective 11/30/2019
43 CR 16, August 25, 2020, effective 9/14/2020
44 CR 10, May 25, 2021, effective 4/13/2021
44 CR 10, May 25, 2021, effective 4/14/2021
44 CR 11, June 10, 2021, effective 5/11/2021
44 CR 16, August 25, 2021, effective 7/13/2021
44 CR 16, August 25, 2021, effective 9/14/2021
46 CR 11, June 10, 2023, effective 6/30/2023
46 CR 22, November 25, 2023, effective 10/24/2023 exp. 2/21/2024 (Emergency)
47 CR 06, March 25, 2024, effective 4/15/2024