7 Colo. Code Regs. § 1101-5-2-2

Current through Register Vol. 47, No. 24, December 25, 2024
Section 7 CCR 1101-5-2-2 - Condemning a Boiler
(a) Conditions which a State or Special Inspector may determine to be unsafe include: bypassed safety controls, inoperative safety valves, an excessive gas leak and any other condition that, in the Inspector's judgment, means the boiler should be condemned.
(b) The owner or user must shut down the condemned boiler or pressure vessel as directed by the Inspector. If neither the owner nor user is available, the Inspector will cause the boiler to be shut down.
(c) The Inspector will affix to a condemned boiler or pressure vessel a notice that it has been condemned and may not be used until satisfactory repairs are made, as determined by a re-inspection by an authorized State or Special Inspector.

7 CCR 1101-5-2-2

40 CR 11, June 10, 2017, effective 7/1/2017