7 Colo. Code Regs. § 1101-15-3-2

Current through Register Vol. 47, No. 24, December 25, 2024
Section 7 CCR 1101-15-3-2 - Delivery after Interruption of Service
(a) When delivery is made to an LPG container assembly that has had an interruption of service as defined by these regulations, a leak check shall be performed immediately after LPG is introduced into the piping.
(b) The leak check shall be performed according to one of the methods set forth in Annex D (Suggested Method of Checking for Leakage) of NFPA 54 or another method approved by the division in advance.
(c) The person performing the leak check shall document that the test was performed. The documentation shall include, at minimum, the following information:
(1) Date the test was performed
(2) Test start time
(3) Test end time
(4) Name of person performing the test
(5) Name of person's employer
(6) Address and phone number of person's employer
(7) Type of test
(8) Test start pressure and end pressure if a constant pressure is used
(d) Documentation of the leak check shall be retained for a minimum of one year by the employer of the person who performed the test.

7 CCR 1101-15-3-2

40 CR 07, April 10, 2017, effective 5/1/2017
40 CR 17, September 10, 2017, effective 9/30/2017