5 Colo. Code Regs. § 1002-84.7

Current through Register Vol. 47, No. 17, September 10, 2024
Section 5 CCR 1002-84.7 - RECLAIMED WATER CATEGORIES AND STANDARDS
(A)Category 1 Standards: Reclaimed water, for uses where Category 1 water is required, shall, at a minimum, receive secondary treatment with disinfection. The following reclaimed water standards shall apply at the point of compliance:

Parameter

Limit

E. coli /100 ml

126/100 ml monthly geometric mean and 235/100 ml single sample maximum.

Total Suspended Solids

30 mg/L as a daily maximum.

(B)Category 2 Standards: Reclaimed water, for uses where Category 2 water is required, shall, at a minimum, receive secondary treatment with filtration and disinfection. The following reclaimed water standards shall apply at the point of compliance:

Parameter

Limit

E. coli /100 ml

126/100 ml monthly geometric mean and 235/100 ml single sample maximum.

Turbidity, NTU

Not to exceed 3 NTU as a monthly average and not to exceed 5 NTU in more than 5 percent of the individual analytical results during any calendar month.

(C)Category 3 Standards: Reclaimed water for uses where Category 3 water is required shall, at a minimum, receive secondary treatment with filtration and disinfection. The following reclaimed water standards shall apply at the point of compliance:

Parameter

Limit

E. coli /100 ml

None detected in at least 75% of samples in a calendar month and 126/100 ml single sample maximum.

Turbidity, NTU

Not to exceed 3 NTU as a monthly average and not to exceed 5 NTU in more than 5 percent of the individual analytical results during any calendar month.

5 CCR 1002-84.7

41 CR 21, November 10, 2018, effective 11/30/2018
42 CR 23, December 10, 2019, effective 1/14/2020
43 CR 17, September 10, 2020, effective 9/30/2020
45 CR 14, July 25, 2022, effective 8/14/2022