Revise and replace section R502.2 as follows:
R502.3 Allowable joist spans.
Spans for floor joists shall be in accordance with Tables R502.3.1(1) and R502.3.1(2). For other grades and species and for other loading conditions, refer to the AWC STJR or the American Wood Council "AWC" Maximum Span Calculator for Wood Joists and Rafters found at: https://www.awc.org/codes-standards/calculators-software/spancalc.
Delete the following from R502.11.1 Design.
After registered design professional, Delete "where required by the statutes of the jurisdiction in which the project is to be constructed in accordance with Section R106.1."
Add new section R506.1.1 Control Joints as follows:
Exception: Control joints may be omitted when the slab is reinforced in accordance with Table R506.1.1. Reinforcement shall be placed at the mid-depth of the slab or two inches (51 mm) from the top of slabs greater than 4 inches (102 mm) in thickness.
Add new Table R506.1.1 as follows:
Table R506.1.1
MAXIMUM DIMENSION OF SLAB OR DISTANCE BETWEEN CONTROL JOINTS (ft.) | WWF WIRE | WWF WIRE SIZE | |||||
Slab Thickness (in.) | |||||||
3.5 | 4.0 | 4.5 | 5.0 | 5.5 | 6.0 | ||
42 | 36 | 32 | 29 | 26 | 24 | 6 x 6 | W1.4 x W1.4 |
59 | 52 | 46 | 42 | 38 | 35 | 6 x 6 | W2.0 x W2.0 |
86 | 75 | 67 | 60 | 55 | 50 | 6 x 6 | W2.9 x W2.9 |
780 CMR, ch. 51, ch. R5, R502.3