780 CMR, ch. 51, ch. 4, R405.3

Current through Register 1538, January 3, 2025
Subsection R405.3 - Passive House International (PHI) Documentation
1. If using PHI Passive House software, prior to the issuance of a building permit, the following items must be provided to the Building Official:
a. A PHPP compliance report which demonstrates project compliance with current PHI performance requirements;
b. A statement from the Certified Passive House Consultant/Designer (CPHC/D) that the PHPP results and compliance report accurately reflect the plans submitted;
c. Evidence of project registration from a Certified Passive House Certifier.

OR

a. A Design Certification Letter from a Certified Passive House Certifier.
2. Prior to the issuance of a certificate of occupancy, the following item(s) must be provided to the building official:
a. A Design Certification Letter from a Certified Passive House Certifier.
b. An updated PHPP compliance report which reflects "as-built" conditions and test results (blower door and ventilation results) that demonstrate project compliance with PHI performance requirements;
c. A statement from the CPHD that the project test results meet the model performance requirements, all the mandatory limits and any other mandatory requirements.
d. A copy of the Passive House Verifier's or Rater's test results;

OR

a. A Final Certification Letter from a Certified Passive House Certifier

AND

e. A statement from the Passive House Verifier or Rater of compliance with R404.4: EV ready, and Appendix RB: Solar Ready Provisions.

780 CMR, ch. 51, ch. 4, R405.3

Amended by Mass Register Issue 1532, eff. 10/11/2024.