780 CMR, ch. 51, app AF, app AJ, AJ112.4

Current through Register 1538, January 3, 2025
Subsection AJ112.4 - Fire Protection

Fire protection features shall comply with the code for new construction throughout the addition.

AJ112.4.1Smoke, Carbon Monoxide and Heat Protection. Where the addition requires smoke, carbon monoxide, and/or heat detection in Sections R314, R314.5 or R315, the addition shall comply with the provisions for new construction.
AJ112.4.1.1 Where the addition requires smoke, carbon monoxide, and/or heat detection in accordance with AJ102.3, the provisions shall apply throughout the building.
AJ112.4.2Automatic fire sprinkler system. Where the addition creates a condition that would require the installation of a fire sprinkler system per Section R313, an automatic fire sprinkler system shall be installed throughout the addition.

780 CMR, ch. 51, app AF, app AJ, AJ112.4