Carbon monoxide protection shall be provided in accordance with 527 CMR 31.00: Carbon Monoxide Alarms and 248 CMR as listed in Chapter 35: Referenced Standards, in addition to this Code. Carbon monoxide alarms, carbon monoxide detectors and combination smoke/carbon monoxide alarms and combination smoke/carbon monoxide detectors described in sections 916.1.1 through 916.1.4 shall be installed and maintained in accordance with the provisions of this code, 527 CMR 31.00, 248 CMR, NFPA 72 and NFPA 720.
916.1.1 Carbon Monoxide Alarms. Single- or multiple-station carbon monoxide alarms shall be listed and labeled in accordance with ANSI/UL 2034.916.1.2 Carbon Monoxide Detectors. Carbon monoxide detectors shall be listed and labeled in accordance with ANSI/UL 2075.916.1.3 Combination Smoke/Carbon Monoxide Alarms. Combination smoke/carbon monoxide alarms shall be listed and labeled in accordance with ANSI/UL 217 and ANDI/UL 2034. The smoke alarm shall utilize photoelectric sensing technology.916.1.4 Combination Smoke/Carbon Monoxide Detectors. Combination smoke/ carbon monoxide detectors shall be listed and labeled in accordance with ANSI/UL 268 and ANDI/UL 2075. The smoke alarm shall utilize photoelectric sensing technology.