780 CMR, 1022.4

Current through Register 1533, October 25, 2024
Subsection 1022.4 - Penetrations

Penetrations into and openings through an exitenclosure are prohibited except for required exit doors, equipment and ductwork necessary for independent ventilation or pressurization, sprinkler piping, standpipes, electrical raceway for fire department communication systems and electrical raceway serving the exitenclosure and terminating at a steel box not exceeding 16 square inches (0.010 m2). Such penetrations shall be protected in accordance with Section 713. There shall be no penetrations or communication openings, whether protected or not, between adjacent exit enclosures.

780 CMR, 1022.4