780 CMR, 1018.1

Current through Register 1533, October 25, 2024
Subsection 1018.1 - Construction

Corridors shall be fire-resistance rated in accordance with Table 1018.1. The corridor walls required to be fire-resistance rated shall comply with Section 709 for fire partitions.

Exceptions:

1. A fire-resistance rating is not required for corridors in an occupancy in Group E where each room that is used for instruction has at least one door opening directly to the exterior and rooms for assembly purposes have at least one-half of the required means of egress doors opening directly to the exterior. Exterior doors specified in this exception are required to be at ground level.
2. A fire-resistance rating is not required for corridors contained within a dwelling or sleeping unit in an occupancy in Group R.
3. A fire-resistance rating is not required for corridors in open parking garages.
4. A fire-resistance rating is not required for corridors in an occupancy in Group B which is a space requiring only a single means of egress complying with Section 1015.1.

TABLE 1018.1 CORRIDOR FIRE-RESISTANCE RATING

OCCUPANCYOCCUPANT LOAD SERVED BY CORRIDORREQUIRED FIRE-RESISTANCE RATING (hours)
Without sprinkler systemWith sprinkler systemc
H-1, H-2, H-3 All Not Permitted 1
H-4, H-5 Greater than 30 Not Permitted 1
A, B, E, F, M, S, U Greater than 30 1 0
R Greater than 10 Not Permitted 0.5
I-2a, I-4 All Not Permitted 0
I-1, I-3 All Not Permitted 1b

a.For requirements for occupancies in Group I-2, see Sections 407.2 and 407.3.
b.For a reduction in the fire-resistance rating for occupancies in Group I-3, see Section 408.8.
c.Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 where allowed.

780 CMR, 1018.1