Exits shall be so located on each story such that the maximum length of exitaccess travel, measured from the most remote point within a story along the natural and unobstructed path of egress travel to an exterior exit door at the level of exit discharge, an entrance to a vertical exit enclosure, an exit passageway, a horizontal exit, an exteriorexitstairway or an exterior exitramp, shall not exceed the distances given in Table 1016.1.
Exceptions:
Where applicable, travel distance on unenclosed exitaccessstairways or ramps and on connecting stories shall also be included in the travel distance measurement. The measurement along stairways shall be made on a plane parallel and tangent to the stair tread nosings in the center of the stairway.
TABLE 1016.1 EXIT ACCESS TRAVEL DISTANCEa
OCCUPANCY | WITHOUT SPRINKLER SYSTEM (feet) | WITH SPRINKLER SYSTEM (feet) |
A, E, F-1, M, R, S-1 | 200 | 250b |
I-1 | Not Permitted | 250c |
B | 200 | 300c |
F-2, S-2, U | 300 | 400c |
H-1 | Not Permitted | 75c |
H-2 | Not Permitted | 100c |
H-3 | Not Permitted | 150c |
H-4 | Not Permitted | 175c |
H-5 | Not Permitted | 200c |
I-2, I-3, I-4 | Not Permitted | 200c |
For SI: 1 foot = 304.8 mm. a. See the following sections for modifications to exit access travel distance requirements: Section 402.4: For the distance limitation in malls. Section 404.9: For the distance limitation through an atrium space. Section 407.4: For the distance limitation in Group I-2. Sections 408.6.1 and 408.8.1: For the distance limitations in Group I-3. Section 411.4: For the distance limitation in special amusement buildings. Section 1014.2.2: For the distance limitation in Group I-2 hospital suites. Section 1015.4: For the distance limitation in refrigeration machinery rooms. Section 1015.5: For the distance limitation in refrigerated rooms and spaces. Section 1021.2: For buildings with one exit. Section 1028.7: For increased limitation in assembly seating. Section 1028.7: For increased limitation for assembly open-air seating. Section 3103.4: For temporary structures. Section 3104.9: For pedestrian walkways. b. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. See Section 903 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.2. c. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. |
780 CMR, 1016.1