Two exits or exit access doorways from any space shall be provided where one of the following conditions exists:
Exception: Group I-2 occupancies shall comply with Section 1014.2.2 through 1014.2.7.
Exception: In Group R-2 and R-3 occupancies, one means of egress is permitted within and from individual dwelling units with a maximum occupant load of 20 where the dwelling unit is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
Where a building contains mixed occupancies, each individual occupancy shall comply with the applicable requirements for that occupancy. Where applicable, cumulative occupant loads from adjacent occupancies shall be considered in accordance with the provisions of Section 1004.1.
TABLE 1015.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY
OCCUPANCY | MAXIMUM OCCUPANT LOAD |
A, B, Ea, F, M, U | 49 |
H-1, H-2, H-3 | 3 |
H-4, H-5, I-1, I-3, I-4, R | 10 |
S | 29 |
a. Day care maximum occupant load is 10. |
780 CMR, 1015.1