All Limited use/Limited Application Elevators in Massachusetts are required to comply with the provisions of 521 CMR 28.1 through 28.13.5 (Architectural Access Board Regulations).
Section 5.2.1 Electric Limited-use/Limited-application Elevators
Add a prefatory section:
5.2.1 Electric Limited-use/Limited-application Elevators. All limited-use/limited-application elevators shall comply with the provisions of 521 CMR as applicable.
5.2.1.1.2 Delete (a) and renumber (b) and (c) as (a) and (b).
5.2.1.4.1 Bottom Car Clearance. Delete and replace with:
5.2.1.4.1 Bottom Car Clearance. Elevators shall conform to 2.4.1.
5.2.1.4.2 through 5.2.1.4.2.2 Delete.
5.2.1.11 Protection of Hoistway Landing Openings. Add a new (f), (g), and (h) that read:
5.2.1.13 Power Operation of Hoistway Doors and Car Doors and Gates. Delete and replace with:
5.2.1.13 Power Operation of Hoistway Doors and Car Doors and Gates. Power operation shall be as described in the applicable provisions of 521 CMR: Architectural Access Board.
5.2.1.14 Car Enclosures, Car Doors, and Car Illumination. Delete (f) and replace with:
5.2.1.14 Car Enclosures, Car Doors, and Car Illumination. Add a new (n) that reads:
EXCEPTION: If an emergency generator provides emergency car lighting within ten seconds after power failure, a battery operated lighting unit is not required.
5.2.2.7 Valves, Pressure piping and Fittings. Delete and replace with:
5.2.2.7 Valves, Pressure piping and Fittings. Valves, pressure piping, and fittings shall conform to 3.19 except 3.19.3.3. A flexible hose is prohibited between the power unit and the jack.
524 CMR 5.2