Section 10.22 - Boiler Discharge to the Building Drainage System
(1)General.
(a) Water entering the building drainage system shall not exceed 150 °F.
(b) The pressure of boiler discharge into the building drainage system shall not exceed five PSI.
(c) Steam discharge shall not be directly connected to a building, drainage system but shall first pass through a proper drain water tempering system or device.
(d) Potable water connection to blow-off tank must be properly protected by a backflow preventer.
(e) Types of devices shall include, but not be limited to, boiler blow-off tanks, automatic cooling facilities and drain water tempering devices.

Figure 1: Illustration of Boiler Blow off Tank

Click to view image