Example 1 - Crown Venting
Exception:
Example 2 - Wet Vent Extension of a Horizontal Drain
10.16: Example 3 - Offsets of More Than 45°
Example 4 - Vent Extension Through Roof
Example 5 - Vent Extension Through Observation Deck or Similar
Example 6 - Location of Vent Terminal
Example 7 - Vent Terminal from Forced Air Inlet
Exception: For remodeling and alteration work only, vents may be installed outside the building when all other means of venting have been eliminated or are not practical and with prior permission of the Inspector.
The lowest portion of the pipe serving as a wet vent shall break the centerline of the horizontal drain it serves. See 10.16: Example 11.
Example 10 - Miscellaneous Wet Venting
Example 11 - Wet Venting Breaking the Centerline
Example 12 - Miscellaneous Stack Venting
Stack Venting Top Floor
Stack Venting Top Floor with Estabrook
Stack Venting Lower Floors
Example 13 - Miscellaneous Types Venting
Drawing 1.
Drawing 2.
Relief Vent Necessary Per 10.16 Table 1
Drawing 3.
See248 CMR 10.16(7)(c)
Exception: Fixtures connecting to each parallel horizontal branch shall be sized based on 50% of the fixture units permitted on a horizontal branch for a battery drainage system.
Example 14 - Battery Venting Installations
Example 15 - Circuit and Loop VentingSee 10.03: Definition of Circuit Vent and Loop Vent
Example 16 - Typical Bow Vent Installations
Table 1
Distance of Fixture Trap from Vent
Diameter of Pipe | Maximum Developed Length of the Pipe |
11/2 | 5" |
2 | 6' |
3 | 8' |
4 | 10' |
Slope not to exceed 1/4" per foot |
Table 2
Size and Lengths of Vents
Diameter of Soil or Waste Stack or Branch in Inches | Total Fixture Units Connected to Stack or Branch in Fixture Units | ||||||||||
11/4 | 11/2 | 2 | 21/2 | 3 | 4 | 5 | 6 | 8 | 10 | ||
11/2 | 4 | 50 | 150 | ||||||||
2 | 10 | 25 | 50 | 150 | |||||||
21/2 | 28 | 30 | 100 | 300 | |||||||
3 | 7 | 42 | 150 | 360 | 1040 | ||||||
3 | 21 | 32 | 110 | 270 | 810 | ||||||
3 | 53 | 27 | 94 | 230 | 680 | ||||||
3 | 102 | 25 | 86 | 210 | 620 | ||||||
4 | 43 | 35 | 85 | 250 | 980 | ||||||
4 | 140 | 27 | 65 | 200 | 750 | ||||||
4 | 320 | 23 | 55 | 170 | 640 | ||||||
4 | 530 | 21 | 50 | 150 | 580 | ||||||
5 | 190 | 28 | 82 | 320 | 990 | ||||||
5 | 490 | 21 | 63 | 250 | 760 | ||||||
5 | 940 | 18 | 53 | 210 | 640 | ||||||
5 | 1,400 | 16 | 49 | 190 | 590 | ||||||
6 | 500 | 33 | 130 | 400 | 1,000 | ||||||
6 | 1,100 | 26 | 100 | 310 | 780 | ||||||
6 | 2,000 | 22 | 84 | 260 | 660 | ||||||
6 | 2,900 | 20 | 77 | 240 | 600 | ||||||
8 | 1,800 | 31 | 95 | 240 | 940 | ||||||
8 | 3,400 | 24 | 73 | 190 | 720 | ||||||
8 | 5,600 | 20 | 62 | 160 | 610 | ||||||
8 | 7,600 | 18 | 56 | 140 | 560 | ||||||
10 | 4,000 | 31 | 78 | 310 | 960 | ||||||
10 | 7,200 | 24 | 60 | 240 | 740 | ||||||
10 | 11,000 | 20 | 51 | 200 | 630 | ||||||
10 | 15,000 | 18 | 46 | 180 | 570 |
Note 1: Table 2 shall also apply to the sizing of vents for branch soil and waste lines.
To determine size of vent, use the following procedure:
Table 3
Size and Lengths of Sump Vents2
Diameter of Drain to Sump1 | Diameter of Vent (inches) | ||||||||||
1A | 1A | 2 | 2A | 3 | 4 | 5 | 6 | 8 | 10 | 12 | |
2 | 23 | 52 | 290 | ||||||||
2A | 5 | 13 | 89 | 290 | |||||||
3 | 2 | 30 | 110 | 290 | |||||||
4 | 1 | 17 | 57 | 280 | |||||||
5 | 10 | 80 | 280 | ||||||||
6 | 20 | 97 | 280 | ||||||||
8 | 3 | 41 | 270 | ||||||||
10 | 1 | 53 | 250 | ||||||||
12 | 61 | 230 |
Note 1: Where more than one drain connects to the sump, size vent on the basis of a drain diameter having a cross sectional area equal to the sum of the areas of the multiple drains.
Note 2: The above values provide for a maximum of one-inch pressure drop in the system.
Example 17
Individual Venting - Wet Venting - Stack venting
248 CMR, § 10.16