Current through Register 1536, December 6, 2024
Section 150.390 - Utility Rooms - Nursing Care Units(A)Separate Clean and Soiled Rooms Required. Each unit shall contain separate clean and soiled utility rooms which shall not be interconnected but shall have separate entrances off the corridor.(B)Clean Utility Room. The clean utility room shall contain wall hung and base cabinets. The base cabinet shall be equipped with a counter top and sink with hot and cold running water and a gooseneck spout. The minimum area shall be 70-square feet with no dimension less than six feet.(C)Soiled Utility Room. The soiled utility room shall contain a service sink with gooseneck faucet and hot and cold running water; either a clinical service sink or a device to ensure adequate waste disposal, and washing and sanitizing of equipment; and a work counter with contiguous space at least 24 inches wide and 36 inches high by four feet long. Handwashing facilities shall be provided. The minimum area shall be 70-square feet with no dimension less than six feet.(D) Smaller dimensions maybe approved for HB/LTCFs and long term care facility with 20 or fewer single-occupancy resident bedrooms per unit and no multi-bed rooms.Adopted by Mass Register Issue 1361, eff. 3/23/2018.Amended by Mass Register Issue 1440, eff. 4/2/2021.