Table 193.50-10(a)-Carriage of Portable Fire Extinguisher and Semi-Portable Fire Extinguishing Systems
Space | Minimum required rating | Quantity and location |
Safety Areas | ||
Wheelhouse or fire control room | None. | |
Stairway and elevator enclosures | None. | |
Communicating corridors | 2-A | 1 in each main corridor not more than 150 ft apart. (May be located in stairways.) |
Lifeboat embarkation and lowering stations | None. | |
Radio room | 20-B:C1 | 2 in the vicinity of the exit.1 |
Accommodations | ||
Staterooms, toilet spaces, public spaces, offices, lockers, isolated storerooms, pantries, open decks, etc | None. | |
Service Spaces | ||
Galleys | 40-B:C | 1 for each 2,500 sq ft or fraction thereof. |
Machinery Spaces | ||
Paint and lamp rooms | 40-B | 1 outside space in the vicinity of the exit. |
Accessible baggage, mail, and specie rooms, and storerooms | 2-A | 1 for each 2,500 sq ft or fraction thereof located in the vicinity of the exits, either inside or outside the spaces. |
Carpenter shop and similar spaces | 2-A | 1 outside the space in the vicinity of the exit. |
Coal-fired boilers: Bunker and boiler space | None. | |
Oil-fired boilers: Spaces containing oil-fired boilers, either main or auxiliary, or their fuel-oil units | 40-B | 2 required.2 |
160-B | 1 required.3 | |
Internal combustion or gas turbine propelling machinery spaces | 40-B | 1 for each 1,000 brake horsepower, but not fewer than 2 nor more than 6.4 |
120-B | 1 required.5 6 | |
Electric propulsive motors or generators of open type | 40-B:C | 1 for each propulsion motor or generator unit. |
Enclosed ventilating systems for motors and generators of electric propelling machinery | None. | |
Auxiliary Spaces | ||
Internal combustion gas turbine | 40-B | 1 outside the space in vicinity of the exit.6 |
Electric emergency motors or generators | 40-B:C | 1 outside the space in vicinity of the exit.7 |
Steam | None required. | |
Trunks to machinery spaces | None required. | |
Fuel tanks | None required. | |
Scientific Spaces | ||
Chemistry laboratory or scientific laboratory | 40-B:C | 2 for each 300 sq ft of deck space or fraction thereof, with one (1) of each kind located in the vicinity of the exit. |
Chemical storeroom | 40-B:C | Same as for the chemistry laboratory. |
Spare Units | ||
2-A | 10 percent of required units rounded up. | |
40-B:C | 10 percent of required units rounded up. |
1 For vessels on an international voyage, substitute one 40-B:C in vicinity of the exit.
2 Vessels of fewer than 1,000 GT require one.
3 Vessels of fewer than 1,000 GT may substitute one 120-B.
4 Only one required for motorboats.
5 If oil burning donkey boiler fitted in space, the 160-B previously required for the protection of the boiler may be substituted. Not required where a fixed carbon dioxide system is installed.
6 Not required on vessels of fewer than 300 GT if fuel has a flash-point higher than 110 °F.
7 Not required on vessels of fewer than 300 GT.
46 C.F.R. §193.50-10