46 C.F.R. § 164.007-5

Current through May 31, 2024
Section 164.007-5 - Test requirements

The insulation value of the specimens for the full scale test shall be such that the average temperature of the thermocouples on the unexposed surface described in § 164.007-4(f)(2) will not rise more than 139 °C. (250 °F.) above the initial temperature, nor will the temperature at any one point on the surface, including any through metallic connection, rise more than 181 °C. (325 °F.) above the original temperature at the end of 60 minutes. The results obtained on the small scale test 2' * 2' (60 cm. * 60 cm.) shall be recorded.

46 C.F.R. §164.007-5