46 C.F.R. § 154.1120

Current through October 31, 2024
Section 154.1120 - Nozzles
(a) Nozzles for the water spray system must be spaced to provide the minimum discharge density under § 154.1115 in each part of the protected area.
(b) The vertical distance between water spray nozzles for the protection of vertical surfaces must be 3.7 m (12 ft.) or less.

46 C.F.R. §154.1120