46 C.F.R. § 131.899

Current through May 31, 2024
Section 131.899 - Fire dampers

Each fire damper installed within the boundary of a space protected by a fixed fire extinguishing system must be fitted with an indicator showing whether the damper is open or closed and must be marked with red letters at least 13 millimeters ( 1/2 -inch) high stating "FIRE DAMPER" and, as otherwise appropriate, identifying the space served by the fire damper.

46 C.F.R. § 131.899