46 C.F.R. § 129.323

Current through May 31, 2024
Section 129.323 - Multiple generators

If an OSV uses two or more generators to supply electricity for the ship's service loads, to comply with § 129.310(a) of this subpart, the following requirements must be met:

(a) Each generator must have an independent prime mover.
(b) The circuit breaker of a generator to be operated in parallel with another generator must comply with §§ 111.12-11(f) , 111.30-19(a) , and 111.30-25(d) of this chapter.
(c) The circuit breaker of a generator not to be operated in parallel with another generator must be interlocked to prevent that generator from being connected to the switchboard simultaneously with another.

46 C.F.R. §129.323