46 C.F.R. § 111.60-7

Current through September 30, 2024
Section 111.60-7 - Demand loads

Generator, feeder, and bus-tie cables must be selected on the basis of a computed load of not less than the demand load given in Table 111.60-7.

Table 1 to § 111.60-7 -Demand Loads

Type of circuitDemand load
Generator Cables115 percent of continuous generator rating.
Switchboard bus-ties, except ship's service to emergency switchboard bus-ties75 percent of generating capacity of the larger switchboard.
Emergency switchboard bus-ties115 percent of continuous rating of emergency generator.
Motor feedersArticle 430 of NFPA 70 (incorporated by reference; see § 110.10-1 of this subchapter).
Galley equipment feeders100 percent of either the first 50 kW or one-half the connected load, whichever is the larger, plus 65 percent of the remaining connected load, plus 50 percent of the rating of the spare switches or circuit breakers on the distribution panel.
Lighting feeders100 percent of the connected load plus the average active circuit load for the spare switches or circuit breakers on the distribution panels.
Grounded neutral of a dual voltage feeders100 percent of the capacity of the ungrounded conductors when grounded neutral is not protected by a circuit breaker overcurrent trip, or not less than 50 percent of the capacity of the ungrounded conductors when the grounded neutral is protected by a circuit breaker overcurrent trip or overcurrent alarm.

46 C.F.R. §111.60-7

CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2004-18884, 69 FR 58348, Sept. 30, 2004; USCG-2003-16630, 73 FR 65198, Oct. 31, 2008
88 FR 16364, 4/17/2023