46 C.F.R. § 111.51-3

Current through May 31, 2024
Section 111.51-3 - Short-circuit calculations for systems below 1500 kilowatts

The following short-circuit assumptions must be made for a system with an aggregate generating capacity below 1500 kilowatts, unless detailed computations in accordance with § 111.51-4 are submitted:

(a) The maximum short-circuit current of a direct current system must be assumed to be 10 times the aggregate normal rated generator currents plus 6 times the aggregate normal rated currents of all motors that may be in operation.
(b) The maximum asymmetrical short-circuit current for an alternating current system must be assumed to be 10 times the aggregate normal rated generator currents plus 4 times the aggregate normal rated currents of all motors that may be in operation.
(c) The average asymmetrical short circuit current for an alternating-current system must be assumed to be 81/2 times the aggregate normal rated generator currents plus 31/2 times the aggregate normal rated currents of all motors that may be in operation.

46 C.F.R. §111.51-3

88 FR 16362, 4/17/2023