Current through September 30, 2024
Section 111.30-24 - Generation systems greater than 3000 kWExcept on a non-self-propelled mobile offshore drilling unit (MODU) and a non-self-propelled floating Outer Continental Shelf facility, when the total installed electric power of the ship's service generation system is more than 3000 kW, the switchboard must have the following:
(a) At least two sections of the main bus that are connected by:(1) A non-automatic circuit breaker;(2) A disconnect switch; or(b) As far as practicable, the connection of generators and duplicated equipment equalized between the sections of the main bus.CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28279, June 4, 1996